Herman C Lau
2008-Dec-31 05:31 UTC
[Nut-upsuser] Unknown product ID for Tripp-Lite UPS (SU1500RTXL2UA)
To all, I attempted to configure the UPS tools for the Tripp-Lite SmartOnline 1500VA 2U rackmount UPS. I followed the instructions from the 'upsdrvctl start' output and posted the diagnostic information below. Is my UPS using an unknown product ID as reported? From the mailing list archive, I have found another posting for the same UPS with device model '09AE/4003', whereas mine is '09AE/4001'. Content of ups.conf: [su1500] driver = usbhid-ups port = /dev/usb/hiddev0 desc = "Tripp Lite SmartOnline 1500VA" Output from staring upsdrvctl: herman at herman-desktop:/lib/nut$ sudo /sbin/upsdrvctl start Network UPS Tools - UPS driver controller 2.2.2 Network UPS Tools: 0.29 USB communication driver - core 0.33 (2.2.2) This Tripp Lite device (09ae:4001) is not (or perhaps not yet) supported by usbhid-ups. Please make sure you have an up-to-date version of NUT. If this does not fix the problem, try running the driver with the '-x productid=4001' option. Please report your results to the NUT user's mailing list <nut-upsuser at lists.alioth.debian.org>. Output from running usbhid-ups with '-x productid=4001' option: herman at herman-desktop:/lib/nut$ sudo /lib/nut/usbhid-ups -a su1500 -u root -DD -x productid=4001 Network UPS Tools: 0.29 USB communication driver - core 0.33 (2.2.2) debug level is '2' upsdrv_initups... Checking device (1D6B/0002) (005/001) - VendorID: 1d6b - ProductID: 0002 - Manufacturer: Linux 2.6.27-9-generic ehci_hcd - Product: EHCI Host Controller - Serial Number: 0000:00:1d.7 - Bus: 005 Trying to match device Device does not match - skipping Checking device (1D6B/0001) (002/001) - VendorID: 1d6b - ProductID: 0001 - Manufacturer: Linux 2.6.27-9-generic uhci_hcd - Product: UHCI Host Controller - Serial Number: 0000:00:1d.1 - Bus: 002 Trying to match device Device does not match - skipping Checking device (045E/0053) (001/003) - VendorID: 045e - ProductID: 0053 - Manufacturer: Microsoft - Product: Microsoft 3-Button Mouse with IntelliEye(TM) - Serial Number: unknown - Bus: 001 Trying to match device Device does not match - skipping Checking device (1D6B/0001) (001/001) - VendorID: 1d6b - ProductID: 0001 - Manufacturer: Linux 2.6.27-9-generic uhci_hcd - Product: UHCI Host Controller - Serial Number: 0000:00:1d.0 - Bus: 001 Trying to match device Device does not match - skipping Checking device (1D6B/0001) (004/001) - VendorID: 1d6b - ProductID: 0001 - Manufacturer: Linux 2.6.27-9-generic uhci_hcd - Product: UHCI Host Controller - Serial Number: 0000:00:1d.3 - Bus: 004 Trying to match device Device does not match - skipping Checking device (09AE/4001) (003/003) - VendorID: 09ae - ProductID: 4001 - Manufacturer: Tripp Lite - Product: UPS - Serial Number: - Bus: 003 Trying to match device Device matches failed to claim USB device, trying 2 more time(s)... detaching kernel driver from USB device... trying again to claim USB device... HID descriptor length 1004 Report Descriptor size = 1004 Using subdriver: TrippLite HID 0.2 (experimental) Path: UPS.PowerSummary.iProduct, Type: Feature, ReportID: 0x28, Offset: 0, Size: 8, Value: 6.000000 Path: UPS.PowerSummary.iSerialNumber, Type: Feature, ReportID: 0x29, Offset: 0, Size: 8, Value: 20.000000 Path: UPS.PowerSummary.iManufacturer, Type: Feature, ReportID: 0x2b, Offset: 0, Size: 8, Value: 4.000000 Path: UPS.PowerSummary.Input.ConfigVoltage, Type: Feature, ReportID: 0x30, Offset: 0, Size: 8, Value: 120.000000 Path: UPS.PowerSummary.Input.Voltage, Type: Feature, ReportID: 0x31, Offset: 0, Size: 16, Value: 122.800000 Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, ReportID: 0x11, Offset: 0, Size: 8, Value: 2.000000 Path: UPS.PowerSummary.iDeviceChemistry, Type: Feature, ReportID: 0x2a, Offset: 0, Size: 8, Value: 10.000000 Path: UPS.PowerSummary.iOEMInformation, Type: Feature, ReportID: 0x62, Offset: 0, Size: 8, Value: 4.000000 Path: UPS.PowerSummary.CapacityMode, Type: Feature, ReportID: 0x33, Offset: 0, Size: 8, Value: 2.000000 Path: UPS.PowerSummary.RemainingCapacity, Type: Input, ReportID: 0x34, Offset: 0, Size: 8, Value: 100.000000 Path: UPS.PowerSummary.RemainingCapacity, Type: Feature, ReportID: 0x34, Offset: 0, Size: 8, Value: 100.000000 Path: UPS.PowerSummary.RemainingCapacityLimit, Type: Feature, ReportID: 0x3a, Offset: 0, Size: 8, Value: 25.000000 Path: UPS.PowerSummary.FullChargeCapacity, Type: Feature, ReportID: 0x37, Offset: 0, Size: 8, Value: 100.000000 Path: UPS.PowerSummary.DesignCapacity, Type: Feature, ReportID: 0x36, Offset: 0, Size: 8, Value: 100.000000 Path: UPS.PowerSummary.WarningCapacityLimit, Type: Feature, ReportID: 0x38, Offset: 0, Size: 8, Value: 50.000000 Path: UPS.PowerSummary.CapacityGranularity1, Type: Feature, ReportID: 0x3b, Offset: 0, Size: 8, Value: 1.000000 Path: UPS.PowerSummary.CapacityGranularity2, Type: Feature, ReportID: 0x39, Offset: 0, Size: 8, Value: 1.000000 Path: UPS.PowerSummary.Rechargeable, Type: Feature, ReportID: 0x2c, Offset: 0, Size: 8, Value: 1.000000 Path: UPS.PowerSummary.PresentStatus.InternalFailure, Type: Input, ReportID: 0x32, Offset: 7, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.ShutdownImminent, Type: Input, ReportID: 0x32, Offset: 9, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Input, ReportID: 0x32, Offset: 16, Size: 1, Value: 1.000000 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Input, ReportID: 0x32, Offset: 18, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.FullyCharged, Type: Input, ReportID: 0x32, Offset: 19, Size: 1, Value: 1.000000 Path: UPS.PowerSummary.PresentStatus.Charging, Type: Input, ReportID: 0x32, Offset: 20, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Input, ReportID: 0x32, Offset: 21, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.FullyDischarged, Type: Input, ReportID: 0x32, Offset: 22, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID: 0x32, Offset: 23, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.InternalFailure, Type: Feature, ReportID: 0x32, Offset: 7, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.ShutdownImminent, Type: Feature, ReportID: 0x32, Offset: 9, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x32, Offset: 16, Size: 1, Value: 1.000000 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x32, Offset: 18, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.FullyCharged, Type: Feature, ReportID: 0x32, Offset: 19, Size: 1, Value: 1.000000 Path: UPS.PowerSummary.PresentStatus.Charging, Type: Feature, ReportID: 0x32, Offset: 20, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Feature, ReportID: 0x32, Offset: 21, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.FullyDischarged, Type: Feature, ReportID: 0x32, Offset: 22, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Feature, ReportID: 0x32, Offset: 23, Size: 1, Value: 0.000000 Path: UPS.BatterySystem.Battery.ConfigVoltage, Type: Feature, ReportID: 0x04, Offset: 0, Size: 16, Value: 48.000000 Path: UPS.BatterySystem.Battery.Voltage, Type: Feature, ReportID: 0x20, Offset: 0, Size: 16, Value: 52.400000 Path: UPS.BatterySystem.Battery.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x23, Offset: 2, Size: 1, Value: 0.000000 Path: UPS.BatterySystem.Battery.PresentStatus.FullyCharged, Type: Feature, ReportID: 0x23, Offset: 3, Size: 1, Value: 1.000000 Path: UPS.BatterySystem.Battery.PresentStatus.Charging, Type: Feature, ReportID: 0x23, Offset: 4, Size: 1, Value: 0.000000 Path: UPS.BatterySystem.Battery.PresentStatus.Discharging, Type: Feature, ReportID: 0x23, Offset: 5, Size: 1, Value: 0.000000 Path: UPS.BatterySystem.Battery.PresentStatus.FullyDischarged, Type: Feature, ReportID: 0x23, Offset: 6, Size: 1, Value: 0.000000 Path: UPS.BatterySystem.Battery.PresentStatus.NeedReplacement, Type: Feature, ReportID: 0x23, Offset: 7, Size: 1, Value: 0.000000 Path: UPS.BatterySystem.Battery.RemainingCapacity, Type: Feature, ReportID: 0x21, Offset: 0, Size: 8, Value: 100.000000 Path: UPS.BatterySystem.Test, Type: Feature, ReportID: 0x10, Offset: 0, Size: 8, Value: 1.000000 Path: UPS.BatterySystem.Temperature, Type: Feature, ReportID: 0x1a, Offset: 0, Size: 16, Value: 296.000000 Path: UPS.Flow.ConfigVoltage, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 120.000000 Path: UPS.Flow.ConfigFrequency, Type: Feature, ReportID: 0x02, Offset: 0, Size: 8, Value: 60.000000 Can't retrieve Report 85: Broken pipe Path: UPS.Flow.ffff0097, Type: Feature, ReportID: 0x55, Offset: 0, Size: 8 Path: UPS.Flow.ConfigApparentPower, Type: Feature, ReportID: 0x03, Offset: 0, Size: 16, Value: 1500.000000 Path: UPS.PowerConverter.Input.Voltage, Type: Feature, ReportID: 0x18, Offset: 0, Size: 16, Value: 122.800000 Path: UPS.PowerConverter.Input.Frequency, Type: Feature, ReportID: 0x19, Offset: 0, Size: 16, Value: 59.900000 Path: UPS.PowerConverter.Output.Voltage, Type: Feature, ReportID: 0x1b, Offset: 0, Size: 16, Value: 120.200000 Path: UPS.PowerConverter.Output.Frequency, Type: Feature, ReportID: 0x1c, Offset: 0, Size: 16, Value: 59.900000 Path: UPS.PowerConverter.Output.Current, Type: Feature, ReportID: 0x46, Offset: 0, Size: 16, Value: 0.000000 Path: UPS.PowerConverter.Output.ActivePower, Type: Feature, ReportID: 0x47, Offset: 0, Size: 16, Value: 0.000000 Path: UPS.PowerConverter.Output.LowVoltageTransfer, Type: Feature, ReportID: 0x06, Offset: 0, Size: 16, Value: 65.000000 Path: UPS.PowerConverter.Output.HighVoltageTransfer, Type: Feature, ReportID: 0x09, Offset: 0, Size: 16, Value: 138.000000 Path: UPS.PowerConverter.Output.TLLowVoltageTransferMax, Type: Feature, ReportID: 0x07, Offset: 0, Size: 16, Value: 70.000000 Path: UPS.PowerConverter.Output.TLLowVoltageTransferMin, Type: Feature, ReportID: 0x08, Offset: 0, Size: 16, Value: 65.000000 Path: UPS.PowerConverter.Output.TLHighVoltageTransferMax, Type: Feature, ReportID: 0x0a, Offset: 0, Size: 16, Value: 138.000000 Path: UPS.PowerConverter.Output.TLHighVoltageTransferMin, Type: Feature, ReportID: 0x0b, Offset: 0, Size: 16, Value: 133.000000 Path: UPS.PowerConverter.PresentStatus.VoltageOutOfRange, Type: Feature, ReportID: 0x22, Offset: 0, Size: 1, Value: 0.000000 Path: UPS.PowerConverter.PresentStatus.Buck, Type: Feature, ReportID: 0x22, Offset: 1, Size: 1, Value: 0.000000 Path: UPS.PowerConverter.PresentStatus.Boost, Type: Feature, ReportID: 0x22, Offset: 2, Size: 1, Value: 0.000000 Path: UPS.PowerConverter.PresentStatus.Overload, Type: Feature, ReportID: 0x22, Offset: 4, Size: 1, Value: 0.000000 Path: UPS.PowerConverter.PresentStatus.Used, Type: Feature, ReportID: 0x22, Offset: 5, Size: 1, Value: 1.000000 Path: UPS.PowerConverter.PresentStatus.OverTemperature, Type: Feature, ReportID: 0x22, Offset: 6, Size: 1, Value: 0.000000 Path: UPS.PowerConverter.PresentStatus.InternalFailure, Type: Feature, ReportID: 0x22, Offset: 7, Size: 1, Value: 0.000000 Path: UPS.PowerConverter.PresentStatus.AwaitingPower, Type: Feature, ReportID: 0x22, Offset: 14, Size: 1, Value: 0.000000 Path: UPS.OutletSystem.Outlet.DelayBeforeShutdown, Type: Feature, ReportID: 0x15, Offset: 0, Size: 16, Value: -1.000000 Path: UPS.OutletSystem.Outlet.DelayBeforeStartup, Type: Feature, ReportID: 0x61, Offset: 0, Size: 16, Value: 0.000000 Path: UPS.OutletSystem.Outlet.DelayBeforeReboot, Type: Feature, ReportID: 0x17, Offset: 0, Size: 16, Value: -1.000000 Path: UPS.OutletSystem.Outlet.ActivePower, Type: Feature, ReportID: 0x54, Offset: 0, Size: 16, Value: 0.000000 Path: UPS.OutletSystem.Outlet.PercentLoad, Type: Feature, ReportID: 0x1e, Offset: 0, Size: 8, Value: 0.000000 Path: UPS.OutletSystem.Outlet.ffff0056, Type: Feature, ReportID: 0x16, Offset: 0, Size: 16, Value: 0.000000 Path: UPS.OutletSystem.Outlet.ffff0081, Type: Feature, ReportID: 0x41, Offset: 0, Size: 8, Value: 0.000000 Path: UPS.OutletSystem.Outlet.ffff0091, Type: Feature, ReportID: 0x51, Offset: 0, Size: 8, Value: 0.000000 Path: UPS.OutletSystem.Outlet.TLWatchdog, Type: Feature, ReportID: 0x52, Offset: 0, Size: 8, Value: 0.000000 Path: UPS.OutletSystem.Outlet.ffff0093, Type: Feature, ReportID: 0x53, Offset: 0, Size: 8, Value: 0.000000 Path: UPS.OutletSystem.Outlet.ffff0094, Type: Feature, ReportID: 0x56, Offset: 0, Size: 8, Value: 1.000000 Path: UPS.OutletSystem.Outlet.ffff0095, Type: Feature, ReportID: 0x67, Offset: 0, Size: 8, Value: 3.000000 Path: UPS.OutletSystem.Outlet.ffff0096, Type: Feature, ReportID: 0x68, Offset: 0, Size: 8, Value: 3.000000 Path: UPS.OutletSystem.Outlet.ffff0098, Type: Feature, ReportID: 0x69, Offset: 0, Size: 8, Value: 0.000000 Can't retrieve Report 106: Broken pipe Path: UPS.OutletSystem.Outlet.ffff0099, Type: Feature, ReportID: 0x6a, Offset: 0, Size: 8 Can't retrieve Report 107: Broken pipe Path: UPS.OutletSystem.Outlet.ffff009a, Type: Feature, ReportID: 0x6b, Offset: 0, Size: 8 Path: UPS.ffff0010.[1].ffff0075, Type: Feature, ReportID: 0x0d, Offset: 0, Size: 8, Value: 8.000000 Path: UPS.ffff0010.[1].ffff0076, Type: Feature, ReportID: 0x0e, Offset: 0, Size: 8, Value: 0.000000 Path: UPS.ffff0010.[1].ffff007c, Type: Feature, ReportID: 0x0f, Offset: 0, Size: 8, Value: 176.000000 Path: UPS.ffff0010.[1].ffff009b, Type: Feature, ReportID: 0x42, Offset: 0, Size: 8, Value: 0.000000 Path: UPS.ffff0010.[1].ffff009c, Type: Feature, ReportID: 0x43, Offset: 0, Size: 8, Value: 1.000000 Path: UPS.ffff0010.[1].ffff007d, Type: Feature, ReportID: 0x6c, Offset: 0, Size: 16, Value: 16385.000000 Report descriptor retrieved (Reportlen = 1004) Found HID device Detected a UPS: Tripp Lite /UPS Path: UPS.PowerSummary.RemainingCapacity, Type: Feature, ReportID: 0x34, Offset: 0, Size: 8, Value: 100.000000 Path: UPS.PowerSummary.RemainingCapacityLimit, Type: Feature, ReportID: 0x3a, Offset: 0, Size: 8, Value: 25.000000 Path: UPS.PowerSummary.WarningCapacityLimit, Type: Feature, ReportID: 0x38, Offset: 0, Size: 8, Value: 50.000000 Path: UPS.BatterySystem.Battery.ConfigVoltage, Type: Feature, ReportID: 0x04, Offset: 0, Size: 16, Value: 48.000000 Path: UPS.BatterySystem.Battery.Voltage, Type: Feature, ReportID: 0x20, Offset: 0, Size: 16, Value: 52.400000 Path: UPS.PowerSummary.iDeviceChemistry, Type: Feature, ReportID: 0x2a, Offset: 0, Size: 8, Value: 10.000000 Path: UPS.BatterySystem.Temperature, Type: Feature, ReportID: 0x1a, Offset: 0, Size: 16, Value: 296.000000 Path: UPS.OutletSystem.Outlet.DelayBeforeStartup, Type: Feature, ReportID: 0x61, Offset: 0, Size: 16, Value: 0.000000 Path: UPS.OutletSystem.Outlet.DelayBeforeShutdown, Type: Feature, ReportID: 0x15, Offset: 0, Size: 16, Value: -1.000000 Path: UPS.OutletSystem.Outlet.DelayBeforeReboot, Type: Feature, ReportID: 0x17, Offset: 0, Size: 16, Value: -1.000000 Path: UPS.BatterySystem.Test, Type: Feature, ReportID: 0x10, Offset: 0, Size: 8, Value: 1.000000 Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, ReportID: 0x11, Offset: 0, Size: 8, Value: 2.000000 Path: UPS.Flow.ConfigApparentPower, Type: Feature, ReportID: 0x03, Offset: 0, Size: 16, Value: 1500.000000 Path: UPS.OutletSystem.Outlet.ActivePower, Type: Feature, ReportID: 0x54, Offset: 0, Size: 16, Value: 0.000000 Path: UPS.OutletSystem.Outlet.PercentLoad, Type: Feature, ReportID: 0x1e, Offset: 0, Size: 8, Value: 0.000000 Path: UPS.OutletSystem.Outlet.TLWatchdog, Type: Feature, ReportID: 0x52, Offset: 0, Size: 8, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.InternalFailure, Type: Feature, ReportID: 0x32, Offset: 7, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.ShutdownImminent, Type: Feature, ReportID: 0x32, Offset: 9, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x32, Offset: 16, Size: 1, Value: 1.000000 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x32, Offset: 18, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.FullyCharged, Type: Feature, ReportID: 0x32, Offset: 19, Size: 1, Value: 1.000000 Path: UPS.PowerSummary.PresentStatus.Charging, Type: Feature, ReportID: 0x32, Offset: 20, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Feature, ReportID: 0x32, Offset: 21, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.FullyDischarged, Type: Feature, ReportID: 0x32, Offset: 22, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Feature, ReportID: 0x32, Offset: 23, Size: 1, Value: 0.000000 Path: UPS.PowerConverter.PresentStatus.VoltageOutOfRange, Type: Feature, ReportID: 0x22, Offset: 0, Size: 1, Value: 0.000000 Path: UPS.PowerConverter.PresentStatus.Buck, Type: Feature, ReportID: 0x22, Offset: 1, Size: 1, Value: 0.000000 Path: UPS.PowerConverter.PresentStatus.Boost, Type: Feature, ReportID: 0x22, Offset: 2, Size: 1, Value: 0.000000 Path: UPS.PowerConverter.PresentStatus.Overload, Type: Feature, ReportID: 0x22, Offset: 4, Size: 1, Value: 0.000000 Path: UPS.PowerConverter.PresentStatus.Used, Type: Feature, ReportID: 0x22, Offset: 5, Size: 1, Value: 1.000000 Path: UPS.PowerConverter.PresentStatus.OverTemperature, Type: Feature, ReportID: 0x22, Offset: 6, Size: 1, Value: 0.000000 Path: UPS.PowerConverter.PresentStatus.InternalFailure, Type: Feature, ReportID: 0x22, Offset: 7, Size: 1, Value: 0.000000 Path: UPS.PowerConverter.PresentStatus.AwaitingPower, Type: Feature, ReportID: 0x22, Offset: 14, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.Input.ConfigVoltage, Type: Feature, ReportID: 0x30, Offset: 0, Size: 8, Value: 120.000000 Path: UPS.PowerSummary.Input.Voltage, Type: Feature, ReportID: 0x31, Offset: 0, Size: 16, Value: 122.800000 Path: UPS.PowerConverter.Input.Frequency, Type: Feature, ReportID: 0x19, Offset: 0, Size: 16, Value: 59.900000 Path: UPS.PowerConverter.Output.LowVoltageTransfer, Type: Feature, ReportID: 0x06, Offset: 0, Size: 16, Value: 65.000000 Path: UPS.PowerConverter.Output.TLLowVoltageTransferMax, Type: Feature, ReportID: 0x07, Offset: 0, Size: 16, Value: 70.000000 Path: UPS.PowerConverter.Output.TLLowVoltageTransferMin, Type: Feature, ReportID: 0x08, Offset: 0, Size: 16, Value: 65.000000 Path: UPS.PowerConverter.Output.HighVoltageTransfer, Type: Feature, ReportID: 0x09, Offset: 0, Size: 16, Value: 138.000000 Path: UPS.PowerConverter.Output.TLHighVoltageTransferMax, Type: Feature, ReportID: 0x0a, Offset: 0, Size: 16, Value: 138.000000 Path: UPS.PowerConverter.Output.TLHighVoltageTransferMin, Type: Feature, ReportID: 0x0b, Offset: 0, Size: 16, Value: 133.000000 Path: UPS.Flow.ConfigVoltage, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 120.000000 Path: UPS.PowerConverter.Output.Voltage, Type: Feature, ReportID: 0x1b, Offset: 0, Size: 16, Value: 120.200000 Path: UPS.PowerConverter.Output.Current, Type: Feature, ReportID: 0x46, Offset: 0, Size: 16, Value: 0.000000 Path: UPS.Flow.ConfigFrequency, Type: Feature, ReportID: 0x02, Offset: 0, Size: 8, Value: 60.000000 Path: UPS.PowerConverter.Output.Frequency, Type: Feature, ReportID: 0x1c, Offset: 0, Size: 16, Value: 59.900000 Path: UPS.BatterySystem.Test, Type: Feature, ReportID: 0x10, Offset: 0, Size: 8, Value: 1.000000 Path: UPS.BatterySystem.Test, Type: Feature, ReportID: 0x10, Offset: 0, Size: 8, Value: 1.000000 Path: UPS.BatterySystem.Test, Type: Feature, ReportID: 0x10, Offset: 0, Size: 8, Value: 1.000000 Path: UPS.OutletSystem.Outlet.DelayBeforeShutdown, Type: Feature, ReportID: 0x15, Offset: 0, Size: 16, Value: -1.000000 Path: UPS.OutletSystem.Outlet.DelayBeforeStartup, Type: Feature, ReportID: 0x61, Offset: 0, Size: 16, Value: 0.000000 Path: UPS.OutletSystem.Outlet.DelayBeforeShutdown, Type: Feature, ReportID: 0x15, Offset: 0, Size: 16, Value: -1.000000 Path: UPS.OutletSystem.Outlet.DelayBeforeReboot, Type: Feature, ReportID: 0x17, Offset: 0, Size: 16, Value: -1.000000 Path: UPS.OutletSystem.Outlet.TLWatchdog, Type: Feature, ReportID: 0x52, Offset: 0, Size: 8, Value: 0.000000 Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, ReportID: 0x11, Offset: 0, Size: 8, Value: 2.000000 Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, ReportID: 0x11, Offset: 0, Size: 8, Value: 2.000000 Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, ReportID: 0x11, Offset: 0, Size: 8, Value: 2.000000 Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, ReportID: 0x11, Offset: 0, Size: 8, Value: 2.000000 Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, ReportID: 0x11, Offset: 0, Size: 8, Value: 2.000000 upsdrv_initinfo... upsdrv_updateinfo... Got -110 HID objects... Quick update... Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x32, Offset: 16, Size: 1, Value: 1.000000 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x32, Offset: 18, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.FullyCharged, Type: Feature, ReportID: 0x32, Offset: 19, Size: 1, Value: 1.000000 Path: UPS.PowerSummary.PresentStatus.Charging, Type: Feature, ReportID: 0x32, Offset: 20, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Feature, ReportID: 0x32, Offset: 21, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.FullyDischarged, Type: Feature, ReportID: 0x32, Offset: 22, Size: 1, Value: 0.000000 dstate_init: sock /var/run/nut/usbhid-ups-su1500 open on fd 5 upsdrv_updateinfo... Got 1 HID objects... Path: UPS.PowerSummary.RemainingCapacity, Type: Input, ReportID: 0x34, Offset: 0, Size: 8, Value: 100.000000 Quick update... Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x32, Offset: 16, Size: 1, Value: 1.000000 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x32, Offset: 18, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.FullyCharged, Type: Feature, ReportID: 0x32, Offset: 19, Size: 1, Value: 1.000000 Path: UPS.PowerSummary.PresentStatus.Charging, Type: Feature, ReportID: 0x32, Offset: 20, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Feature, ReportID: 0x32, Offset: 21, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.FullyDischarged, Type: Feature, ReportID: 0x32, Offset: 22, Size: 1, Value: 0.000000 upsdrv_updateinfo... Got 9 HID objects... Path: UPS.PowerSummary.PresentStatus.InternalFailure, Type: Input, ReportID: 0x32, Offset: 7, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.ShutdownImminent, Type: Input, ReportID: 0x32, Offset: 9, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Input, ReportID: 0x32, Offset: 16, Size: 1, Value: 1.000000 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Input, ReportID: 0x32, Offset: 18, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.FullyCharged, Type: Input, ReportID: 0x32, Offset: 19, Size: 1, Value: 1.000000 Path: UPS.PowerSummary.PresentStatus.Charging, Type: Input, ReportID: 0x32, Offset: 20, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Input, ReportID: 0x32, Offset: 21, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.FullyDischarged, Type: Input, ReportID: 0x32, Offset: 22, Size: 1, Value: 0.000000 Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID: 0x32, Offset: 23, Size: 1, Value: 0.000000
Kjell Claesson
2008-Dec-31 09:45 UTC
[Nut-upsuser] Unknown product ID for Tripp-Lite UPS (SU1500RTXL2UA)
Den Wednesday 31 December 2008 06.31.05 skrev Herman C Lau:> To all, >Hi Herman,> I attempted to configure the UPS tools for the Tripp-Lite SmartOnline > 1500VA 2U rackmount UPS. I followed the instructions from the 'upsdrvctl > start' output and posted the diagnostic information below. > > Is my UPS using an unknown product ID as reported? From the mailing list > archive, I have found another posting for the same UPS with device model > '09AE/4003', whereas mine is '09AE/4001'.The output from the debug run looks OK. so you can try to add the productid to the ups.conf [su1500] driver = usbhid-ups port = /dev/usb/hiddev0 productid = 4001 desc = "Tripp Lite SmartOnline 1500VA" And I think it ignore the port value. so you can set that to auto. Se the : man usbhid-ups Now run it as normal and se if the driver starts and the upsd so you can get some values back with: upsc su1500 Regards Kjell
Arjen de Korte
2008-Dec-31 10:07 UTC
[Nut-upsuser] Unknown product ID for Tripp-Lite UPS (SU1500RTXL2UA)
Citeren Kjell Claesson <kjell.claesson at epost.tidanet.se>:> The output from the debug run looks OK. so you can try to add the > productid to the ups.conf > > [su1500] > driver = usbhid-ups > port = /dev/usb/hiddev0 > productid = 4001 > desc = "Tripp Lite SmartOnline 1500VA"This should work for now. I have added this productid to the list of supported devices, so future releases of NUT should recognise this unit without additional configuration. Thanks for reporting this. Best regards, Arjen -- Please keep list traffic on the list