Displaying 18 results from an estimated 18 matches for "fullydischarged".
2019 Dec 08
3
Tripp Lite SMART1500LCD repeatedly disconnecting and reconnecting
...th:
UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Input,
ReportID: 0x32, Offset: 5, Size: 1, Value: 0
0.143492 Path: UPS.PowerSummary.PresentStatus.FullyCharged, Type:
Input, ReportID: 0x32, Offset: 6, Size: 1, Value: 1
0.143636 Path: UPS.PowerSummary.PresentStatus.FullyDischarged, Type:
Input, ReportID: 0x32, Offset: 7, Size: 1, Value: 0
0.143780 Path: UPS.PowerSummary.PresentStatus.ShutdownImminent,
Type: Feature, ReportID: 0x32, Offset: 0, Size: 1, Value: 0
0.143926 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type:
Feature, ReportID: 0x32, Offset: 1, Siz...
2007 Aug 11
3
[nut-commits] svn commit r1043 - in trunk: . docs drivers
...lf fully charged at less than 100%.
FullyCharged is not precisely an "alarm", as it is not a condition to
be worried about. It is a kind of status. The standard actually
defines four related codes defined: "Charging", "Discharging",
"FullyCharged", and "FullyDischarged". Although some UPS simply
pretend to be "charging" all the time, this is often confusing to
users, who expect that their battery must be full at some point.
It would make sense to me to map all four related codes to status
flags. In fact, precisely one of the four should be true at...
2017 Aug 21
5
TrippLite SMART1500LCD no delay before ups shutdown.
...UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Input,
ReportID: 0x32, Offset: 5, Size: 1, Value: 0
0.147872 Path: UPS.PowerSummary.PresentStatus.FullyCharged, Type:
Input, ReportID: 0x32, Offset: 6, Size: 1, Value: 1
0.147874 Path: UPS.PowerSummary.PresentStatus.FullyDischarged,
Type: Input, ReportID: 0x32, Offset: 7, Size: 1, Value: 0
0.147876 Path: UPS.PowerSummary.PresentStatus.ShutdownImminent,
Type: Feature, ReportID: 0x32, Offset: 0, Size: 1, Value: 0
0.147879 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type:
Feature, ReportID: 0x32, Offset: 1,...
2013 Aug 07
4
HP R1500 G3 problems
...Path: UPS.PowerSummary.PresentStatus.InternalFailure,
Type: Input, ReportID: 0x32, Offset: 0, Size: 1, Value: 0
0.473220 Path: UPS.PowerSummary.PresentStatus.ShutdownImminent,
Type: Input, ReportID: 0x32, Offset: 1, Size: 1, Value: 0
0.473305 Path: UPS.PowerSummary.PresentStatus.FullyDischarged,
Type: Input, ReportID: 0x32, Offset: 2, Size: 1, Value: 0
0.473389 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type:
Input, ReportID: 0x32, Offset: 3, Size: 1, Value: 1
0.473512 Path:
UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Input,
ReportID: 0x32, O...
2008 Dec 31
2
Unknown product ID for Tripp-Lite UPS (SU1500RTXL2UA)
...set: 19, Size: 1, Value: 1.000000
Path: UPS.PowerSummary.PresentStatus.Charging, Type: Input, ReportID: 0x32, Offset: 20, Size: 1, Value: 0.000000
Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Input, ReportID: 0x32, Offset: 21, Size: 1, Value: 0.000000
Path: UPS.PowerSummary.PresentStatus.FullyDischarged, Type: Input, ReportID: 0x32, Offset: 22, Size: 1, Value: 0.000000
Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID: 0x32, Offset: 23, Size: 1, Value: 0.000000
Path: UPS.PowerSummary.PresentStatus.InternalFailure, Type: Feature, ReportID: 0x32, Offset: 7, Size: 1, Value:...
2017 Dec 18
2
Tripp-Lite BCPERS450 shutdown/restart problems
...66798 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Input, ReportID: 0x32, Offset: 5, Size: 1, Value: 0
0.066819 Path: UPS.PowerSummary.PresentStatus.FullyCharged, Type: Input, ReportID: 0x32, Offset: 6, Size: 1, Value: 1
0.066839 Path: UPS.PowerSummary.PresentStatus.FullyDischarged, Type: Input, ReportID: 0x32, Offset: 7, Size: 1, Value: 0
0.066863 Path: UPS.PowerSummary.PresentStatus.ShutdownImminent, Type: Feature, ReportID: 0x32, Offset: 0, Size: 1, Value: 0
0.066886 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x32, Offset: 1, Size: 1, Va...
2007 Feb 26
1
Tripp Lite USB UPS
...t: 19, Size: 1, Value: 0.000000
Path: UPS.PowerSummary.PresentStatus.Charging, Type: Input, ReportID: 0x32,
Offset: 20, Size: 1, Value: 1.000000
Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Input, ReportID: 0x32,
Offset: 21, Size: 1, Value: 0.000000
Path: UPS.PowerSummary.PresentStatus.FullyDischarged, Type: Input, ReportID:
0x32, Offset: 22, Size: 1, Value: 0.000000
Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID:
0x32, Offset: 23, Size: 1, Value: 0.000000
Path: UPS.PowerSummary.PresentStatus.InternalFailure, Type: Feature, ReportID:
0x32, Offset: 7, Size: 1, Valu...
2007 May 13
0
No subject
...;es (and
systems) connected to that same server. We even warn for this in the
documentation:
Note: upsd injects "FSD" by itself following that command by a
master upsmon process. Drivers must not set that value.
> Since we (MGE) don't use the RemainingTimeLimitExpired nor
> FullyDischarged, I can't tell for these ones. But in theory, the
> FullyDischarged flag should also trigger LB.
I discussed this with Peter and we came to the conclusion that
Fully(Dis)Charged indicates the end of (dis)charge and as such should
remove the (DIS)CHRG flag from "ups.status". By that...
2020 Jun 28
2
AVR750U Low Power not Triggering Shutdown
...0.028237 Path: UPS.PowerSummary.PresentStatus.Charging, Type: Input, ReportID: 0x32, Offset: 20, Size: 1, Value: 0
0.028262 Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Input, ReportID: 0x32, Offset: 21, Size: 1, Value: 0
0.028286 Path: UPS.PowerSummary.PresentStatus.FullyDischarged, Type: Input, ReportID: 0x32, Offset: 22, Size: 1, Value: 0
0.028310 Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID: 0x32, Offset: 23, Size: 1, Value: 0
0.028333 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x3...
2008 Jan 02
2
[nut-commits] svn commit r1210 - in trunk: . drivers
On Jan 2, 2008 3:34 PM, Arjen de Korte <adkorte-guest at alioth.debian.org> wrote:
> Author: adkorte-guest
> Date: Wed Jan 2 20:34:26 2008
> New Revision: 1210
>
> Log:
> Parsing continues if the HID path for a report ends in 0x00000000 (these will not be made available). Commonly used as placeholders.
>
> It looks like (but correct me if I'm wrong) that reports
2015 Aug 15
2
Small patch to scale the values for TRIPP-LITE SMART*LCDT's
Hi,
I just decided to fix some scaling issues for my UPS (TRIPP-LITE
SMART1500LCDT). Apparently that issue existed for some time (and I knew
about it as well:-()
See http://thread.gmane.org/gmane.comp.monitoring.nut.devel/6482 for a
thread.
My little patch is attached (against 2.7.3). It seems to be working
better for me but I don't have any other TRIPP-LITE's to test that I did
2015 Aug 15
2
Small patch to scale the values for TRIPP-LITE SMART*LCDT's
Hi,
I just decided to fix some scaling issues for my UPS (TRIPP-LITE
SMART1500LCDT). Apparently that issue existed for some time (and I knew
about it as well:-()
See http://thread.gmane.org/gmane.comp.monitoring.nut.devel/6482 for a
thread.
My little patch is attached (against 2.7.3). It seems to be working
better for me but I don't have any other TRIPP-LITE's to test that I did
2010 Feb 18
2
HP R1500 G2 UPS
...ize: 8, Value: 1.000000
Path: UPS.PowerSummary.PresentStatus.InternalFailure, Type: Input, ReportID: 0x32, Offset: 0, Size: 1, Value: 0.000000
Path: UPS.PowerSummary.PresentStatus.ShutdownImminent, Type: Input, ReportID: 0x32, Offset: 1, Size: 1, Value: 0.000000
Path: UPS.PowerSummary.PresentStatus.FullyDischarged, Type: Input, ReportID: 0x32, Offset: 2, Size: 1, Value: 0.000000
Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Input, ReportID: 0x32, Offset: 3, Size: 1, Value: 1.000000
Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Input, ReportID: 0x32, Offset: 4, Size: 1, Value...
2020 Jun 28
0
AVR750U Low Power not Triggering Shutdown
...Path: UPS.PowerSummary.PresentStatus.Charging, Type: Input, ReportID: 0x32, Offset: 20, Size: 1, Value: 0
> 0.028262 Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Input, ReportID: 0x32, Offset: 21, Size: 1, Value: 0
> 0.028286 Path: UPS.PowerSummary.PresentStatus.FullyDischarged, Type: Input, ReportID: 0x32, Offset: 22, Size: 1, Value: 0
> 0.028310 Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID: 0x32, Offset: 23, Size: 1, Value: 0
> 0.028333 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, R...
2020 Jan 01
2
Tripp Lite SMART1500LCD will not stay shut down when power is disconnected
...th:
UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Input,
ReportID: 0x32, Offset: 5, Size: 1, Value: 0
0.159316 Path: UPS.PowerSummary.PresentStatus.FullyCharged, Type:
Input, ReportID: 0x32, Offset: 6, Size: 1, Value: 1
0.159654 Path: UPS.PowerSummary.PresentStatus.FullyDischarged, Type:
Input, ReportID: 0x32, Offset: 7, Size: 1, Value: 0
0.159998 Path: UPS.PowerSummary.PresentStatus.ShutdownImminent,
Type: Feature, ReportID: 0x32, Offset: 0, Size: 1, Value: 0
0.160316 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type:
Feature, ReportID: 0x32, Offset: 1, Siz...
2020 Jun 28
2
AVR750U Low Power not Triggering Shutdown
...0.028237 Path: UPS.PowerSummary.PresentStatus.Charging, Type: Input, ReportID: 0x32, Offset: 20, Size: 1, Value: 0
> > 0.028262 Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Input, ReportID: 0x32, Offset: 21, Size: 1, Value: 0
> > 0.028286 Path: UPS.PowerSummary.PresentStatus.FullyDischarged, Type: Input, ReportID: 0x32, Offset: 22, Size: 1, Value: 0
> > 0.028310 Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID: 0x32, Offset: 23, Size: 1, Value: 0
> > 0.028333 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportI...
2017 Dec 20
3
Tripp-Lite BCPERS450 shutdown/restart problems
...63595 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Input, ReportID: 0x32, Offset: 5, Size: 1, Value: 0
0.063616 Path: UPS.PowerSummary.PresentStatus.FullyCharged, Type: Input, ReportID: 0x32, Offset: 6, Size: 1, Value: 1
0.063636 Path: UPS.PowerSummary.PresentStatus.FullyDischarged, Type: Input, ReportID: 0x32, Offset: 7, Size: 1, Value: 0
0.063657 Path: UPS.PowerSummary.PresentStatus.ShutdownImminent, Type: Feature, ReportID: 0x32, Offset: 0, Size: 1, Value: 0
0.063679 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature, ReportID: 0x32, Offset: 1, Size: 1, Va...
2007 May 11
11
tripp lite smart2200RMXL2U error reading protocol
I'm working on a gentoo server with Nut 2.0.5-r1 and libusb-0.1.12.
I originally tried the hidups driver which seemed to work, but produced
a large amount of unhandled events. Then I tried the newhidups which
told me my ups wasn't supported. When I try using
tripplite_usb -u root -DDDD /proc/bus/usb/002/002
I get that there isn't a match. But when I try using
tripplite_usb -DDDD