2005 Aug 26
0
NUT patches
...r fixing it). Note that after the places marked ###, the parser shifts all Usages by one, which mangles the tree. This bug is fixed in nut-cvs-patch-PARSER-2005-08-24. ---------------------------------------------------------------------- Before fixing the HIDParser bug: HIDDumpTree... Path: UPS.PowerSummary.iSerialNumber Path: UPS.PowerSummary.iDeviceChemistry Path: UPS.PowerSummary.iOEMInformation Path: UPS.PowerSummary.Rechargeable Path: UPS.PowerSummary.APCStatusFlag Path: UPS.PowerSummary.APCStatusFlag Path: UPS.PowerSummary.ManufacturerDate Path: UPS.PowerSummary.ConfigVoltage Path: UPS.PowerSumm...
2007 Jan 26
1
newhidups output for Geek Squad GS1285U
...s)... detaching kernel driver from USB device... trying again to claim USB device... HID descriptor retrieved (Reportlen = 387) Report descriptor retrieved (Reportlen = 387) Found HID device Report Descriptor size = 387 Detected a UPS: CPS/ GS 1285U Using subdriver: APC/CyberPower HID 0.9 Path: UPS.PowerSummary.iProduct, Type: Feature, Value: 1.000000 Path: UPS.PowerSummary.iSerialNumber, Type: Feature, Value: 2.000000 Path: UPS.PowerSummary.iDeviceChemistry, Type: Feature, Value: 4.000000 Path: UPS.PowerSummary.iOEMInformation, Type: Feature, Value: 3.000000 Path: UPS.PowerSummary.Rechargeable, Type: Fea...
2006 Nov 11
1
Help with newhidups subdriver for Dynex UPS
...e matches HID descriptor retrieved (Reportlen = 374) Report descriptor retrieved (Reportlen = 374) Found HID device Network UPS Tools: 0.28 USB communication driver 0.28 - core 0.30 (2.1.0) Report Descriptor size = 374 Detected a UPS: CPS/DX-800U Using subdriver: APC/CyberPower HID 0.9 Path: UPS.PowerSummary.iProduct, Type: Feature, Value: 1.000000 Path: UPS.PowerSummary.iSerialNumber, Type: Feature, Value: 2.000000 Path: UPS.PowerSummary.iDeviceChemistry, Type: Feature, Value: 4.000000 Path: UPS.PowerSummary.iOEMInformation, Type: Feature, Value: 3.000000 Path: UPS.PowerSummary.Rechargeable, Type: Fea...
2005 Aug 29
1
Belkin and newhidups
...mware: -16 ups.load: 43 ups.mfr: Belkin ups.model: UPS ups.power.nominal: 550 ups.serial: unknown ups.serial.internal: ups.status: OL CHRG ups.test.result: No test initiated ups.type: offline zzz.ups.belkinstatus.belkinbatterystatus: 00000010 zzz.ups.belkinstatus.belkinpowerstatus: 0000c000 zzz.ups.powersummary.capacitygranularity1: 1 zzz.ups.powersummary.capacitygranularity2: 1 zzz.ups.powersummary.capacitymode: 2 zzz.ups.powersummary.configvoltage: 12 zzz.ups.powersummary.current: 0 zzz.ups.powersummary.designcapacity: 100 zzz.ups.powersummary.fullchargecapacity: 100 zzz.ups.powersummary.ioeminformation...
2006 Nov 15
1
Tripp Lite OMNI900LCD
...different HID descriptors retrieved (Reportlen = 459 vs. 618) HID descriptor retrieved (Reportlen = 618) Report descriptor retrieved (Reportlen = 618) Found HID device Report Descriptor size = 618 Detected a UPS: Tripp Lite /TRIPP LITE UPS Using subdriver: TrippLite HID 0.1 (experimental) Path: UPS.PowerSummary.iProduct, Type: Feature, Value: 1.000000 Path: UPS.PowerSummary.iSerialNumber, Type: Feature, Value: 2.000000 Path: UPS.PowerSummary.iManufacturer, Type: Feature, Value: 3.000000 Path: UPS.PowerSummary.Input.ConfigVoltage, Type: Feature, Value: 120.000000 Path: UPS.PowerSummary.AudibleAlarmControl,...
2007 Feb 26
1
Tripp Lite USB UPS
...81 75 08 95 01 26 ff 00 85 0d 09 75 b1 03 85 0e 09 76 b1 03 85 0f 09 7c b1 03 85 42 09 9b b1 82 85 43 09 9c b1 82 85 6c 75 10 27 ff ff 00 00 09 7d b1 82 c0 c0 Detected a UPS: Tripp Lite /TRIPP LITE UPS Using subdriver: TrippLite HID 0.1 (experimental) Report[r]: (2 bytes) => 28 06 Path: UPS.PowerSummary.iProduct, Type: Feature, ReportID: 0x28, Offset: 0, Size: 8, Value: 6.000000 Report[r]: (2 bytes) => 29 14 Path: UPS.PowerSummary.iSerialNumber, Type: Feature, ReportID: 0x29, Offset: 0, Size: 8, Value: 20.000000 Report[r]: (2 bytes) => 2b 04 Path: UPS.PowerSummary.iManufacturer, Type: Feat...
2017 Apr 17
1
New UPS information - Liebert GXT4 via US
...atches 0.004705 failed to claim USB device: could not claim interface 0: Device or resource busy 0.004740 detached kernel driver from USB device... 0.005265 HID descriptor length 505 0.007255 Report Descriptor size = 505 0.007544 Using subdriver: Belkin HID 0.15 0.007767 Path: UPS.PowerSummary.Undefined, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 0 0.008018 Path: UPS.PowerSummary.iSerialNumber, Type: Feature, ReportID: 0x02, Offset: 0, Size: 4, Value: 3 0.008049 Path: UPS.PowerSummary.iManufacturer, Type: Feature, ReportID: 0x02, Offset: 4, Size: 4, Value: 1 0....
2005 Aug 02
0
newhidups for APC Back-UPS ES 650
...d.h nut-2.0.2/drivers/apc-hid.h --- nut-2.0.2.orig/drivers/apc-hid.h 2005-06-22 03:39:36.000000000 -0400 +++ nut-2.0.2/drivers/apc-hid.h 2005-07-25 16:40:46.000000000 -0400 @@ -87,6 +87,11 @@ "%.0f", HU_FLAG_OK, &replacebatt_info[0] }, { "ups.status", 0, 1, "UPS.PowerSummary.PresentStatus.ShutdownImminent", NULL, "%.0f", HU_FLAG_OK, &shutdownimm_info[0] }, + /* The following two are returned with long notification from Back-UPS ES 650 */ + { "ups.status", 0, 1, "UPS.PowerSummary.PresentStatus.RemainingTimeLimitExpired", NUL...
2008 Jan 02
2
[nut-commits] svn commit r1210 - in trunk: . drivers
On Jan 2, 2008 3:34 PM, Arjen de Korte <adkorte-guest at alioth.debian.org> wrote: > Author: adkorte-guest > Date: Wed Jan 2 20:34:26 2008 > New Revision: 1210 > > Log: > Parsing continues if the HID path for a report ends in 0x00000000 (these will not be made available). Commonly used as placeholders. > > It looks like (but correct me if I'm wrong) that reports
2006 Sep 08
3
newhidups with APC Smart-UPS 1500
Hello, I'm using the stable amd64 port of Debian Linux. I installed (the latest) nut-2.0.1-4 and nut-usb packages for utilizing an APC Smart-UPS 1500 USB. I tried "apcupsd" first but "nut" makes an even more sophisticated impression on me and has more security options. I had problems with the newhidups driver. It didn't find a device with matching VendorID. And
2015 Jan 09
0
persistent "low battery" condition
...derstand why. I don't think it's for the reason described in the FAQ (but I'm not 100% sure). I think that FAQ #39 ("My APC UPS keeps reporting OL LB, even after it?s been charging for many hours") refers to a continuous LB state. > In the trace output I can see that UPS.PowerSummary.RunTimeToEmpty is usually around 150 - 170 seconds. Occasionally it drops to 105. I don't see any reason why the load would be changing significantly. In any case, I've set the threshold to 90 seconds in ups.conf. > > See below for debug info. > > If somebody could offer sugge...
2015 Jan 12
2
persistent "low battery" condition
...it's for the reason described in the >> FAQ (but I'm not 100% sure). > > I think that FAQ #39 ("My APC UPS keeps reporting OL LB, even after > it?s been charging for many hours") refers to a continuous LB state. > >> In the trace output I can see that UPS.PowerSummary.RunTimeToEmpty is >> usually around 150 - 170 seconds. Occasionally it drops to 105. I >> don't see any reason why the load would be changing significantly. In >> any case, I've set the threshold to 90 seconds in ups.conf. >> >> See below for debug info. >&g...
2006 Oct 18
2
newhidups with APC Smart-UPS 1500
...> 0.28 > > USB communication driver 0.28 - core 0.30 (2.1.0) > > > > Report Descriptor size = 1040 > > Detected a UPS: American Power Conversion/Smart-UPS 1500 RM > > FW:617.3.I > > > USB FW:1.5 Using subdriver: APC/CyberPower HID 0.9 > > Path: UPS.PowerSummary.iProduct, Type: Feature, Value: 1.000000 > > Path: UPS.PowerSummary.iSerialNumber, Type: Feature, Value: 2.000000 > > Path: UPS.PowerSummary.iManufacturer, Type: Feature, Value: 3.000000 > > Path: UPS.PowerSummary.iOEMInformation, Type: Feature, Value: > > 3.000000 > &gt...
2019 Dec 08
3
Tripp Lite SMART1500LCD repeatedly disconnecting and reconnecting
...Device release number: 0009 0.017430 Trying to match device 0.017736 Device matches 0.021374 HID descriptor length 662 0.111731 Report Descriptor size = 662 0.113247 Using subdriver: TrippLite HID 0.82 0.113406 74 HID objects found 0.115493 Path: UPS.PowerSummary.iProduct, Type: Feature, ReportID: 0x28, Offset: 0, Size: 8, Value: 2 0.117475 Path: UPS.PowerSummary.iSerialNumber, Type: Feature, ReportID: 0x29, Offset: 0, Size: 8, Value: 3 0.119478 Path: UPS.PowerSummary.iManufacturer, Type: Feature, ReportID: 0x2b, Offset: 0, Size: 8, Value: 1...
2015 Jan 09
2
persistent "low battery" condition
...SD port) with an APC Back-UPS CS 350 connected via USB. I get persistent (every few minutes) messages logged "battery is low" but I don't understand why. I don't think it's for the reason described in the FAQ (but I'm not 100% sure). In the trace output I can see that UPS.PowerSummary.RunTimeToEmpty is usually around 150 - 170 seconds. Occasionally it drops to 105. I don't see any reason why the load would be changing significantly. In any case, I've set the threshold to 90 seconds in ups.conf. See below for debug info. If somebody could offer suggestions on how to fix...
2016 May 04
2
New UPS Support: Eaton 5S 1000
...1 5.438016 Path: UPS.PowerConverter.Rectifier.PresentStatus.DCBusUnbalanced, Type: Feature, ReportID: 0x03, Offset: 32, Size: 8, Value: 0 5.438024 Path: UPS.PowerConverter.Rectifier.PresentStatus.DCBusUnbalanced, Type: Input, ReportID: 0x03, Offset: 32, Size: 8, Value: 0 5.481950 Path: UPS.PowerSummary.AudibleAlarmControl, Type: Feature, ReportID: 0x1f, Offset: 0, Size: 8, Value: 2 5.481967 Path: UPS.PowerSummary.CapacityGranularity1, Type: Feature, ReportID: 0x0c, Offset: 16, Size: 8, Value: 1 5.481977 Path: UPS.PowerSummary.CapacityMode, Type: Feature, ReportID: 0x0c, Offset: 24, Size: 8,...
2020 Oct 23
2
Nut-upsuser Digest, Vol 184, Issue 8
...SB device: could not claim interface 0: Device or resource busy 0.012115 detached kernel driver from USB device... 0.013789 HID descriptor length 487 0.018281 Report Descriptor size = 487 0.018987 Using subdriver: CyberPower HID 0.4 0.019108 57 HID objects found 0.021013 Path: UPS.PowerSummary.iProduct, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 1 0.023914 Path: UPS.PowerSummary.iSerialNumber, Type: Feature, ReportID: 0x02, Offset: 0, Size: 8, Value: 2 0.026500 Path: UPS.PowerSummary.ff0100d0, Type: Feature, ReportID: 0x1b, Offset: 0, Size: 8, Value: 5 0.027249 Pa...
2019 Jun 11
2
UPS shuts down on NUT boot with low battery [APS Back-UPS RS 550G]
...ber: 0090 > 0.011822 Trying to match device > 0.012248 Device matches > 0.013822 HID descriptor length 1134 > 0.016761 Report Descriptor size = 1134 > 0.019750 Using subdriver: APC HID 0.96 > 0.019824 112 HID objects found > 0.020801 Path: UPS.PowerSummary.iProduct, Type: Feature, ReportID: 0x01, Offset: 0, Size: 8, Value: 2 > 0.021529 Path: UPS.PowerSummary.iSerialNumber, Type: Feature, ReportID: 0x02, Offset: 0, Size: 8, Value: 3 > 0.022404 Path: UPS.PowerSummary.iDeviceChemistry, Type: Feature, ReportID: 0x03, Offset: 0, Size: 8, V...
2016 May 03
2
New UPS Support: Eaton 5S 1000
Oops... changing that to --with-user=nut solved one problem. I have the driver, upsd and upsmon running now. Thank you! Now I'm back to another issue, every 2 seconds I get in the logs: May 3 13:45:23 myhost upsd[2587]: Connected to UPS [eaton]: usbhid-ups-eaton It seems happy to do this forever. On Tue, May 3, 2016 at 8:17 AM, Charles Lepple <clepple at gmail.com> wrote: > On
2005 Jul 22
1
Another HID USB UPS
...USB FW:w1 - Serial Number: QB0518132135 HID descriptor retrieved (Reportlen = 872) Report descriptor retrieved (Reportlen = 872) found 1 (872) Network UPS Tools: New USB/HID UPS driver 0.23 (2.0.2) Report Descriptor size = 872 Detected an UPS: APC/Back-UPS ES 650 FW:818.w1.D USB FW:w1 Path: UPS.PowerSummary.iSerialNumber Path: UPS.PowerSummary.iDeviceChemistry Path: UPS.PowerSummary.iOEMInformation Path: UPS.PowerSummary.Rechargeable Path: UPS.PowerSummary.APCStatusFlag Path: UPS.PowerSummary.APCStatusFlag Path: UPS.PowerSummary.ManufacturerDate Path: UPS.PowerSummary.ConfigVoltage Path: UPS.PowerSumm...