similar to: Eaton 5E 2000i - incorrect values reported by usbhid-ups

Displaying 20 results from an estimated 1000 matches similar to: "Eaton 5E 2000i - incorrect values reported by usbhid-ups"

2015 Jul 27
0
[HCL] Eaton 5E1100i supported by usbhid-ups
Device manufacturer and name: *Eaton 5E 1100i USB* *upsc eaton5e* Init SSL without certificate database eaton5e root at eger:/home/siposg# upsc eaton5e Init SSL without certificate database battery.charge: 100 battery.runtime: 3160 battery.type: PbAc device.mfr: EATON device.model: 5E 1100i device.type: ups driver.name: usbhid-ups driver.parameter.pollfreq: 30 driver.parameter.pollinterval: 2
2013 Sep 10
1
[HCL] Eaton 5S1500LCD supported by usbhid-ups
Device Manufacturer: Eaton Device Name: 5S1500LCD ---------------------------------------------------------- upsc output: battery.charge: 100 battery.charge.low: 20 battery.runtime: 3515 battery.type: PbAc device.mfr: EATON device.model: Ellipse PRO 1500 device.serial: 0000000000 device.type: ups driver.name: usbhid-ups driver.parameter.pollfreq: 30 driver.parameter.pollinterval: 2
2013 Sep 10
1
[HCL] Eaton 5S1500LCD supported by usbhid-ups
Device Manufacturer: Eaton Device Name: 5S1500LCD ---------------------------------------------------------- upsc output: battery.charge: 100 battery.charge.low: 20 battery.runtime: 3515 battery.type: PbAc device.mfr: EATON device.model: Ellipse PRO 1500 device.serial: 0000000000 device.type: ups driver.name: usbhid-ups driver.parameter.pollfreq: 30 driver.parameter.pollinterval: 2
2016 Oct 26
0
Questions about Eaton 5E 1, 100W 2, 200VA 6-Outlet UPS
It seems that the UPS I bought is actually served by the blazer_usb driver. USB ids 06da:0003 (lsusb DB thinks it's a "Phoenixtec Power Co., Ltd 1300VA UPS", but this has apparantly been re-used by Eaton 5E2200USB-LA) It's sold as an Eaton 5E 1,100W 2,200VA 6-Outlet UPS SKU: 147140 Mfr Part #: 5E2200USB-LA UPC: 743172064875
2014 Jul 26
4
Power race? with Eaton 5E and how to auto-mute beeper
I have a brand new Eaton 5E UPS purchased in Australia. Details: Eaton 5E Model: 5E650iUSB-AU Date: best I can find is the shipping date to supplier on box label - May 2014 OS: Ubuntu 14.04 Server edition Nut 2.7.1 Installed via apt-get install nut I have two problems I would like to fix. First the beeper is annoying and loud and I worry it will wake everyone up at night. I read that you can
2008 Jun 10
2
Phoenix Ph1200upsb serial
Hi, i just got a Phoenix Technologies PH1200UPSB 1200va serial-port ups and it is only partially supported by bestups driver (needs manual ID or driver rewriting). It comes with a tool called UPSilon 2.1 on a CD (which worked better with TERM=linux). After [sl]tracing it i came to these results: COMMANDS : - Command: I Response: "#XPHOENIX TECH PH1200UPS VER2.00C " - Command: F
2020 Jan 08
0
Hardware compatability report: Eaton Ellipse ECO 1600
Here is a Compatibility Report for the Eaton Ellipse ECO 1600 UPS. Roger battery.charge: 100 battery.charge.low: 20 battery.runtime: 1575 battery.type: PbAc device.mfr: EATON device.model: Ellipse ECO 1600 device.serial: 000000000 device.type: ups driver.name: usbhid-ups driver.parameter.lowbatt: 37 driver.parameter.offdelay: 30 driver.parameter.ondelay: 40 driver.parameter.pollfreq: 30
2013 Feb 07
0
nut-2.6.5: ups.timer.start problem with EATON Protection Station 650
Hi, I have successfully configured Nut to work with EATON PS 650: system detects low battery, initiates shutdown, waits for UPS to switch power off. However, when power is restored, UPS immediately powers on all power plugs independently from ups.timer.start setting. upsc reports "ups.timer.start" variable availability which is set to 0. upsrw reports "ups.delay.start"
2007 Oct 29
1
Outlet switching on the MGE Pulsar 1500 using usbhid-ups on FreeBSD
I am running NUT 2.2.0 compiled from the FreeBSD ports tree. [inchoate 14:50] ~ >upsc ups1 at localhost battery.charge: 59 battery.charge.low: 20 battery.charge.restart: 0 battery.runtime: 6350 battery.type: PbAc battery.voltage: 43.0 driver.name: usbhid-ups driver.parameter.offdelay: 120 driver.parameter.ondelay: 13 driver.parameter.pollinterval: 2 driver.parameter.port: auto driver.version:
2017 Jul 07
0
Eaton PW9130 1500VA-T with netxml-ups driver
Hello, I have some questions about netxml-ups driver. My UPS: Eaton PW9130 1500VA-T with Network Management Card. OS: Fedora 24 NUT 2.7.4 (from fedoraproject repo) Driver: netxml-ups. Results of upsc: ambient.humidity.high: 90 ambient.humidity.low: 5 ambient.temperature.high: 40 ambient.temperature.low: 5 battery.charge: 100 battery.charge.low: 20 battery.charge.restart: 0 battery.runtime: 69012
2017 Apr 07
0
[Eaton 5S 1500] overvoltage shut down?
Hello Charles, I've attached a dump below. There were no long entries on any of the hosts, neither the one running standalone, nor the master/slave combo, which is not too surprising, it was really fast: I saw the light flickering in the room, almost like flash, and all those 3 systems went down. I first heard the "click" of the ports being disabled, heard the systems shut down, and
2015 Mar 19
0
Brand new EATON 3S700DIN (mfr.date 09/28/14) doesn't wait for LB flag
Sergey, I?m no expert on this but I have been reading the driver code, trying to sort out bigger problems with the OpenUPS driver! I can make 2 observations that I can?t check out myself : ?beeper.disable? was previously ?beeper off? - and ?beeper.enable? was ?beeper.on?. Not sure if it?s worth trying the old versions? If your UPS doesn?t wait for LB, could this be because there is another
2014 Nov 10
0
Eaton-9130 (usbhid-ups) no battery.voltage parameter!
On Nov 10, 2014, at 9:10 AM, ??????? ?????????? <v.linch at icloud.com> wrote: > My windows version is 2.6.5-3, latest on NUT site. > "upsc ups" shows many ups parameters such as ups.load, battery.charge etc. but there is no battery.voltage, which I need (ups - is the name of my device in config). > If I load driver usbhid-ups in debug mode (-DD), I see something like
2014 Nov 10
3
Eaton-9130 (usbhid-ups) no battery.voltage parameter!
An HTML attachment was scrubbed... URL: <http://lists.alioth.debian.org/pipermail/nut-upsuser/attachments/20141111/7dd98eaa/attachment-0001.html> -------------- next part -------------- A non-text attachment was scrubbed... Name: usbhid.zip Type: application/zip Size: 5991 bytes Desc: not available URL:
2014 Nov 11
0
Eaton-9130 (usbhid-ups) no battery.voltage parameter!
On Nov 10, 2014, at 6:44 PM, Valeri Linchevski <lincher at ya.ru> wrote: > Parameter, "blabla" :-) really is Ups.PowerSummary.Voltage, debug output is in attach. > Apparently some models are missing from the table that is consulted for "mge_type": https://github.com/networkupstools/nut/blob/master/drivers/mge-hid.c#L201 Arnaud or Emilien, Is there any way we
2014 Nov 11
2
Eaton-9130 (usbhid-ups) no battery.voltage parameter!
An HTML attachment was scrubbed... URL: <http://lists.alioth.debian.org/pipermail/nut-upsuser/attachments/20141111/42cd1a34/attachment.html>
2014 Nov 11
0
Eaton-9130 (usbhid-ups) no battery.voltage parameter!
On Nov 10, 2014, at 11:00 PM, Valeri Linchevski <lincher at ya.ru> wrote: > So, how can I get this value? You could comment out the switch statements in drivers/mge-hid.c, functions mge_battery_voltage_nominal_fun() and mge_battery_voltage_fun(), and recompile. I logged an issue for fixing this the right way: https://github.com/networkupstools/nut/issues/170 -- Charles Lepple clepple
2014 Nov 11
0
Emne: Re: Eaton-9130 (usbhid-ups) no battery.voltageparameter!
The model should also work with the bcmxcp driver, but maybe that only works with serial, not usb. http://nutwiki.kanonbra.com/wiki/Category:Eaton_Powerware_9130 Alf Sent from my Cat? phone. Valeri Linchevski <lincher at ya.ru>:
2017 Jul 14
0
UPSC dump for Eaton/Powerware 5115 Rackmount unit (driver version 2.7.2)
Hi, just wanted to provide a upsc dump for an Eaton/Powerware 5115 rack mount unit. This was on a CentOS 7.3 machine with following packages installed: nut-client-2.7.2-3.el7.x86_64 nut-2.7.2-3.el7.x86_64 nut-cgi-2.7.2-3.el7.x86_64 $ upsc eaton5115 ambient.temperature: 43 ambient.temperature.high: 75 battery.charge: 100 battery.runtime: 24171 battery.voltage: 40.96 device.mfr: Eaton
2014 Nov 10
0
Eaton-9130 (usbhid-ups) no battery.voltage parameter!
On Nov 9, 2014, at 9:35 AM, ??????? ?????????? <v.linch at icloud.com> wrote: > I've installed latest NUT under Windows XP, all works fine, but when I run "upsc ups" command I don't see the battery.voltage parameter, which I most need. Can you provide a few more details? The latest version of NUT (2.7.2 at the moment) has not been ported to Windows. Also, what does