2008-Jan-15 13:51 UTC
[Nut-upsuser] How to lower float charge voltage of an APC Smart UPS
Dear Sir, Please tell me if u have any method to increase the charging current of APC smart 1000/1400VA with and without external battery bank option. I am using externally 40 and 80 Amp lead acid batteries but charging time is too long. Please help me ASAP. Regards, Afzaal Ahmad UPS Engineer afzaal.ahmad at sbp.org.pk -------------- next part -------------- An HTML attachment was scrubbed... URL: http://lists.alioth.debian.org/pipermail/nut-upsuser/attachments/20080115/20b133e1/attachment.htm
Arjen de Korte
2008-Jan-15 15:08 UTC
[Nut-upsuser] How to lower float charge voltage of an APC Smart UPS
> Please tell me if u have any method to increase the charging current of > APC smart 1000/1400VA with and without external battery bank option. I > am using externally 40 and 80 Amp lead acid batteries but charging time > is too long. Please help me ASAP.You would have to ask APC for that. Since the original batteries that go into this system are only 12Ah, I can imagine that charging time will be (very) long when empty when using the build in charger. I'm fairly certain that this can't be done through a command that is sent to the UPS, so this probably requires additional hardware (if it can be done at all, safely). I expect that adding an extrenal charger might/will interfere with the internal charging circuits, so I really doubt if this is an optimal solution. Several vendors have systems where additional battery modules can be added that come with their own (integrated) chargers. Best regards, Arjen -- Eindhoven - The Netherlands Key fingerprint - 66 4E 03 2C 9D B5 CB 9B 7A FE 7E C1 EE 88 BC 57