Displaying 20 results from an estimated 151 matches for "charger".
Did you mean:
charge
2015 Mar 25
2
On ups.status CHRG/DISCHRG Vs battery.charger.status
Hi NUT developers,
part of the 2.7.3 release, we are about to merge the below branch / PR for
the bcmxcp drivers family:
https://github.com/networkupstools/nut/pull/158
https://github.com/networkupstools/nut/tree/pull_158_bcmxcp_rebased
It has introduced the battery.charger.status variable, which is something I
wanted to implement since around 2007.
However, while considering a similar implementation for usbhid-ups, and
thinking a bit more broadly, this new variable tends to collide with the
CHRG / DISCHRG status bits from ups.status, and adding 2 more (floating and...
2015 Mar 30
1
On ups.status CHRG/DISCHRG Vs battery.charger.status
...es,
2015-03-29 0:44 GMT+01:00 Charles Lepple <clepple at gmail.com>:
> On Mar 25, 2015, at 4:11 AM, Arnaud Quette <arnaud.quette at gmail.com>
> wrote:
>
> > 1) Keep the legacy CHRG / DISCHRG status bits for ups.status, along with
> the complementary ones for battery.charger.status. And advocate (document)
> for the use of / switch to the latter, that is more suitable for publishing
> such information. All that with an impact on all the NUT driver, and a
> transition period to address that cleanly.
>
> I prefer this option, for what it's worth. Let...
2015 Mar 28
0
On ups.status CHRG/DISCHRG Vs battery.charger.status
On Mar 25, 2015, at 4:11 AM, Arnaud Quette <arnaud.quette at gmail.com> wrote:
> 1) Keep the legacy CHRG / DISCHRG status bits for ups.status, along with the complementary ones for battery.charger.status. And advocate (document) for the use of / switch to the latter, that is more suitable for publishing such information. All that with an impact on all the NUT driver, and a transition period to address that cleanly.
I prefer this option, for what it's worth. Let's not make ups.status...
2018 Jan 16
2
Eaton 5PX after battery replacement still says "replace battery" in NUT
...lation are:
OS: Debian 6
NUT version: 2.7.4
Installation method: from source tarball
UPS device: Eaton 5PX2000IRT, 240V, 1800W, 2000VA, bought in October 2013
Here?s the status as reported by upsc:
battery.capacity: 9.00
battery.charge: 100
battery.charge.low: 20
battery.charge.restart: 0
battery.charger.status: floating
battery.energysave: no
battery.protection: yes
battery.runtime: 1032
battery.type: PbAc
device.mfr: EATON
device.model: Eaton 5PX 2000
device.serial: G098D27047
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter....
2011 May 04
0
charger does not work?
My netbook (http://www.laptopspark.com) was charging fine when I was first on it. I accidently pulled it too far but the charger didn't un-attatch from Sony Vaio EA3S1E/L Intel Core i3 370M 2.4GHz 500GB HDD 4GB RAM 14.1" WXGA TFT Laptop (http://www.laptopspark.com/products/Sony-Vaio-EA3S1EL-Intel-Core-i3-370M-24GHz-500GB-HDD-4GB-RAM-141-WXGA-TFT-Laptop-laptop-290.html) or plug. I checked it over and it seems fine, b...
2003 Apr 03
0
New Coin Operated Mobile Phone Charger - Seeking Overseas Distributors
ProductPublic Mobile Phone Multi-charger
(With/Without Coin Module)
Functions1. Accept coins.
2. Allows conversation while charging.
2. 10 travel charger plugs for most models.
3. Light box advertising.
4. UV phone sanitizing
InputAC 110 - 250V 50~60Hz
Output< 12 V 1C 5 A x 10
Measurement29 cm x 20 cm x 51.6 cm
Net Weight5...
2014 Feb 19
3
Logic problem in NUT with upscode2 driver
...I have what is probably a 12 year old (or older) Compaq R3000 UPS
plugged into a FreeBSD 8 system running NUT version 2.6.5
This UPS contains a total of 16 batteries in 2 banks of 8,
each battery is 6 volts and the bank produces 50 volts.
The UPS monitors battery voltage and the battery charger in
the UPS works like this. For about 2 days it will apply a
charge/float/topping voltage of 55.2 volts to the batteries.
During that time the battery voltage measures 55.2 volts
both with a voltmeter on the batteries and as reported by
upsc, and the "calculated state of charge" of the U...
2024 Nov 13
2
Eaton 5PX 3rd party batteries
resending, sorry, I mangled the list address.
On Tue, Nov 12, 2024, at 11:49 PM, Harlan Stenn wrote:
> - put each battery on a charger for several hours
Do you have a recommendation for a battery charger? Or a list of features to look for?
> Anyway, when I have a set of replacement new batteries, I then:
>
> - put each battery on a charger for several hours
> - rotating thru the entire set at least twice
> - then...
2008 Apr 01
1
Incorrect battery status on MGE Pulsar M 3000
...rtID: 0x24, Offset:
0, Size: 8, Value: 1.000000
Path: UPS.BatterySystem.Battery.TestPeriod, Type: Feature, ReportID: 0x25,
Offset: 0, Size: 32, Value: 604800.000000
Path: UPS.BatterySystem.BatterySystemID, Type: Feature, ReportID: 0x20,
Offset: 8, Size: 8, Value: 1.000000
Path: UPS.BatterySystem.Charger.ChargerID, Type: Feature, ReportID: 0x20,
Offset: 16, Size: 8, Value: 1.000000
Path: UPS.BatterySystem.Charger.ChargerType, Type: Feature, ReportID: 0x26,
Offset: 0, Size: 8, Value: 0.000000
Path: UPS.BatterySystem.Charger.PresentStatus.InternalFailure, Type: Feature,
ReportID: 0x27, Offset: 8,...
2011 Jan 04
1
isolinux, extlinux and accented characters
Hello,
First of all, thanks very much for this piece of software, it's working
like a charm.
I'm using it to boot a Linux distro I'm working on.
What I want to deal with is the display of accented characters in ISOLINUX.
First, I set EXTLINUX up to boot an ext2-formatted USB stick. No problem
so far.
I wrote a config file ordering to load a font (lat-9w) to display french
2016 Oct 30
2
Power Cut
Thank you for your reply. You are correct and the ups is present there but
the battery charger can no longer bear power cuts more than two hours so I
need some means to distinguish frequent power cuts there among the system
logs.
On Sun, Oct 30, 2016 at 12:02 AM, Eero Volotinen <eero.volotinen at iki.fi>
wrote:
> you could use smart ups and connect information from it to system, s...
2016 Oct 30
7
Power Cut
Dear All
I am using a centos server for cdr billing and mediation device on a remote
network. I am experiencing problem that I am suspicious it comes from main
supply power cut at the remote site. The power supply to the remote site
comes from battery charger that will be automatically switched in circuit
under main supply power cut but cannot provide adequate power for more than
2 hours . I am suspicious that the remote system is suffering from many
frequent main supply power cut . Can you please do me favor and let me know
if there is any log on my ce...
2008 Jan 15
1
How to lower float charge voltage of an APC Smart UPS
Dear Sir,
Please tell me if u have any method to increase the charging current of
APC smart 1000/1400VA with and without external battery bank option. I
am using externally 40 and 80 Amp lead acid batteries but charging time
is too long. Please help me ASAP.
Regards,
Afzaal Ahmad
UPS Engineer
afzaal.ahmad at sbp.org.pk
-------------- next part --------------
An HTML
2019 Jun 17
2
Monitoring for an alarm
I found one of UPS has a
ups.alarm : Battery charger fail! Internal UPS fault!
Is there a way to monitor for this kind of failure? In upsmon I did not
find and event type for alarms like this...
Thanks
Adam Pribyl
2018 May 25
1
[HCL] IBM 1500VA/1000W Tower HV UPS supported by usbhid-ups
...ze: 8, Value: 4
3.485363 Path: UPS.BatterySystem.Battery.ffff0045, Type: Feature,
ReportID: 0x25, Offset: 0, Size: 32, Value: 7.776e+06
3.485614 Path: UPS.BatterySystem.BatterySystemID, Type: Feature,
ReportID: 0x20, Offset: 8, Size: 8, Value: 1
3.485813 Path: UPS.BatterySystem.Charger.ChargerID, Type: Feature,
ReportID: 0x20, Offset: 16, Size: 8, Value: 1
3.512824 Path: UPS.BatterySystem.Charger.ffff006b, Type: Feature,
ReportID: 0x26, Offset: 0, Size: 8, Value: 4
3.513050 Path: UPS.BatterySystem.Charger.ffff0094, Type: Feature,
ReportID: 0x26, Offset: 8, Size: 8,...
2004 Sep 09
3
Store data from call to database
...anks
Jerome
Vous manquez d?espace pour stocker vos mails ?
Yahoo! Mail vous offre GRATUITEMENT 100 Mo !
Cr?ez votre Yahoo! Mail sur http://fr.benefits.yahoo.com/
Le nouveau Yahoo! Messenger est arriv? ! D?couvrez toutes les nouveaut?s pour dialoguer instantan?ment avec vos amis. A t?l?charger gratuitement sur http://fr.messenger.yahoo.com
2016 Oct 30
3
Power Cut
...a network management interface. Why aren't you using it to
> send alerts?
>
> On Oct 30, 2016 12:05 AM, "Hadi Motamedi" <motamedi24 at gmail.com> wrote:
>
> > Thank you for your reply. You are correct and the ups is present there
> but
> > the battery charger can no longer bear power cuts more than two hours so
> I
> > need some means to distinguish frequent power cuts there among the system
> > logs.
> >
> > On Sun, Oct 30, 2016 at 12:02 AM, Eero Volotinen <eero.volotinen at iki.fi>
> > wrote:
> >
> >...
2007 Nov 10
9
problème de téléchargement
salut Alex, je ne peut pas télécharger wxruby-1.9.2 avec rubygems. J''avait wxruby-1.9.0, mais j''ai fait une restauration complète de mon pc hier.
J''ai la version 0.9.4 de ruby gems.
J''ai un message d''erreur <openURI::HTTPerror> quand je veut installer wxruby-1.9.2.
merci
______________...
2007 Apr 14
7
=question sur wxruby2
Bonjour, je voulais savoir si wxruby2 est intégré à l''interpréteur ruby?
Que veut dire $0 ?
merci
Sebastien
_______________________________________________
wxruby-users mailing list
wxruby-users@rubyforge.org
http://rubyforge.org/mailman/listinfo/wxruby-users
2020 Nov 01
1
ups.test.result meaning
>
>
> > battery.voltage: 16.0
> At that voltage, 5 of the 12 cells are shorted
> > output.voltage: 138.0
> too high by about 15 volts
>
> Wow! That battery is beyond toasted, shoulda been replaced months ago.
> And the output voltage is a bit much if its truthfull.
>
Thanks for the response Gene!
I've ordered a replacement unit.
I'm not sure about the