search for: upss

Displaying 20 results from an estimated 209 matches for "upss".

Did you mean: mpss
2010 Jun 25
1
Supporting APC 5G UPSs
Hi Guys, I'd like to submit a patch to enable NUT to communicate with APC 5G UPSs. The current usbhid-ups driver recognises APC UPSs by the Vendor ID and Product ID of 0x051D and 0x0002. This needs to be amended with the new Product ID of 0x0003. (See attached file: apc-hid.patch) Secondly, when Nut polls the UPS via the interrupt channel, these will time out, resulting in fr...
2017 Mar 02
6
NUT - General Concept Question
...a feel for what it is. But I'm still not clear whether what I'd *like* to accomplish is actually practical using NUT. Perhaps someone here can tell me if they've done something similar, or if I'm way off base. I would like to set up a Linux host as a central monitoring system for UPSs throughout our network. I'd like that system to be able to see the various UPSs basically in one of two ways: 1) Tapping into a native network interface on the target UPS (such as some larger APC and Tripp-Lite UPSs we have) 2) Talking to a Raspberry Pi connected to the UPS via a U...
2017 Oct 31
4
Email Alerts for Multiple UPSs with upssched
Greetings Gentlebeings, I have started deploying a number of NUT instances on Raspberry Pi machines (Raspbian Jessie) across my network. The purpose of these "nutcases" as we refer to them is to monitor the status of the UPSs supporting our network switching infrastructure and notify us of power and battery events via email. No shutdown or other actions are required. Everything is going spiffy as all get-out so far. But now I'm running up against a configuration issue I don't quite know how to address. Thus...
2007 Sep 14
1
Bug#441342: Nut can kill power to UPSs that never went on battery
...news back. 2007/9/9, Robert Woodcock <rcw at debian.org>: > Package: nut > Version: 2.2.0-2 > Severity: important > > I recently set up nut at work to monitor the 15 APC Smart-UPS 1500s we have > in our server room. Since we currently only have one Linux system, all 15 > UPSs are connected via USB hubs to it. > > Over the last couple months, we have had a couple incidents (luckily all on > weekends) where all 15 UPSs will mysteriously shut off, and we had to > manually power them back up. To top it off, there was nothing in syslog > about any UPS going on...
2015 Sep 02
1
monitoring Eaton parallel/redundant UPSs
I have been happily using NUT to monitor a couple of Eaton UPS. These are independent UPSs, each driving one "leg" of the power in our data center. In this scenario, I've told my clients they need to have one UPS working and to shutdown when the last UPS reaches critical battery. I have recently learned that our power arrangement will be changing to a parallel-fed/redun...
2017 Oct 31
2
Email Alerts for Multiple UPSs with upssched
Ah! So I can detect the source UPS in the upssched.conf and pass it as a distinct event to the shell script. That sounds like an excellent approach. Thanks! GMH From: O'Shaughnessy, Mike [mailto:Mike.OShaughnessy at gd-ms.com] Sent: Tuesday, October 31, 2017 12:46 PM To: Garrett Michael Hayes <Garrett at VerbalImaging.com>; nut-up...
2013 Aug 28
1
Question marks in Broadcast Messages
I'm setting up a NUT server. During testing, I have deployed it on both CentOS and SUSE. I have both servers looking at two physical UPSs and two "dummy" UPSs. My NUT client is running on Solaris and is rigged to look at the "dummy" UPSs. As I toggle states on the dummy UPSs, the client correctly detects the changes and throws a message of the type: > Broadcast Message from ups (???) on nut Wed Aug 28 13:5...
2017 Oct 31
0
Email Alerts for Multiple UPSs with upssched
...es <Garrett at VerbalImaging.com> wrote: >Greetings Gentlebeings, > >I have started deploying a number of NUT instances on Raspberry Pi >machines (Raspbian Jessie) across my network. The purpose of these >"nutcases" as we refer to them is to monitor the status of the UPSs >supporting our network switching infrastructure and notify us of power >and battery events via email. No shutdown or other actions are >required. > >Everything is going spiffy as all get-out so far. But now I'm running >up against a configuration issue I don't quite kno...
2017 Nov 01
1
Email Alerts for Multiple UPSs with upssched
...nal Message----- From: Jim Klimov [mailto:jimklimov at cos.ru] Sent: Tuesday, October 31, 2017 1:36 PM To: nut-upsuser at lists.alioth.debian.org; Garrett Michael Hayes <Garrett at VerbalImaging.com>; nut-upsuser at lists.alioth.debian.org Subject: Re: [Nut-upsuser] Email Alerts for Multiple UPSs with upssched On October 31, 2017 4:09:46 PM GMT+01:00, Garrett Michael Hayes <Garrett at VerbalImaging.com> wrote: >Greetings Gentlebeings, > >I have started deploying a number of NUT instances on Raspberry Pi >machines (Raspbian Jessie) across my network. The purpose of these...
2017 Oct 31
0
Email Alerts for Multiple UPSs with upssched
...to be replaced NOCOMM A UPS is unavailable (can't be contacted for monitoring) From: Garrett Michael Hayes [mailto:Garrett at VerbalImaging.com] Sent: Tuesday, October 31, 2017 1:19 PM To: O'Shaughnessy, Mike; nut-upsuser at lists.alioth.debian.org Subject: RE: Email Alerts for Multiple UPSs with upssched Ah! So I can detect the source UPS in the upssched.conf and pass it as a distinct event to the shell script. That sounds like an excellent approach. Thanks! GMH From: O'Shaughnessy, Mike [mailto:Mike.OShaughnessy at gd-ms.com] Sent: Tuesday, October 31, 2017 12:46 PM To: Gar...
2019 Dec 25
1
NUT not shutting down one of three UPSs (sometimes none of them shut down)
...AP9617 - ups3-1 - does not shut down when FSD is sent. It did when I first set this system up a year or two ago but it's stopped doing so since then. Resetting the management interface does not change anything. This is all that shows up in /var/log/messages on the host that is connected to the UPSs and running the full NUT suite: Dec 25 08:00:26 [redacted] upsd[9800]: Client upsmon@[redacted] set FSD on UPS [ups1-1] Dec 25 08:00:26 [redacted] upsd: Client upsmon@[redacted] set FSD on UPS [ups1-1] Dec 25 08:00:26 [redacted] upsd: Client upsmon@[redacted] set FSD on UPS [ups2-1] Dec 25 08:00:26...
2019 Jul 25
6
how to increase DNS reliability?
...nance on your servers > > (a) too often > (b) during office / peak hours I can't help it when the primary name server goes down because the UPS fails the self test and tells the server it has 2 minutes or so left in wich case the server figures it needs to shut down. I wanted better UPSs ... > You could load balance multiple servers (using lots of available load-balancing technologies) to allow you to perform maintenance at certain times, but it has its own issues. Load balancing or clustering? At least clustering seems not entirely trivial to do. > I've recently been...
2017 Oct 31
0
Email Alerts for Multiple UPSs with upssched
...-2 0 <User> <Pw> master MONITOR ups-3 0 <User> <Pw> master MONITOR ups-4 0 <User> <Pw> master MONITOR ups-5 1 <User> <Pw> master MONITOR ups-6 1 <User> <Pw> master MONITOR ups-7 0 <User> <Pw> master NOTIFYCMD /sbin/upssched NOTIFYFLAG ONLINE SYSLOG+WALL+EXEC NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC NOTIFYFLAG FSD SYSLOG+WALL+EXEC NOTIFYFLAG COMMOK SYSLOG+WALL+EXEC NOTIFYFLAG COMMBAD SYSLOG+WALL+EXEC NOTIFYFLAG SHUTDOWN SYSLOG+WALL+EXEC NOTIFYF...
2020 Mar 25
0
[EXTERNAL] thoughts on tripp lite Smart Online UPSs?
...__ From: Nut-upsuser <nut-upsuser-bounces+david_zomaya=tripplite.com at alioth-lists.debian.net> on behalf of Lee Damon <nomad at ee.washington.edu> Sent: Wednesday, March 25, 2020 5:09 PM To: nut-upsuser Mailing List Subject: [EXTERNAL] [Nut-upsuser] thoughts on tripp lite Smart Online UPSs? This is an EXTERNAL email. Please take a moment and think before clicking any links or opening any attachments from this email. If suspicious, please forward to ishelpdesk at tripplite.com for review. ______________________________________________________________________ We're looking at r...
2020 Mar 25
5
thoughts on tripp lite Smart Online UPSs?
...nd yes, I've tried USB-RS232 adapters and every one I tried started kicking out errors within a few hours). One of the bids we have is for a "Tripp Lite UPS Smart Online 5000VA 4500W Rackmount 5kVA 200V/240V" as the potential replacement unit. I have no experience with Tripp Lite UPSs and the reviews I've found online are scant and fairly mixed so I thought I'd ask here... Does anyone on this list have experience with these UPSs? Any thoughts? Would you buy it again? Does it work well with NUT? thanks, nomad F.T.R. the full description is "Tripp Lite UPS Smart...
2020 Mar 25
2
[EXTERNAL] thoughts on tripp lite Smart Online UPSs?
...tried seemed to work fine. For reference, the SU5000RT4UHV should be a 4004 USB protocol. ________________________________ From: David Zomaya Sent: Wednesday, March 25, 2020 5:21 PM To: Lee Damon; nut-upsuser Mailing List Subject: Re: [EXTERNAL] [Nut-upsuser] thoughts on tripp lite Smart Online UPSs? I'm obviously biased but I like Tripp Lite stuff. I try to pitch in and help with Network UPS Tools issues related to Tripp Lite when I can too (albeit the developers and users on this list are usually more helpful than me). Just to confirm, it sounds like you are looking at the SU5000RT4...
2017 Jun 25
3
Why are LAN ports not standard on UPSs these days?
Larry, On 2017-06-25 23:26, Larry Fahnoe wrote: > Hi Phil, > > I don't have an answer to your question about the lack of LAN ports, I think it is weird - with everything else being connected to LANs like fridges etc . . why not UPSs? > but can offer my experience with NUT for a home server environment. > I've tended to prefer the Tripp-Lite UPS systems, mainly because I > originally felt they did a good job of power filtering. I use a NUT > master running on a Raspberry Pi 3 which is easy to maintain and get...
2018 Jul 11
2
Adding drivers to NUT?
Dear Daniele, thanks a lot for your support, i have some things that are not so clear for me: - I can send you the whole sources for our UPSs, do you need only Headers and C files or also other files (i suppose Driver list)? - Seen that we had some problems with the Blazer driver (the battery voltage calculation were not correct for our UPSs) we copied it and modified a bit while changing the name, is this possible or it's a proble...
2012 May 10
2
Two servers with redundant supplies on two UPSs
Scenario: * Two windows 2003 servers (different models) * Each server has two PSUs * Each server has a single serial port * Two UPSs are available of the exact same type (XPower Tigra 1kVA). Each has a serial port * The 1st PSU of each server is powered by the 1st UPS * The 2nd PSU of each server is powered by the 2nd UPS I am trying to install NUT on the best "optimal" way for these two systems. My obvious solution...
2006 Nov 05
1
EMC/ACBEL Polytech UPS
I have a couple EMC relabled ACBEL/Polytech UPSs which I'm unable to find anything about. What I do know is that ACBEL/Polytech is CoolerMaster, however, they don't make UPSs that I know of. These UPSs were used as part of an EMC Clarion array. Does anyone know anything about these? Thanks, Mark. -------------- next part --------------...