Lee Damon
2019-Dec-25 19:16 UTC
[Nut-upsuser] NUT not shutting down one of three UPSs (sometimes none of them shut down)
I have three APC SmartUPS 5000s. Two of them are AP9617 and one is AP9619. I have a RS-232 connections from my monitor host to all three. All three report status and give information. One of the two AP9617 - ups3-1 - does not shut down when FSD is sent. It did when I first set this system up a year or two ago but it's stopped doing so since then. Resetting the management interface does not change anything. This is all that shows up in /var/log/messages on the host that is connected to the UPSs and running the full NUT suite: Dec 25 08:00:26 [redacted] upsd[9800]: Client upsmon@[redacted] set FSD on UPS [ups1-1] Dec 25 08:00:26 [redacted] upsd: Client upsmon@[redacted] set FSD on UPS [ups1-1] Dec 25 08:00:26 [redacted] upsd: Client upsmon@[redacted] set FSD on UPS [ups2-1] Dec 25 08:00:26 [redacted] upsd: Client upsmon@[redacted] set FSD on UPS [ups3-1] Dec 25 08:00:26 [redacted] upsd[9800]: Client upsmon@[redacted] set FSD on UPS [ups2-1] Dec 25 08:00:26 [redacted] upsd[9800]: Client upsmon@[redacted] set FSD on UPS [ups3-1] The other two do shut down... most of the time. I've now observed two occasions in the past 6 months where none of them do so. All three UPSs report the same Application module and APC OS.: Application Module Name: sumx Version: v3.7.2 Date: 02/02/2010 Time: 19:08:16 APC OS (AOS) Name: aos Version: v3.7.3 Date: 02/02/2010 Time: 17:05:14 Yes, these are old UPSs and I've requested money to replace ups3-1. Of course, that won't help if NUT doesn't shut down any of them. Any advice would be appreciated. thanks, nomad -------------- next part -------------- An HTML attachment was scrubbed... URL: <http://alioth-lists.debian.net/pipermail/nut-upsuser/attachments/20191225/983f008b/attachment.html>
Roger Price
2019-Dec-25 20:40 UTC
[Nut-upsuser] NUT not shutting down one of three UPSs (sometimes none of them shut down)
On Wed, 25 Dec 2019, Lee Damon wrote:> I have three APC SmartUPS 5000s. Two of them are AP9617 and one is AP9619. > > One of the two AP9617 - ups3-1 - does not shut down when FSD is sent. It did > when I first set this system up a year or two ago but it's stopped doing so > since then. Resetting the management interface does not change anything. > > The other two do shut down... most of the time. I've now observed two > occasions in the past 6 months where none of them do so.If you swap the physical units ups1-1 and ups3-1, does the problem follow the hardware, or does it stay with ups3-1 ? Roger