2013 Jun 10
2
several problems with Powercom BNT-500AP
I took the log. Here's what happened.
Broadcast Message from nut at rasp
(somewhere) at 16:18 ...
UPS BNT500AP at localhost battery needs to be replaced
occurred when for the first time value "1" was read as "UPS.PowerSummary.PresentStatus.NeedReplacement", on this line:
6409.240690 Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID: 0x0a, Offset: 6, Size: 1, Value: 1
It happened for 9 times, but the message appeared only on first.
Broadcast Message from nut at rasp
(somewhere) at 17:33 ...
UPS BNT500AP a...
2010 Sep 17
1
Liebert PSP
...000000
0.577942 Report[buf]: (2 bytes) => 07 0d
0.577954 Path: UPS.PowerSummary.PresentStatus.ShutdownImminent,
Type: Feature, ReportID: 0x07, Offset: 5, Size: 1, Value: 0.000000
0.577963 Report[buf]: (2 bytes) => 07 0d
0.577975 Path: UPS.PowerSummary.PresentStatus.NeedReplacement,
Type: Input, ReportID: 0x07, Offset: 6, Size: 1, Value: 0.000000
0.577984 Report[buf]: (2 bytes) => 07 0d
0.577996 Path: UPS.PowerSummary.PresentStatus.NeedReplacement,
Type: Feature, ReportID: 0x07, Offset: 6, Size: 1, Value: 0.000000
0.578005 Report[buf]: (2 bytes) =...
2010 Sep 17
1
Liebert PSP
...000000
0.577942 Report[buf]: (2 bytes) => 07 0d
0.577954 Path: UPS.PowerSummary.PresentStatus.ShutdownImminent,
Type: Feature, ReportID: 0x07, Offset: 5, Size: 1, Value: 0.000000
0.577963 Report[buf]: (2 bytes) => 07 0d
0.577975 Path: UPS.PowerSummary.PresentStatus.NeedReplacement,
Type: Input, ReportID: 0x07, Offset: 6, Size: 1, Value: 0.000000
0.577984 Report[buf]: (2 bytes) => 07 0d
0.577996 Path: UPS.PowerSummary.PresentStatus.NeedReplacement,
Type: Feature, ReportID: 0x07, Offset: 6, Size: 1, Value: 0.000000
0.578005 Report[buf]: (2 bytes) =...
2005 Aug 02
0
newhidups for APC Back-UPS ES 650
....BelowRemainingCapacityLimit
Path: UPS.PowerSummary.PresentStatus.ShutdownImminent
Path: UPS.PowerSummary.PresentStatus.ShutdownImminent
Path: UPS.PowerSummary.PresentStatus.RemainingTimeLimitExpired
Path: UPS.PowerSummary.PresentStatus.RemainingTimeLimitExpired
Path: UPS.PowerSummary.PresentStatus.NeedReplacement
Path: UPS.PowerSummary.PresentStatus.NeedReplacement
Path: UPS.PowerSummary.PresentStatus.OverLoad
Path: UPS.PowerSummary.PresentStatus.OverLoad
Path: UPS.PowerSummary.RemainingTimeLimit
Path: UPS.PowerSummary.AudibleAlarmControl
Path: UPS.Battery.APCBattReplaceDate
Path: UPS.Battery.Manufactu...
2013 Jun 11
0
several problems with Powercom BNT-500AP
...:
> I took the log. Here's what happened.
> Broadcast Message from nut at rasp
> (somewhere) at 16:18 ...
> UPS BNT500AP at localhost battery needs to be replaced
>
> occurred when for the first time value "1" was read as "UPS.PowerSummary.PresentStatus.NeedReplacement", on this line:
> 6409.240690 Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID: 0x0a, Offset: 6, Size: 1, Value: 1
> It happened for 9 times, but the message appeared only on first.
Correct, upsmon throttles the REPLBATT event:
http://www.networkupstools...
2014 Sep 17
0
FW: POWERCOM HID USB controller update
...quot;new commands" pointed in your archive (thanks for isolating
these changes!):
- Usage ID : 85:68 is already supported with UPS.PowerSummary.RunTimeToEmpty
- Usage ID :85:4B is already supported with 1 of the 2 below (can't check
the HID report structure)
UPS.PowerSummary.PresentStatus.NeedReplacement
UPS.PresentStatus.NeedReplacement
This leaves the 2 "Outlet Group" commands, which is probably the actual
reason why you contacted us:
Usage ID : 84:01
Report ID : 50
Write : 1
Description : Outlet Group1 ON
Usage ID : 84:01
Report ID : 49
Write : 0
Description : Outlet Group2 OFF...
2005 Aug 26
0
NUT patches
....BelowRemainingCapacityLimit
Path: UPS.PowerSummary.PresentStatus.ShutdownImminent
Path: UPS.PowerSummary.PresentStatus.ShutdownImminent
Path: UPS.PowerSummary.PresentStatus.RemainingTimeLimitExpired
Path: UPS.PowerSummary.PresentStatus.RemainingTimeLimitExpired
Path: UPS.PowerSummary.PresentStatus.NeedReplacement
Path: UPS.PowerSummary.PresentStatus.NeedReplacement
Path: UPS.PowerSummary.PresentStatus.OverLoad
Path: UPS.PowerSummary.PresentStatus.OverLoad
Path: UPS.PowerSummary.PresentStatus.00000000
Path: UPS.PowerSummary.PresentStatus.00000000
Path: UPS.PowerSummary.PresentStatus.00000000
Path: UPS.P...
2006 Sep 08
3
newhidups with APC Smart-UPS 1500
Hello,
I'm using the stable amd64 port of Debian Linux. I installed (the
latest) nut-2.0.1-4 and nut-usb packages for utilizing an APC Smart-UPS
1500 USB. I tried "apcupsd" first but "nut" makes an even more
sophisticated impression on me and has more security options.
I had problems with the newhidups driver. It didn't find a device with
matching VendorID. And
2007 Feb 26
1
Tripp Lite USB UPS
...Size: 1, Value: 1.000000
Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Input, ReportID: 0x32,
Offset: 21, Size: 1, Value: 0.000000
Path: UPS.PowerSummary.PresentStatus.FullyDischarged, Type: Input, ReportID:
0x32, Offset: 22, Size: 1, Value: 0.000000
Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID:
0x32, Offset: 23, Size: 1, Value: 0.000000
Path: UPS.PowerSummary.PresentStatus.InternalFailure, Type: Feature, ReportID:
0x32, Offset: 7, Size: 1, Value: 0.000000
Path: UPS.PowerSummary.PresentStatus.ShutdownImminent, Type: Feature,
ReportID: 0x32, Offset: 9, Size:...
2017 Dec 18
2
Tripp-Lite BCPERS450 shutdown/restart problems
...1, Value: 1
0.066736 Path: UPS.PowerSummary.PresentStatus.Charging, Type: Input, ReportID: 0x32, Offset: 2, Size: 1, Value: 1
to 0.066756 Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Input, ReportID: 0x32, Offset: 3, Size: 1, Value: 0
0.066777 Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID: 0x32, Offset: 4, Size: 1, Value: 0
0.066798 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Input, ReportID: 0x32, Offset: 5, Size: 1, Value: 0
0.066819 Path: UPS.PowerSummary.PresentStatus.FullyCharged, Type: Input, ReportID: 0x32, Offset:...
2005 Jul 22
1
Another HID USB UPS
....BelowRemainingCapacityLimit
Path: UPS.PowerSummary.PresentStatus.ShutdownImminent
Path: UPS.PowerSummary.PresentStatus.ShutdownImminent
Path: UPS.PowerSummary.PresentStatus.RemainingTimeLimitExpired
Path: UPS.PowerSummary.PresentStatus.RemainingTimeLimitExpired
Path: UPS.PowerSummary.PresentStatus.NeedReplacement
Path: UPS.PowerSummary.PresentStatus.NeedReplacement
Path: UPS.PowerSummary.PresentStatus.OverLoad
Path: UPS.PowerSummary.PresentStatus.OverLoad
Path: UPS.PowerSummary.PresentStatus.00000000
Path: UPS.PowerSummary.PresentStatus.00000000
....................... a total of 46 PresentStatus.00000...
2016 May 28
2
Powercom INF-800 support
...mary.PresentStatus.RemainingTimeLimitExpired, Type: Input,
ReportID: 0x0a, Offset: 5, Size: 1, Value: 0
0.130630 Path:
UPS.PowerSummary.PresentStatus.RemainingTimeLimitExpired, Type: Feature,
ReportID: 0x0a, Offset: 5, Size: 1, Value: 0
0.130634 Path: UPS.PowerSummary.PresentStatus.NeedReplacement,
Type: Input, ReportID: 0x0a, Offset: 6, Size: 1, Value: 0
0.130638 Path: UPS.PowerSummary.PresentStatus.NeedReplacement,
Type: Feature, ReportID: 0x0a, Offset: 6, Size: 1, Value: 0
0.130643 Path:
UPS.PowerSummary.PresentStatus.VoltageNotRegulated, Type: Input,
ReportID: 0x0a...
2013 Nov 27
0
several problems with Powercom BNT-500AP
...:
> I took the log. Here's what happened.
> Broadcast Message from nut at rasp
> (somewhere) at 16:18 ...
> UPS BNT500AP at localhost battery needs to be replaced
>
> occurred when for the first time value "1" was read as "UPS.PowerSummary.PresentStatus.NeedReplacement", on this line:
> 6409.240690 Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID: 0x0a, Offset: 6, Size: 1, Value: 1
> It happened for 9 times, but the message appeared only on first.
Correct, upsmon throttles the REPLBATT event:
http://www.networkupstools...
2020 Jun 28
2
AVR750U Low Power not Triggering Shutdown
...8262 Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Input, ReportID: 0x32, Offset: 21, Size: 1, Value: 0
0.028286 Path: UPS.PowerSummary.PresentStatus.FullyDischarged, Type: Input, ReportID: 0x32, Offset: 22, Size: 1, Value: 0
0.028310 Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID: 0x32, Offset: 23, Size: 1, Value: 0
0.028333 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature, ReportID: 0x32, Offset: 18, Size: 1, Value: 0
0.028357 Path: UPS.PowerSummary.PresentStatus.FullyCharged, Type: Feature, ReportID:...
2008 Jan 02
2
[nut-commits] svn commit r1210 - in trunk: . drivers
On Jan 2, 2008 3:34 PM, Arjen de Korte <adkorte-guest at alioth.debian.org> wrote:
> Author: adkorte-guest
> Date: Wed Jan 2 20:34:26 2008
> New Revision: 1210
>
> Log:
> Parsing continues if the HID path for a report ends in 0x00000000 (these will not be made available). Commonly used as placeholders.
>
> It looks like (but correct me if I'm wrong) that reports
2013 Jun 08
0
several problems with Powercom BNT-500AP
On Jun 8, 2013, at 12:57 PM, M?rti?? Pu??tis wrote:
> I'll take a longer driver log. This page (http://www.networkupstools.org/support.html) says that to take a driver log NUT should be stopped, so I won't be able to tell when these events occurred within a driver log.
Hmm, I didn't realize it said that, but I think that's to prevent having two copies of the same driver
2006 Oct 18
2
newhidups with APC Smart-UPS 1500
...> Feature, Value: 0.000000
> > Path: UPS.PowerSummary.PresentStatus.CommunicationLost, Type: Input,
> > Value: 0.000000
> > Path: UPS.PowerSummary.PresentStatus.CommunicationLost, Type:
> > Feature,
> > Value: 0.000000
> > Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input,
> > Value: 0.000000
> > Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Feature,
> > Value: 0.000000
> > Path: UPS.PowerSummary.PresentStatus.Overload, Type: Input, Value:
> > 0.000000
> > Path: UPS.PowerSummary.PresentStatus.Overlo...
2008 Dec 31
2
Unknown product ID for Tripp-Lite UPS (SU1500RTXL2UA)
..., Size: 1, Value: 0.000000
Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Input, ReportID: 0x32, Offset: 21, Size: 1, Value: 0.000000
Path: UPS.PowerSummary.PresentStatus.FullyDischarged, Type: Input, ReportID: 0x32, Offset: 22, Size: 1, Value: 0.000000
Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID: 0x32, Offset: 23, Size: 1, Value: 0.000000
Path: UPS.PowerSummary.PresentStatus.InternalFailure, Type: Feature, ReportID: 0x32, Offset: 7, Size: 1, Value: 0.000000
Path: UPS.PowerSummary.PresentStatus.ShutdownImminent, Type: Feature, ReportID: 0x32, Offset: 9, Size: 1,...
2013 Jun 08
2
several problems with Powercom BNT-500AP
Thanks for the support.
Here's list of when transition to battery with return to utility power within a few seconds occurred in last few days:
Wednesday
1:41
11:48
11:54
12:59
13:42
14:42
18:13
18:14
Thursday
5:23
Friday
5:12
7:39
7:43
Saturday
7:34
Here's list of when messages that battery needs replacement occurred:
Wednesday
20:34
Thursday
9:07
23:09
Friday
18:25
Saturday
7:32
19:47
2006 Feb 08
2
2.0.3-pre2: Spurious UPS UPS@localhost battery is
Peter Selinger wrote:
> Hm. I need more information, as NUT seems to garble the values even
> before I can see them. I am not so worried about the date and
> temperatures (although, strangely, the battery replacement date
> appears to be Sept 25, 2001, which makes no sense). But the voltage is
> definitely important.
>
> [...]
>
Thanks Peter - I'll send the new