search for: gamatron

Displaying 20 results from an estimated 44 matches for "gamatron".

Did you mean: gamatronic
2013 Dec 19
0
Gamatronic company
On Dec 18, 2013, at 3:17 AM, Leon Vak wrote: > Actually, someone has already done most of the work for our units, however I might have general technical details to contribute, like the fact that the driver for our equipment is called "gamatronic", while actually it is just the well-known SEC protocol (from the former Systems Enhancement Corporation) and not our invention. I wonder who I have to contact for structural changes like this, and what's the best way to connect a programmer on our side to the project. From docs/acknowl...
2006 Mar 22
0
Gamatronic Smart Compact 750 with NUTs
I was told by someone who used to have a Gamatronic to use the Fenton driver. However, when I use the Fenton driver I receive the following error: Unknown ups - please report this ID string: #GAMATRONICS SC06GM0G V8.0 Detected Unknown C06GM0G on /dev/ttyS1 The person who pointed me at this driver mentioned that Gamatronic changed their...
2013 Dec 17
4
Gamatronic company
Greetings to all developers of the Network UPS Tools, and Merry Christmas greetings to those of you who celebrate! I have been looking in to your work from time to time, and I am very impressed with your efforts. I think this is a good time to officially supply the required information about Gamatronic products to the community. Furthermore, I would like to know how our company may contribute to the development effort. I hope that relevant people can contact me to further discuss these subjects. BR, and Happy New Year! Leon Vak Control & Management Manager <http://www.gamatron...
2006 May 01
5
Gamatronic UPS using nut 2.0.3
I have a Gamatronic Smart Compact 750. I have it connected to my linux machine via serial cable and am running nut 2.0.3. There is no interruption in power, but the ups is reporting OB (on battery). Is there a configuration option I am missing? The relevant ups.conf entry is: [Gamatronic] port = /dev/tt...
2006 Jun 14
3
Trouble Configuring NUT with Gamatronic USB
Hi I am running FC5 with nut coming from the fc5 extras repositories. I am trying to configure a Gamatronic D-Compact ups. The cable that came with the ups has a serial connector on one end and a usb on the other. cat /proc/bus/usb/devices produces T: Bus=01 Lev=01 Prnt=01 Port=01 Cnt=01 Dev#= 4 Spd=1.5 MxCh= 0 D: Ver= 1.10 Cls=00(>ifc ) Sub=00 Prot=00 MxPS= 8 #Cfgs= 1 P: Vendor=0925 ProdID...
2016 Jan 13
2
[HCL] NHS Laser Senoidal 5000VA supported by gamatronic
...lt;clepple at gmail.com> Para: "Thiago Wiezbicki - NHS" <thiago.wiezbicki at nhs.com.br> Cc: "nut-upsdev" <nut-upsdev at lists.alioth.debian.org> Enviadas: S?bado, 9 de janeiro de 2016 19:41:09 Assunto: Re: [Nut-upsdev] [HCL] NHS Laser Senoidal 5000VA supported by gamatronic On Jan 8, 2016, at 7:09 AM, Thiago Wiezbicki - NHS <thiago.wiezbicki at nhs.com.br> wrote: > >>> battery.runtime: 00076 >>> battery.runtime.low: 59940 >> >> This seems rather high. This variable is supposed to represent the runtime [in seconds] below whic...
2016 Jan 06
0
[HCL] NHS Laser Senoidal 5000VA supported by gamatronic
...is this with a different load? > battery.runtime.low: 59940 > battery.temperature: 00 Is this fixed at 0, or is there a temperature option? > battery.voltage: 163.4 > device.mfr: NHS Sistemas de Energia > device.model: Laser Senoidal 5000VA > device.type: ups > driver.name: gamatronic > driver.parameter.pollinterval: 20 > driver.parameter.port: /dev/ttyACM2 > driver.version: 2.6.3 > driver.version.internal: 0.02 > input.frequency: 59.9 > input.transfer.high: 144 > input.transfer.low: 096 > input.voltage: 127.6 > input.voltage.nominal: 120 > output...
2015 Dec 29
2
[HCL] NHS Laser Senoidal 5000VA supported by gamatronic
...is in normal condition: battery.charge: 100 battery.current: 0.4 battery.date: 12292015 battery.runtime: 00000 battery.runtime.low: 59940 battery.temperature: 00 battery.voltage: 163.4 device.mfr: NHS Sistemas de Energia device.model: Laser Senoidal 5000VA device.type: ups driver.name: gamatronic driver.parameter.pollinterval: 20 driver.parameter.port: /dev/ttyACM2 driver.version: 2.6.3 driver.version.internal: 0.02 input.frequency: 59.9 input.transfer.high: 144 input.transfer.low: 096 input.voltage: 127.6 input.voltage.nominal: 120 output.current: 0.0 output.frequency: 60.0 o...
2007 Mar 20
1
Re: [nut-commits] svn commit r879 - in trunk: . drivers
...acker/index.php?func=detail&aid=303719&group_id=30602&atid=411544 If you have a newer version of that patch, let me know and we can add it. On 3/19/07, Charles Lepple <clepple-guest@alioth.debian.org> wrote: > Log: > applied patch from Michal Vaner to correct comparison in gamatronic driver. > [Alioth Bug #304063] > > > Modified: trunk/ChangeLog > ============================================================================== > --- trunk/ChangeLog (original) > +++ trunk/ChangeLog Tue Mar 20 03:14:09 2007 > @@ -1,3 +1,8 @@ > +Tue Mar 20 03:11:...
2014 Nov 12
2
[HCL] NHS Expert C Online 6000 supported by gamatronic
...me: Expert C Online 6000 upsc output: battery.charge: 100 battery.current: 0.6 battery.date: 01012014 battery.runtime: 00000 battery.runtime.low: 59940 battery.temperature: 29 battery.voltage: 210.5 device.mfr: NHS Sistemas de Energia device.model: EXPERT GIII 8kVA device.type: ups driver.name: gamatronic driver.parameter.pollinterval: 20 driver.parameter.port: /dev/ttyACM0 driver.version: 2.6.3 driver.version.internal: 0.02 input.frequency: 60.1 input.transfer.high: 265 input.transfer.low: 165 input.voltage: 217.0 input.voltage.nominal: 220 output.current: 0.0 output.frequency: 60.1 output.voltag...
2016 Jan 14
0
[HCL] NHS Laser Senoidal 5000VA supported by gamatronic
On Jan 13, 2016, at 6:00 AM, Thiago Wiezbicki - NHS <thiago.wiezbicki at nhs.com.br> wrote: > > The battery.run.low can be higher than battery.runtime, do you agree? I agree with that statement, given what the gamatronic driver is currently reporting. However, I think it should report the elapsed time as battery.runtime.elapsed. I have created a Github issue to clarify the documentation, and another to patch the driver to be consistent with the other NUT drivers: https://github.com/networkupstools/nut/issues/...
2014 Nov 17
0
[HCL] NHS Expert C Online 6000 supported by gamatronic
...attery.temperature: 29 > battery.voltage: 210.5 210.5 V seems reasonable for the specifications. Is there a way in the SEC protocol to report "battery.voltage.nominal"? > device.mfr: NHS Sistemas de Energia > device.model: EXPERT GIII 8kVA > device.type: ups > driver.name: gamatronic > driver.parameter.pollinterval: 20 > driver.parameter.port: /dev/ttyACM0 For the HCL, should we list this as a serial UPS, or is it USB that is auto-detected by the Linux kernel as a USB-to-serial converter? If it is the latter, what are the USB VendorID and ProductID? You can send the ou...
2016 Jan 08
2
[HCL] NHS Laser Senoidal 5000VA supported by gamatronic
...his fixed at 0, or is there a temperature option? In this case, this UPS doesn't have a temperature sensor, therefore this value is equal zero. > battery.voltage: 163.4 > device.mfr: NHS Sistemas de Energia > device.model: Laser Senoidal 5000VA > device.type: ups > driver.name: gamatronic > driver.parameter.pollinterval: 20 > driver.parameter.port: /dev/ttyACM2 > driver.version: 2.6.3 > driver.version.internal: 0.02 > input.frequency: 59.9 > input.transfer.high: 144 > input.transfer.low: 096 > input.voltage: 127.6 > input.voltage.nominal: 120 > output...
2013 Dec 18
0
Gamatronic company
...evelopers of the Network UPS Tools, and Merry > Christmas greetings to those of you who celebrate! > > I have been looking in to your work from time to time, and I am very > impressed with your efforts. I think this is a good time to officially > supply the required information about Gamatronic products to the > community. Furthermore, I would like to know how our company may > contribute to the development effort. I hope that relevant people can > contact me to further discuss these subjects. > > BR, and Happy New Year! > > > *Leon Vak* > Control & Manage...
2014 Nov 23
0
[HCL] NHS Expert C Online 6000 supported by gamatronic
On Nov 22, 2014, at 5:16 AM, Thiago Wiezbicki <thiagowzb at gmail.com> wrote: > Below , it's a second upsc command using our UPS on battery and with device ID, battery time, battery low time that UPS calcs correctly. Let me remember now, We have the same UPS in 6, 8, 10 and 12 kVA version, and it's names are : Expert C Online 6000 , 8000 , 10000 and 12000 ( or Expert G III
2014 Nov 26
1
[HCL] NHS Expert C Online 6000 supported by gamatronic
What information Do I need to provide more, beyond upsc and shutdown tests for add these devices on HCL ? Thanks, ------------------------------ Thiago Wiezbicki -------------- next part -------------- An HTML attachment was scrubbed... URL: <http://lists.alioth.debian.org/pipermail/nut-upsdev/attachments/20141125/07793b94/attachment-0001.html>
2016 Jan 09
0
[HCL] NHS Laser Senoidal 5000VA supported by gamatronic
On Jan 8, 2016, at 7:09 AM, Thiago Wiezbicki - NHS <thiago.wiezbicki at nhs.com.br> wrote: > >>> battery.runtime: 00076 >>> battery.runtime.low: 59940 >> >> This seems rather high. This variable is supposed to represent the runtime [in seconds] below which the UPS will signal "LB", but this capture only shows "OB". > > This value
2007 Mar 21
1
gamatronic/sec driver: gettimeofday
On 3/20/07, Julius Malkiewicz <jpmalkiewicz@gmail.com> wrote: > I would like to use the gettimeofday() call to do some timing - but > it is invoked optionally, therefore it is _not_ required. I'm aware > that different unix(es) have different header files to include to get > to the gettimeofday() syscall - on linux it is <sys/time.h>. > > How do I modify the
2013 Dec 18
1
Gamatronic company
On 12/17/2013 08:43 PM, Ted Mittelstaedt wrote: > > Before doing that you should try to make some kind of proposal. > Basically you want to say how easy you think it would be to support your > product. For example if your product speaks an interface language > that is very similar to other products that are already supported, a > developer can easily take an existing module
2014 Nov 22
2
[HCL] NHS Expert C Online 6000 supported by gamatronic
...an see in upsc output). respectively. battery.charge: 087 battery.current: 0.0 battery.date: 11172014 battery.runtime: 00687 battery.runtime.low: 3780 battery.temperature: 27 battery.voltage: 198.9 device.mfr: NHS Sistemas de Energia device.model: EXPERT GIII 8kVA device.type: ups driver.name: gamatronic driver.parameter.pollinterval: 20 driver.parameter.port: /dev/ttyS0 driver.version: 2.6.3 driver.version.internal: 0.02 input.frequency: 0.0 input.transfer.high: 265 input.transfer.low: 165 input.voltage: 0.0 input.voltage.nominal: 220 output.current: 0.0 output.frequency: 60.0 output.voltage: 12...