[HCL] CyberPower EC350G supported by usbhid-ups
[shutdown sequence] I have tested and verified the shutdown sequence works. [manufacturor] https://www.cyberpowersystems.com/product/ups/ec350g/ mbeisser at nas:~$ upsc ups Init SSL without certificate database battery.charge: 100 battery.charge.low: 10 battery.charge.warning: 20 battery.mfr.date: CPS battery.runtime: 1575 battery.runtime.low: 300 battery.type: PbAcid battery.voltage: 9.3 battery.voltage.nominal: 1...
2006 May 07
3
Yet another HID device - Cyberpower AE550
...one and their 485 don't provide a load measurement -- the Windows drivers kick it onto battery for a timed period and measure the drain to guess the runtime -- apparently all their other HID models do offer it. (See the note hidden on item 7 of the 'Status Window' documentation: http://cyberpowersystems.com/pp_pe.asp) Also, Ubuntu's package of 2.0.3 doesn't populate /etc/hotplug/usb; I can't tell if that's really a problem or not. -Gratefully and sleep-deprived, -Joe "Floid" Kanowitz
2012 May 28
1
[HCL] Cyber Power Systems CP1000PFCLCD supported by usbhid-ups
...hutdown command coincided with the UPS's own notion of "critical battery" (and associated beeping), which is about 2 minutes runtime remaining (I have about 36 minutes at my typical load). I don't think the UPS's critical level is adjustable. = Product link = http://www.cyberpowersystems.com/products/ups-systems/adaptive-sinewave-series/CP1000PFCLCD.html -------------- next part -------------- An embedded and charset-unspecified text was scrubbed... Name: CP1000PFCLCD-upsc.txt URL: <http://lists.alioth.debian.org/pipermail/nut-upsdev/attachments/20120527/48c9947b/attachment.txt&...
2012 Feb 22
1
[HCL] CyberPower OR700 supported by usbhid-ups
CyberPower OR700LCDRM1U (http://www.cyberpowersystems.com/products/ups-systems/smart-app-ups/rackmount-lcd/OR700LCDRM1U.html) upsc output: battery.charge: 100 battery.charge.low: 10 battery.charge.warning: 20 battery.mfr.date: CPS battery.runtime: 6000 battery.runtime.low: 300 battery.type: PbAcid battery.voltage: 14.5 battery.voltage.nominal: 12 dev...
2024 Jan 13
1
Cyber Power LE1000DG UPS
I have a Cyber Power LE1000DG UPS I got from Best Buy this weekend. I plan to use it with a TrueNAS scale system, and it is connected via USB. Vendor link: https://www.cyberpowersystems.com/product/ups/battery-backup/le1000dg/. TrueNAS has you pick a UPS driver. I could not find any "LE" related models on https://networkupstools.org/stable-hcl.html (which is the list TrueNAS uses). Per your guidance on that page, I tried one that I hoped was compatible: "Cyber Powe...
2020 Oct 31
2
ups.test.result meaning
Hi folks, new to list... nut 2.7.2 on Ubuntu 16.04 with Cyberpowersystems CP1350PFCLCD. After performing upscmd cp1350 at localhost test.battery.start.quick the result was "Done and warning". I searched through syslog but could find no additional information. What is the warning? Battery charge was 100% before test was performed. Here's the full output f...
2012 Apr 26
1
[HCL] CyberPower Systems PR6000LCDRTXL5U supported by usbhid-ups
CyberPower Systems PR6000LCDRTXL5U http://www.cyberpowersystems.com/products/ups-systems/smart-app-ups/pp-series/PR6000LCDRTXL5U.html I had to create the following udev rule (on RHEL6): ATTR{idVendor}=="0764", ATTR{idProduct}=="0601", MODE="664", GROUP="dialout" Shutdown testing successful. UPS comes back online after t...
2020 Oct 21
1
Can't get CyberPower UPS to work with Raspberry Pi 4
...ic.php?t=240651&p=1508882#p1508882 ) exact device name and related information (manufacturing date, web pointers, …) lsusb reports: ID 0764:0501 Cyber Power System, Inc. CP1500 AVR UPS Actual model number is CST135LXU according to the device's labeling. Here's the web page: https://www.cyberpowersystems.com/product/ups/battery-backup/cst135xlu/ complete problem description, with any relevant traces, like system log excerpts, and driver debug output. You can obtain the latter using the following command, as root and after having stopped NUT: /path/to/driver -DD -a <upsname> After installing...
2020 Oct 25
4
Can't get CyberPower UPS to work with Raspberry Pi 4
This was very helpful for me, thank you! On Sat, Oct 24, 2020 at 9:06 AM Charles Lepple <clepple at gmail.com> wrote: > The easiest way to tell if upsd is working is to run "upsc -l" on the same > system, which will list the NUT UPS names, and then run e.g. "upsc mge" > (replacing "mge" with the name returned by "upsc -l") > Here was the
2009 Jul 28
4
Patch for drivers.list
-----BEGIN PGP SIGNED MESSAGE----- Hash: SHA1 Just a little patch for the drivers.list The "Cyber Power Systems Intelligent Series CP1500EAVRLCD" ups http://eu.cyberpowersystems.com/products/ups_systems/intelligent/cp1500eavrlcd.htm Got one here running (see: https://nut.stillbilde.net/cgi-bin/nut/upsstats.cgi?host=CyberPower at upsmonitor) Works flawlessly. Patch as follows: root(upsmonitor)/usr/local/etc/nut# diff -u driver.list driver.list.new - --- driver.list 2009...
2013 Nov 22
0
[HCL] CyberPower LE825G supported by Cyber Power Systems ups 2 685AVR USB (usbhid-ups) driver
...inal: 120 output.voltage: 126.0 ups.beeper.status: enabled ups.delay.shutdown: 20 ups.delay.start: 30 ups.load: 29 ups.mfr: CPS ups.model: CP825AVR-G ups.productid: 0501 ups.realpower.nominal: 450 ups.status: OL ups.timer.shutdown: -1 ups.timer.start: 0 ups.vendorid: 0764 Product page: http://www.cyberpowersystems.com/products/ups-systems/retail-products/LE825G.html Operating environment: FreeNAS-9.1.1-RELEASE-x64 (a752d35) System: Dell Inspiron 660s, Pentium G2030 @ 3.00GHz, 4GB Memory
2018 Sep 26
1
[HCL] Cyber Power Systems CP600LCD supported by usbhid-ups
Cyber Power Systems CP600LCD https://www.cyberpowersystems.com/product/ups/cp600lcd/ upsc output: battery.charge: 100 battery.charge.low: 10 battery.charge.warning: 20 battery.mfr.date: CPS battery.runtime: 2220 battery.runtime.low: 300 battery.type: PbAcid battery.voltage: 13.5 battery.voltage.nominal: 12 device.mfr: CPS device.model: UPS CP600 device.ty...
2019 Mar 06
0
HCL Cyberpower CPS-850AVRLCD supported by usbhid
Cyberpower CPS850avrlcd https://www.cyberpowersystems.com/product/ups/cp850avrlcd/ shutdown sequence: UNTESTED upsc output: _____  sudo upsc cp-ups battery.charge: 100 battery.charge.low: 10 battery.charge.warning: 20 battery.mfr.date: CPS battery.runtime: 1230 battery.runtime.low: 300 battery.type: PbAcid battery.voltage: 13.5 battery.voltage.no...
2020 Oct 31
0
ups.test.result meaning
...ing to guess that since your test runtime of 305 is very close to the low limit of 300, that's the warning. Not yet a fail, but very, very close. On October 31, 2020 11:41:39 AM CDT, Rick Dicaire <kritek at gmail.com> wrote: >Hi folks, new to list... >nut 2.7.2 on Ubuntu 16.04 with Cyberpowersystems CP1350PFCLCD. > >After performing upscmd cp1350 at localhost test.battery.start.quick the >result was "Done and warning". I searched through syslog but could find no >additional information. > >What is the warning? > >Battery charge was 100% before test was perform...
2020 Oct 26
0
Can't get CyberPower UPS to work with Raspberry Pi 4
...ID 0.4 > driver.version.internal: 0.41 > input.voltage: 121.0 > input.voltage.nominal: 120 > output.voltage: 137.0 Given the description on the product page you sent earlier, the UPS is likely not providing 137.0 V, but is bypassing the transformer since the power is good. https://www.cyberpowersystems.com/product/ups/battery-backup/cst135xlu/ This is another known CyberPower issue, and fixing it properly requires making some changes deep in the core USB HID code (that would require a lot of testing on other vendors' equipment) for what is basically a cosmetic issue: https://github.com/netw...
2011 Mar 31
1
Startup timing issue with CyberPower CP425HG UPS
...s, other than to perhaps start the "ups" service from the udev rules file if a known USB UPS device has been found, but that seems like a rather ugly way to go about this. Does anyone have any thoughts? System information: Fedora 11, Kernel 2.6.30, NUT 2.4.3 UPS product page: http://www.cyberpowersystems.com/products/ups-systems/soho-ups/CP425HG.html Thanks, Arun
2018 Sep 26
0
[HCL] Cyber Power Systems AVRG750U supported by usbhid-ups
Cyber Power Systems AVRG750U https://www.cyberpowersystems.com/product/ups/avrg750u/ upsc output: battery.charge: 100 battery.charge.low: 10 battery.charge.warning: 20 battery.mfr.date: CPS battery.runtime: 15360 battery.runtime.low: 300 battery.type: PbAcid battery.voltage: 24.0 battery.voltage.nominal: 24 device.mfr: CPS device.model: AVRG750U device.se...
2024 Apr 23
1
CyberPower CST150UC: Question re: battery.runtime.low configuration settings
...low for details. Thank you OS name and version: ?? ?Description:??? Debian GNU/Linux 12 (bookworm) ?? ?Release:??????? 12 ?? ?Codename:?????? bookworm exact NUT version: ?? ?Version: 2.8.0-7 NUT installation method: ?? ?apt install nut exact device name and related information: https://www.cyberpowersystems.com/product/ups/battery-backup/cst150uc/ ?? ?device.model: CST150UC ?? ?driver.version: 2.8.0 ?? ?driver.version.data: CyberPower HID 0.6 ?? ?driver.version.internal: 0.47 ?? ?driver.version.usb: libusb-1.0.26 (API: 0x1000109) ?? ?ups.vendorid: 0764 supported UPS variables (default values PR...
2015 Jan 21
2
CyberPower BR850ELCD ignores offdelay and turns itself back on while still on battery
...r.start" is also back to default. I'm running Debian 7 with the latest security updates installed on an ODroid U3 (armhf architecture). NUT version is 2.6.4-2.3+deb7u1 and was installed via apt-get package manager. UPS is the CyberPower BR850ELCD - specs are on the homepage: http://eu.cyberpowersystems.com/products/ups_systems/brics_lcd/br850elcd.htm Does anyone have an idea on what I could change to get the UPS to not turn back on while still on battery? As a next test, I'll try to run the battery down to see how it acts then. I'm hoping that it'll not turn on the power until the...
2016 Dec 08
2
[HCL] Cyber Power Systems EC750G supported by usbhid-ups
...battery is low Dec 8 13:14:24 ftest upsmon[2949]: Executing automatic power-fail shutdown Dec 8 13:14:24 ftest upsmon[2949]: Auto logout and shutdown proceeding Dec 8 13:14:29 ftest shutdown: power-down by mike: ==================================== Manufacturer's webpage: https://www.cyberpowersystems.com/products/ups/desktop/ec750g ==================================== Misc. The result of the command upscmd -u user -p password myups load.off.delay 300 is an immediate power-off, no delay. ==================================== Let me know if there's any other info that would be useful....