search for: activepow

Displaying 20 results from an estimated 26 matches for "activepow".

Did you mean: activep
2007 Feb 16
0
Re: NUT works with more ActivePower UPSes
Hello Tomasz, first, thanks for your feedback. > First of all, I want thank you for excellent NUT software :) It saved my ass > from BIG pain :) > > I want to confirm that NUT works with ActivePower UPSes (ActivePower is Polish > company). I have two machines: > > 1st machine: > * mainboard: Asus ATX with Intel Celeron 2.53 GHz, > * OS: openSUSE 10.1, > * kernel: 2.6.16.21-0.13-default, > * UPS: ActivePower 400 connected to /dev/ttyS0, > * NUT: 2.04 (RPM ver...
2006 Apr 07
0
Network UPS Tools (NUT) driver for Activepower 1400VA
I have found by trial and error that the Activepower 1400VA UPS (uninterruptible power supply) (http://www.activepower.pl/1400.php) is best driven by the powermust driver in NUT (Network UPS Tools), on an RS232 cable. The USB connection does not seem to yield, use the serial RS232 cable. This took me quite a while to find out, so I thought I w...
2011 Nov 08
0
mge-xml.c voltage conversion problem
...el in order to find an alternative way to poll our two "Galaxy 5000 UPS" units. I started the tests with netxml-ups driver. The very first thing I noticed that upsc reports 1/10th of input/output AC voltages. Raw HTTP stream: [...] <OBJECT name='UPS.PowerConverter.Output.Phase[1].ActivePower'>0</OBJECT> <OBJECT name='UPS.PowerConverter.Output.Phase[1].ApparentPower'>0</OBJECT> <OBJECT name='UPS.PowerConverter.Input[2].Phase[11].Voltage'>0</OBJECT> <OBJECT name='UPS.PowerConverter.Input[2].Phase[1].Current'>0</OBJEC...
2007 Dec 05
2
Crash when I start driver
...ind object UPS.BatterySystem.Battery.Voltage - Unable to fetch string 24 Can't find object UPS.BatterySystem.Temperature Can't find object UPS.OutletSystem.Outlet.DelayBeforeStartup Can't find object UPS.OutletSystem.Outlet.DelayBeforeReboot Can't find object UPS.OutletSystem.Outlet.ActivePower Can't find object UPS.PowerConverter.Output.ActivePower Can't find object UPS.OutletSystem.Outlet.PercentLoad Can't find object UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit Can't find object UPS.PowerSummary.PresentStatus.FullyCharged Can't find object UPS.PowerC...
2018 Jan 16
2
Eaton 5PX after battery replacement still says "replace battery" in NUT
...Feature, ReportID: 0x14, Offset: 0, Size: 8, Value: 50 5.175587 Path: UPS.Flow.[1].ConfigVoltage, Type: Feature, ReportID: 0x15, Offset: 0, Size: 16, Value: 230 5.215207 Path: UPS.Flow.[1].FlowID, Type: Feature, ReportID: 0x0b, Offset: 0, Size: 8, Value: 1 5.247504 Path: UPS.Flow.[4].ConfigActivePower, Type: Feature, ReportID: 0x74, Offset: 0, Size: 16, Value: 1800 5.283621 Path: UPS.Flow.[4].ConfigApparentPower, Type: Feature, ReportID: 0x75, Offset: 0, Size: 16, Value: 2000 5.320753 Path: UPS.Flow.[4].ConfigFrequency, Type: Feature, ReportID: 0x0d, Offset: 0, Size: 8, Value: 50 5.35...
2008 Dec 31
2
Unknown product ID for Tripp-Lite UPS (SU1500RTXL2UA)
...: 0x1b, Offset: 0, Size: 16, Value: 120.200000 Path: UPS.PowerConverter.Output.Frequency, Type: Feature, ReportID: 0x1c, Offset: 0, Size: 16, Value: 59.900000 Path: UPS.PowerConverter.Output.Current, Type: Feature, ReportID: 0x46, Offset: 0, Size: 16, Value: 0.000000 Path: UPS.PowerConverter.Output.ActivePower, Type: Feature, ReportID: 0x47, Offset: 0, Size: 16, Value: 0.000000 Path: UPS.PowerConverter.Output.LowVoltageTransfer, Type: Feature, ReportID: 0x06, Offset: 0, Size: 16, Value: 65.000000 Path: UPS.PowerConverter.Output.HighVoltageTransfer, Type: Feature, ReportID: 0x09, Offset: 0, Size: 16, Va...
2008 Jan 26
1
USBDEVFS_CONTROL error ?
...ingCapacityLimit Can't find object UPS.PowerSummary.RunTimeToEmpty Can't find object UPS.BatterySystem.Temperature Can't find object UPS.OutletSystem.Outlet.DelayBeforeStartup hu_find_infoval: no matching INFO_* value for this HID value (0) Can't find object UPS.OutletSystem.Outlet.ActivePower Can't find object UPS.PowerConverter.Output.ActivePower Can't find object UPS.OutletSystem.Outlet.PercentLoad Can't find object UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit Can't find object UPS.PowerSummary.PresentStatus.FullyCharged Can't find object UPS.PowerS...
2016 Dec 07
1
Incorrect scale on values for TRIPPLITE UPS
...: 0.00122 0.894188 Path: UPS.PowerConverter.Output.Frequency, Type: Feature, ReportID: 0x1c, Offset: 0, Size: 16, Value: 6020 0.898189 Path: UPS.PowerConverter.Output.Current, Type: Feature, ReportID: 0x46, Offset: 0, Size: 16, Value: 60 0.902185 Path: UPS.PowerConverter.Output.ActivePower, Type: Feature, ReportID: 0x47, Offset: 0, Size: 16, Value: 64 -------------- next part -------------- An HTML attachment was scrubbed... URL: <http://lists.alioth.debian.org/pipermail/nut-upsuser/attachments/20161207/b61ec404/attachment.html>
2020 Jan 01
2
Tripp Lite SMART1500LCD will not stay shut down when power is disconnected
...: 112.5 0.216425 Path: UPS.PowerConverter.Input.Frequency, Type: Feature, ReportID: 0x19, Offset: 0, Size: 16, Value: 59.8 0.218426 Path: UPS.PowerConverter.Output.Voltage, Type: Feature, ReportID: 0x1b, Offset: 0, Size: 16, Value: 112.4 0.220433 Path: UPS.PowerConverter.Output.ActivePower, Type: Feature, ReportID: 0x47, Offset: 0, Size: 16, Value: 0 0.222423 Path: UPS.PowerConverter.PresentStatus.VoltageOutOfRange, Type: Feature, ReportID: 0x22, Offset: 0, Size: 1, Value: 0 0.222594 Path: UPS.PowerConverter.PresentStatus.Buck, Type: Feature, ReportID: 0x22, Offset: 1...
2013 Aug 07
4
HP R1500 G3 problems
...Path: UPS.PowerConverter.PresentStatus.OverTemperature, Type: Feature, ReportID: 0x22, Offset: 6, Size: 1, Value: 0 0.643348 Path: UPS.PowerConverter.PresentStatus.InternalFailure, Type: Feature, ReportID: 0x22, Offset: 7, Size: 1, Value: 0 0.647091 Path: UPS.OutletSystem.Outlet.ActivePower, Type: Feature, ReportID: 0x54, Offset: 0, Size: 16, Value: 0 0.651117 Path: UPS.OutletSystem.Outlet.OutletID, Type: Feature, ReportID: 0x6e, Offset: 0, Size: 8, Value: 0 0.655117 Path: UPS.OutletSystem.Outlet.DelayBeforeShutdown, Type: Feature, ReportID: 0x15, Offset: 0, Size:...
2019 Dec 08
3
Tripp Lite SMART1500LCD repeatedly disconnecting and reconnecting
...: 113.8 0.200983 Path: UPS.PowerConverter.Input.Frequency, Type: Feature, ReportID: 0x19, Offset: 0, Size: 16, Value: 59.8 0.202979 Path: UPS.PowerConverter.Output.Voltage, Type: Feature, ReportID: 0x1b, Offset: 0, Size: 16, Value: 113.8 0.204980 Path: UPS.PowerConverter.Output.ActivePower, Type: Feature, ReportID: 0x47, Offset: 0, Size: 16, Value: 1.67e-05 0.206977 Path: UPS.PowerConverter.PresentStatus.VoltageOutOfRange, Type: Feature, ReportID: 0x22, Offset: 0, Size: 1, Value: 0 0.207138 Path: UPS.PowerConverter.PresentStatus.Buck, Type: Feature, ReportID: 0x22, Of...
2015 Aug 18
0
Need help with Tripp Lite SMART1300LCDT NUT v2.7.3
...ffset: 0, Size: 8, Value: 2 ? 51.974255???? Report[get]: (3 bytes) => 03 14 05 ? 51.974270???? Path: UPS.Flow.ConfigApparentPower, Type: Feature, ReportID: 0x03, Offset: 0, Size: 16, Value: 1300 ? 52.009206???? Report[get]: (3 bytes) => 47 27 01 ? 52.009223???? Path: UPS.PowerConverter.Output.ActivePower, Type: Feature, ReportID: 0x47, Offset: 0, Size: 16, Value: 295 ? 52.077118???? libusb_get_report: Unknown error ? 52.077136???? Can't retrieve Report 1e: Input/output error ? 52.077151???? upsdrv_updateinfo... ? 52.077158???? Got to reconnect! On Tuesday, August 18, 2015 10:05 AM, J...
2015 Aug 18
2
Need help with Tripp Lite SMART1300LCDT NUT v2.7.3
Here are all the usbconfig outputs you have requested. I have left a message with the Dev for NAS4Free to give up the ./configure for NUT portion.? I am hoping they will... usbconfig -u 0 -a 5 dump_device_desc? datanas: ~# usbconfig -u 0 -a 5 dump_device_desc ugen0.5: <TRIPP LITE UPS Tripp Lite> at usbus0, cfg=0 md=HOST spd=LOW (1.5Mbps) pwr=ON (100mA)? bLength = 0x0012 ? bDescriptorType =
2007 Feb 26
1
Tripp Lite USB UPS
...tput.Frequency, Type: Feature, ReportID: 0x1c, Offset: 0, Size: 16, Value: 60.000000 Report[r]: (3 bytes) => 46 1c 00 Path: UPS.PowerConverter.Output.Current, Type: Feature, ReportID: 0x46, Offset: 0, Size: 16, Value: 2.800000 Report[r]: (3 bytes) => 47 2d 01 Path: UPS.PowerConverter.Output.ActivePower, Type: Feature, ReportID: 0x47, Offset: 0, Size: 16, Value: 301.000000 Report[r]: (3 bytes) => 06 41 00 Path: UPS.PowerConverter.Output.LowVoltageTransfer, Type: Feature, ReportID: 0x06, Offset: 0, Size: 16, Value: 65.000000 Report[r]: (3 bytes) => 09 8a 00 Path: UPS.PowerConverter.Output...
2010 Feb 18
2
HP R1500 G2 UPS
...ize: 1, Value: 0.000000 Path: UPS.PowerConverter.PresentStatus.OverTemperature, Type: Feature, ReportID: 0x22, Offset: 6, Size: 1, Value: 0.000000 Path: UPS.PowerConverter.PresentStatus.InternalFailure, Type: Feature, ReportID: 0x22, Offset: 7, Size: 1, Value: 0.000000 Path: UPS.OutletSystem.Outlet.ActivePower, Type: Feature, ReportID: 0x54, Offset: 0, Size: 16, Value: 413.000000 Path: UPS.OutletSystem.Outlet.OutletID, Type: Feature, ReportID: 0x6e, Offset: 0, Size: 8, Value: 0.000000 Path: UPS.OutletSystem.Outlet.DelayBeforeShutdown, Type: Feature, ReportID: 0x15, Offset: 0, Size: 16, Value: -1.000000...
2016 May 03
2
New UPS Support: Eaton 5S 1000
Oops... changing that to --with-user=nut solved one problem. I have the driver, upsd and upsmon running now. Thank you! Now I'm back to another issue, every 2 seconds I get in the logs: May 3 13:45:23 myhost upsd[2587]: Connected to UPS [eaton]: usbhid-ups-eaton It seems happy to do this forever. On Tue, May 3, 2016 at 8:17 AM, Charles Lepple <clepple at gmail.com> wrote: > On
2016 May 04
2
New UPS Support: Eaton 5S 1000
...UPS.PowerConverter.Inverter.PresentStatus.InternalFailure, Type: Feature, ReportID: 0x03, Offset: 16, Size: 8, Value: 0 5.304101 Path: UPS.PowerConverter.Inverter.PresentStatus.InternalFailure, Type: Input, ReportID: 0x03, Offset: 16, Size: 8, Value: 0 5.304121 Path: UPS.PowerConverter.Output.ActivePower, Type: Feature, ReportID: 0x0e, Offset: 32, Size: 16, Value: 0 5.304131 Path: UPS.PowerConverter.Output.ApparentPower, Type: Feature, ReportID: 0x0e, Offset: 48, Size: 16, Value: 0 5.347975 Path: UPS.PowerConverter.Output.ExtendedVoltageMode, Type: Feature, ReportID: 0x1a, Offset: 0, Size:...
2017 Aug 21
5
TrippLite SMART1500LCD no delay before ups shutdown.
...: 115.1 0.162758 Path: UPS.PowerConverter.Input.Frequency, Type: Feature, ReportID: 0x19, Offset: 0, Size: 16, Value: 59.9 0.163350 Path: UPS.PowerConverter.Output.Voltage, Type: Feature, ReportID: 0x1b, Offset: 0, Size: 16, Value: 115 0.163773 Path: UPS.PowerConverter.Output.ActivePower, Type: Feature, ReportID: 0x47, Offset: 0, Size: 16, Value: 0 0.164292 Path: UPS.PowerConverter.PresentStatus.VoltageOutOfRange, Type: Feature, ReportID: 0x22, Offset: 0, Size: 1, Value: 0 0.164298 Path: UPS.PowerConverter.PresentStatus.Buck, Type: Feature, ReportID: 0x22, Offse...
2015 Aug 15
2
Small patch to scale the values for TRIPP-LITE SMART*LCDT's
Hi, I just decided to fix some scaling issues for my UPS (TRIPP-LITE SMART1500LCDT). Apparently that issue existed for some time (and I knew about it as well:-() See http://thread.gmane.org/gmane.comp.monitoring.nut.devel/6482 for a thread. My little patch is attached (against 2.7.3). It seems to be working better for me but I don't have any other TRIPP-LITE's to test that I did
2015 Aug 15
2
Small patch to scale the values for TRIPP-LITE SMART*LCDT's
Hi, I just decided to fix some scaling issues for my UPS (TRIPP-LITE SMART1500LCDT). Apparently that issue existed for some time (and I knew about it as well:-() See http://thread.gmane.org/gmane.comp.monitoring.nut.devel/6482 for a thread. My little patch is attached (against 2.7.3). It seems to be working better for me but I don't have any other TRIPP-LITE's to test that I did