Drew Plaster
2017-Oct-18 18:43 UTC
[Nut-upsuser] debian 8 "jessie" nut 2.7.2 slaves not shutting down
OS name and version, MASTER SYSTEM has three APC smart UPS 3000 UPS connected via USB debian 8 "jessie" Linux pdxvhtst01 3.16.0-4-amd64 #1 SMP Debian 3.16.43-2+deb8u5 (2017-09-19) x86_64 GNU/Linux SLAVE SYSTEMS monitoring MASTER via IP debian 8 "jessie" Linux geaaetst01 3.16.0-4-amd64 #1 SMP Debian 3.16.43-2+deb8u5 (2017-09-19) x86_64 GNU/Linux debian 8 "jessie" Linux pdxvhtst02 3.16.0-4-amd64 #1 SMP Debian 3.16.43-2+deb8u5 (2017-09-19) x86_64 GNU/Linux exact NUT version, Network UPS Tools upsmon 2.7.2 NUT installation method: from source tarball, package or Subversion, installed from package exact device name and related information (manufacturing date, web pointers, ...), device.mfr: American Power Conversion device.model: Smart-UPS 3000 device.type: ups driver.name: usbhid-ups driver.version: 2.7.2 driver.version.data: APC HID 0.95 driver.version.internal: 0.38 ups.firmware: UPS 06.5 / ID=18 ups.mfr: American Power Conversion ups.mfr.date: 2013/02/25 ups.model: Smart-UPS 3000 ups.productid: 0003 ups.vendorid: 051d complete problem description, with any relevant traces, like system log excerpts, and driver debug output. You can obtain the latter using the following command, as root and after having stopped NUT: there are three APC smart ups connected via usb cables to the master system, the master system shuts down as expected but the slave systems never shutdown eventhough I believe that all the configs are properly set the slaves should either shutdown when there is only one ups and it is running low on battery power offline or worst case shutdown after they cannot communicate with the master for longer than the HOSTSYNC 15 or UPS for longer than the DEADTIME 15 [otakHG_sigLogo] Drew Plaster | Systems Administrator 808 SW 3rd Avenue, Suite 300 | Portland, OR 97204 o: 503.415.2385 | c: 503.484.0168 | f: 503.415.2498 www.otak.com<http://www.otak.com> P at Otak, we consider the environment before printing emails. Disclaimer: The information transmitted in this e-mail message and attachments, if any, may contain confidential material, and is intended only for the use of the individual or entity named above. Distribution to, or review by, unauthorized persons is prohibited. In the event of the unauthorized use of any material in this transmission, neither Otak nor the sender shall have any liability and the recipient shall defend, indemnify and hold harmless the sender, Otak and its principals, agents, employees and subconsultants from all related claims and damages. The recipient understands and agrees that any use or distribution of the material in this transmission is conditioned upon the acceptance of the terms stated in this disclaimer. If you have received this transmission in error, immediately notify the sender and permanently delete this transmission including attachments, if any. -------------- next part -------------- An HTML attachment was scrubbed... URL: <http://lists.alioth.debian.org/pipermail/nut-upsuser/attachments/20171018/612fdca6/attachment.html> -------------- next part -------------- A non-text attachment was scrubbed... Name: image001.jpg Type: image/jpeg Size: 1762 bytes Desc: image001.jpg URL: <http://lists.alioth.debian.org/pipermail/nut-upsuser/attachments/20171018/612fdca6/attachment.jpg>
Roger Price
2017-Oct-18 19:53 UTC
[Nut-upsuser] debian 8 "jessie" nut 2.7.2 slaves not shutting down
On Wed, 18 Oct 2017, Drew Plaster wrote:> ??????????????? there are three APC smart ups connected via usb cables > to the master system, the master system shuts down as expected but the > slave systems never shutdown eventhough I believe that all the configs > are properly set the slaves should either shutdown when there is only > one ups and it is running low on battery power offline or worst case > shutdown after they cannot communicate with the master for longer than > the HOSTSYNC 15 or UPS for longer than the DEADTIME 15Hi, Could you show us your NUT configuration files? Please omit the comments, and double spacing will not be needed. Roger> Disclaimer: The information transmitted in this e-mail message and > attachments, if any, may contain confidential material, and is intended > only for the use of the individual or entity named above....It's probably best not to send such a disclaimer to a public mailing list with hundreds of subscribers.
Drew Plaster
2017-Oct-18 20:49 UTC
[Nut-upsuser] debian 8 "jessie" nut 2.7.2 slaves not shutting down
MASTER SYSTEM nut.conf MODE=netserver ups.conf [TOPAPC] driver = usbhid-ups port = auto pollonly serial = "IS1309002707" desc = "TOPAPC" [MIDAPC] driver = usbhid-ups port = auto pollonly serial = "IS1309001233" desc = "MIDAPC" [BOTAPC] driver = usbhid-ups port = auto pollonly serial = "IS1309001213" desc = "BOTAPC" upsd.conf LISTEN 127.0.0.1 3493 LISTEN 172.16.1.158 3493 upsd.users [admin] password = XXXXXXXXX actions = SET instcmds = ALL [user] password = XXXXXXXXX instcmds = ALL [upsmon] password = XXXXXXXXX upsmon master [upsmonslave] password = XXXXXXXXX upsmonslave slave [geaaetst01] password = XXXXXXXXX geaaetst01 slave [pdxvhtst02] password = XXXXXXXXX pdxvhtst02 slave upsmon.conf MONITOR TOPAPC at localhost 1 upsmon pass master MONITOR MIDAPC at localhost 1 upsmon pass master MONITOR BOTAPC at localhost 1 upsmon pass master MINSUPPLIES 1 SHUTDOWNCMD "/sbin/shutdown -h now" NOTIFYCMD /bin/notifynetadmins POLLFREQ 5 POLLFREQALERT 5 HOSTSYNC 15 DEADTIME 15 NOTIFYMSG ONLINE "UPS %s on line power" NOTIFYMSG ONBATT "UPS %s on battery" NOTIFYMSG LOWBATT "UPS %s battery is low" NOTIFYMSG FSD "UPS %s: forced shutdown in progress" NOTIFYMSG COMMOK "Communications with UPS %s established" NOTIFYMSG COMMBAD "Communications with UPS %s lost" NOTIFYMSG SHUTDOWN "Auto logout and shutdown proceeding" NOTIFYMSG REPLBATT "UPS %s battery needs to be replaced" NOTIFYMSG NOCOMM "UPS %s is unavailable" NOTIFYMSG NOPARENT "upsmon parent process died - shutdown impossible" NOTIFYFLAG ONLINE EXEC+SYSLOG+WALL NOTIFYFLAG ONBATT EXEC+SYSLOG+WALL NOTIFYFLAG LOWBATT EXEC+SYSLOG+WALL NOTIFYFLAG FSD EXEC+SYSLOG+WALL NOTIFYFLAG COMMOK EXEC+SYSLOG+WALL NOTIFYFLAG COMMBAD EXEC+SYSLOG+WALL NOTIFYFLAG SHUTDOWN EXEC+SYSLOG+WALL NOTIFYFLAG REPLBATT EXEC+SYSLOG+WALL NOTIFYFLAG NOCOMM EXEC+SYSLOG+WALL NOTIFYFLAG NOPARENT EXEC+SYSLOG+WALL RBWARNTIME 43200 NOCOMMWARNTIME 300 FINALDELAY 5 upssched.conf CMDSCRIPT /bin/upssched-cmd SLAVE SYSTEM (1) nut.conf MODE=netclient upsmon.conf MONITOR TOPAPC at 172.16.1.158 1 geaaetst01 pass slave MONITOR MIDAPC at 172.16.1.158 1 geaaetst01 pass slave MONITOR BOTAPC at 171.16.1.158 1 geaaetst01 pass slave MINSUPPLIES 1 SHUTDOWNCMD "/sbin/shutdown -h now" POLLFREQ 5 POLLFREQALERT 5 HOSTSYNC 15 DEADTIME 15 RBWARNTIME 43200 NOCOMMWARNTIME 300 FINALDELAY 1 upssched.conf CMDSCRIPT /bin/upssched-cmd SLAVE SYSTEM (2) nut.conf MODE=netclient upsmon.conf MONITOR TOPAPC at 172.16.1.158 1 pdxvhtst02 pass slave MONITOR MIDAPC at 172.16.1.158 1 pdxvhtst02 pass slave MONITOR BOTAPC at 171.16.1.158 1 pdxvhtst02 pass slave MINSUPPLIES 1 SHUTDOWNCMD "/sbin/shutdown -h now" POLLFREQ 5 POLLFREQALERT 5 HOSTSYNC 15 DEADTIME 15 RBWARNTIME 43200 NOCOMMWARNTIME 300 FINALDELAY 1 upssched.conf CMDSCRIPT /bin/upssched-cmd ? Drew Plaster | Systems Administrator 808 SW 3rd Avenue, Suite 300 |?Portland, OR 97204 o: 503.415.2385 |?c: 503.484.0168 | f:?503.415.2498 www.otak.com ? ??at Otak, we consider the environment before printing emails. ? Disclaimer: The information transmitted in this e-mail message and attachments, if any, may contain confidential material, and is intended only for the use of the individual or entity named above. Distribution to, or review by, unauthorized persons is prohibited. In the event of the unauthorized use of any material in this transmission, neither Otak nor the sender shall have any liability and the recipient shall defend, indemnify and hold harmless the sender, Otak and its principals, agents, employees and subconsultants from all related claims and damages. The recipient understands and agrees that any use or distribution of the material in this transmission is conditioned upon the acceptance of the terms stated in this disclaimer. If you have received this transmission in error, immediately notify the sender and permanently delete this?transmission including attachments, if any. -----Original Message----- From: Nut-upsuser [mailto:nut-upsuser-bounces+drew.plaster=otak.com at lists.alioth.debian.org] On Behalf Of Roger Price Sent: Wednesday, October 18, 2017 12:54 PM To: nut-upsuser Mailing List Subject: Re: [Nut-upsuser] debian 8 "jessie" nut 2.7.2 slaves not shutting down On Wed, 18 Oct 2017, Drew Plaster wrote:> ??????????????? there are three APC smart ups connected via usb cables > to the master system, the master system shuts down as expected but the > slave systems never shutdown eventhough I believe that all the configs > are properly set the slaves should either shutdown when there is only > one ups and it is running low on battery power offline or worst case > shutdown after they cannot communicate with the master for longer than > the HOSTSYNC 15 or UPS for longer than the DEADTIME 15Hi, Could you show us your NUT configuration files? Please omit the comments, and double spacing will not be needed. Roger> Disclaimer: The information transmitted in this e-mail message and > attachments, if any, may contain confidential material, and is > intended only for the use of the individual or entity named above....It's probably best not to send such a disclaimer to a public mailing list with hundreds of subscribers.
Maybe Matching Threads
- debian 8 "jessie" nut 2.7.2 slaves not shutting down
- debian 8 "jessie" nut 2.7.2 slaves not shutting down
- debian 8 "jessie" nut 2.7.2 slaves not shutting down
- debian 8 "jessie" nut 2.7.2 slaves not shutting down
- Configure NUT slaves for D-Link 320 ShareCenter NUT master