2017 Oct 18
2
debian 8 "jessie" nut 2.7.2 slaves not shutting down
...pected but the slave systems never shutdown eventhough I believe that all the configs are properly set the slaves should either shutdown when there is only one ups and it is running low on battery power offline or worst case shutdown after they cannot communicate with the master for longer than the HOSTSYNC 15 or UPS for longer than the DEADTIME 15
[otakHG_sigLogo]
Drew Plaster | Systems Administrator
808 SW 3rd Avenue, Suite 300 | Portland, OR 97204
o: 503.415.2385 | c: 503.484.0168 | f: 503.415.2498
www.otak.com<http://www.otak.com>
P at Otak, we consider the environment before printing em...
2020 Aug 14
8
Synology NAS is shutting down Ubuntu servers after very brief power outage (fwd)
So I finally got a test in after I changed my RPi to the master and everything else (including my Synology) to slaves. Before I did that though, I timed the shutdown of my Synology since it is the slowest slave to shutdown. It took 40 seconds to shutdown, so I changed HOSTSYNC in upsmon.conf on the master (“Proton”) to 60. I then did a test ("sudo upsmon -c fsd”). The slaves shutdown, then eventually the master, but the Synology never powered down and the UPS powered off which cut the power to it while it was still on. Anyone know what the heck is going on? I’m f...
2012 Oct 09
1
network-ups-tools won't shutdown my PC
...esc = <<EATON Ellipse ASR USBS 1600>>
upsd.conf :
MAXAGE 15
LISTEN 127.0.0.1 3493
MAXCONN 32
ACL all 0.0.0.0/0
ACL localhost 127.0.0.1/27
ACCEPT localhost
REJECT all
upsd.users :
[ups]
password = ups
upsmon.conf
MONITOR ellipse at localhost 1 ups ups master
MINSUPPLIES 1
FINALDELAY 5
HOSTSYNC 15
SHUTDOWNCMD "usr/bin/systemctl poweroff"
POWERDOWNFLAG /etc/killpower
POLLFREQ 5
POLLFREQALERT 5
DEADTIME 15
NOCOMMWARNTIME 300
RBWARNTIME 43200
upssched.conf :
CMDSCRIPT /opt/bin/upssched-cmd
PIPEFN /var/run/nut/upssched.pipe
LOCKFN /var/run/nut/upssched.lock
AT ONBATT * EXECUTE up...
2017 Oct 18
2
debian 8 "jessie" nut 2.7.2 slaves not shutting down
...pdxvhtst02 slave
upsmon.conf
MONITOR TOPAPC at localhost 1 upsmon pass master
MONITOR MIDAPC at localhost 1 upsmon pass master
MONITOR BOTAPC at localhost 1 upsmon pass master
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h now"
NOTIFYCMD /bin/notifynetadmins
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
NOTIFYMSG ONLINE "UPS %s on line power"
NOTIFYMSG ONBATT "UPS %s on battery"
NOTIFYMSG LOWBATT "UPS %s battery is low"
NOTIFYMSG FSD "UPS %s: forced shutdown in progress"
NOTIFYMSG COMMOK "Communication...
2011 Jul 19
2
KIN-1500AP RM + Windows 2008 64-bit Standard R2 SP1 (nut 2.6.1)
...psd.users:
*
*
[monuser]
password = xxxxxxxx
upsmon master
upsmon.conf:
*
*
MONITOR KIN1500 at 192.168.1.2 1 monuser xxxxxxxx master
MINSUPPLIES 1
SHUTDOWNCMD "C:\\WINDOWS\\system32\\shutdown.exe -s -t 0"
NOTIFYCMD /sbin/upssched
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG "C:\\killpower"
NOTIFYFLAG ONLINE SYSLOG+WALL+EXEC
NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC
NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC
RBWARNTIME 43200
NOCOMMWARNTIME 300
FINALDELAY 5
upssched.conf:
*
*
CMDSCRIPT /bin/upssched-cmd
AT ONBATT * START-TIMER onbattwarn 10...
2016 Oct 26
2
setting up CYBERPOWER CP1500PFCLCD
...016 10:46:17 Config Load: NOTIFYCMD set to
"c:\Program Files\WinNUT\alertPopup.exe"
Level INFO 10/26/2016 10:46:17 Config Load: POLLFREQ set to 5
Level INFO 10/26/2016 10:46:17 Config Load: POLLFREQALERT set to 5
Level INFO 10/26/2016 10:46:17 Config Load: HOSTSYNC set to 15
Level INFO 10/26/2016 10:46:17 Config Load: DEADTIME set to 15
Level INFO 10/26/2016 10:46:17 Config Load: RBWARNTIME set to
43200
Level INFO 10/26/2016 10:46:17 Config Load: NOCOMMWARNTIME set to
300
Level INFO 10/26/2016 10:46:17 Config Load: FINA...
2006 Sep 13
2
POWERDOWNFLAG (/etc/killpower) does not contain the upsmon magic string!!!
Hi to all, i install nut and it's work perfectly but when i start upsmon i recive the message:
POWERDOWNFLAG (/etc/killpower) does not contain the upsmon magic string
My upmon.conf contain:
MONITOR myups@theseo 1 orion91 carlos81 master
SHUTDOWNCMD "/sbin/shutdown -h +0"
HOSTSYNC 15
POWERDOWNFLAG /etc/killpower
FINALDELAY 5
My killpower scrit in /etc/killpower contain:
#!/bin/bash
if (test -f /etc/killpower)
then
echo "Killing the power, bye!"
/sbin/upsdrvctl shutdown
sleep 120
# uh oh... the UPS powerof...
2010 Nov 16
2
Shutdown script does not trigger
...sd.conf :
LISTEN 127.0.0.1 3493
/etc/nut/upsd.users :
[admin]
password = ****
actions = SET
instcmds = ALL
[upsmon]
password = ****
upsmon master
/etc/nut/upsmon.conf :
RUN_AS_USER nut
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG /etc/killpower
RBWARNTIME 43200
FINALDELAY 5
MONITOR dell at localhost 1 upsmon **** master
/etc/nut/upssched.conf :
CMDSCRIPT /etc/nut/sched/upssched.sh (this script exists but seems never
to be executed...)
PIPEFN /etc/nut/sched/upssched.pipe
LOCKFN /etc/nut/sched/u...
2012 Apr 11
1
NOTIFYCMD doesn't work from Windows service
...esn't run.
If I run upsmon.exe in cmd (i. e. not as a service) everything works fine.
Here is my upsmon.conf:
MONITOR central at 10.35.0.180 1 user password slave
MINSUPPLIES 1
SHUTDOWNCMD "C:\\NUT\\shutdown.bat"
NOTIFYCMD "C:\\NUT\\shutdown.bat"
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG "C:\\killpower"
NOTIFYMSG ONLINE ONLINE
NOTIFYMSG ONBATT ONBATT
NOTIFYMSG LOWBATT LOWBATT
NOTIFYMSG FSD FSD
NOTIFYFLAG ONLINE SYSLOG+WALL+EXEC
NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC
NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC...
2011 Jun 08
2
Misconfiguration of Windows MSI installer 2.6.0-1 with my Powerware 5115 connected via USB port
...STEN 192.168.1.12 3493
*upsd.users:*
[monuser]
password = xxxxxxxx
upsmon master
*upsmon.conf:*
MONITOR PW5115 at 192.168.1.12 1 monuser xxxxxxxx master
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
NOTIFYCMD /sbin/upssched
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG /etc/killpower
NOTIFYFLAG ONLINE SYSLOG+WALL+EXEC
NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC
NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC
RBWARNTIME 43200
NOCOMMWARNTIME 300
FINALDELAY 5
*upssched.conf:*
CMDSCRIPT /bin/upssched-cmd
AT ONBATT * START-TIMER onbattwarn 10
AT ONLINE * C...
2020 Jan 01
2
Belkin USB UPS Not Turning Off
...s ###########
[local_mon]
password = *********
upsmon master
########### /etc/nut/upsmon.conf ###########
MONITOR belkinusb at localhost 1 local_mon ********* master
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
NOTIFYCMD /home/android/nutShutdown.sh
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG /etc/killpower
NOTIFYMSG ONBATT "UPS %s on battery"
NOTIFYFLAG ONBATT WALL+EXEC
RBWARNTIME 43200
NOCOMMWARNTIME 300
FINALDELAY 5
########### /etc/nut/upssched.conf ###########
CMDSCRIPT /bin/upssched-cmd
########### <scriptname> #######...
2006 Feb 14
3
Master privileges unavailable on UPS
...llowfrom = localhost
actions = SET
instcmds = ALL
# Network UPS Tools: example upsmon configuration
RUN_AS_USER nutmon
MONITOR lupin1500AVR@localhost 1 monmaster * master
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
NOTIFYCMD /usr/local/ups/bin/notifyme
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG /etc/killpower
NOTIFYFLAG ONLINE SYSLOG+WALL+EXEC
NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC
NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC
NOTIFYFLAG FSD SYSLOG+WALL+EXEC
NOTIFYFLAG COMMOK SYSLOG+WALL+EXEC
NOTIFYFLAG COMMBAD SYSLOG+WALL+EXEC
NOTIFYFLAG SHUTDOWN SYSLOG+WALL+EXEC
NOTIFYFLA...
2018 Sep 04
2
WinNUT Client Logs
...to configure it for the first time and I cannot make it to work. Here are my settings:
Nut.conf
MODE=netclient
Upsmon.conf
MONITOR ups at pfsense 1 <username> <password> slave
MINSUPPLIES 1
SHUTDOWNCMD "C:\\WINDOWS\\system32\\shutdown.exe -s -t 0"
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG /usr/local/ups/etc/killpower
RBWARNTIME 43200
NOCOMMWARNTIME 300
FINALDELAY 5
Thank you.
Regards,
Kevin Mychal M. Ong
Sr Infrastructure Engineer, Microsoft Technology Services - Messaging
Global Infrastructure Operations
Ingram Micro Inc.
4F Three World Square, 22 U...
2013 Jun 19
1
Cannot connect to a Eaton Ellipse Pulsar ASR/6000VA usbs
...-------------------------------------------------------------------
# POLLFREQ <n>
POLLFREQ 5
# --------------------------------------------------------------------------
# POLLFREQALERT <n>
POLLFREQALERT 5
# --------------------------------------------------------------------------
# HOSTSYNC - How long upsmon will wait before giving up on another upsmon
HOSTSYNC 15
# --------------------------------------------------------------------------
DEADTIME 15
# --------------------------------------------------------------------------
# POWERDOWNFLAG - Flag file for forcing UPS shutdown on...
2020 Sep 17
3
Shutdown order for servers
Hello to All!
It might be not exactly NUT question but implementation.
I have a rack with one UPS and several servers getting power from this
device. One server is a master and other are slaves. All systems are
running Debian 4.15.3 kernel and APC UPS. Everything works fine but what I
need is to make an order for shutting down servers as they have different
roles.
Is it possible to configure SQL
2023 Oct 27
2
FSD sequence: Waiting for bigger and slower clients before cutting power
...oop, for the INT/TERM/QUIT signal
(it would still be necessary to configure the service manager such that upsmon
is terminated as late as possible). The primary could start shutting down its
services in the meantime, but upsmon would hold the poweroff until the
secondaries have disconnected (or HOSTSYNC expires).
Surely this would be better than cranking up FINALDELAY on the primary and
always waiting for a fixed period of time, as suggested in https://alioth-lists.debian.net/pipermail/nut-upsuser/2012-April/007550.html? I guess I could
try writing a SHUTDOWNCMD script that doesn't exit unt...
2010 Jan 09
2
problem with mailing (nut 2.4.1 and a powermust650 -> megatec_usb)
...ng
the megatec_usb driver. Everything works fine except for the mailing
when something happens. My upsmon looks like this:
MONITOR powermust650 at localhost 1 local controller master
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
NOTIFYCMD /root/upsmailer
POLLFREQ 10
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 45
POWERDOWNFLAG /etc/killpower
NOTIFYMSG ONLINE "UPS %s on line power"
NOTIFYMSG ONBATT "UPS %s on battery"
NOTIFYMSG LOWBATT "UPS %s battery is low"
NOTIFYMSG FSD "UPS %s: forced shutdown in progress"
NOTIFYMSG COMM...
2006 Aug 08
1
2.0.1 upsmon memory leak
...re: Connection refused
Using the configuration file of:
MONITOR sm700_0@192.168.1.21 1 monitoruser password slave
MONITOR rm3000_0@192.168.1.22 0 monitoruser password slave
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
# NOTIFYCMD /usr/local/ups/bin/notifyme
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG /etc/killpower
RBWARNTIME 43200
NOCOMMWARNTIME 300
FINALDELAY 5
Upsmon is:
companyfs1:/var/log# /sbin/upsmon -V
Network UPS Tools upsmon 2.0.1
Rehupping the process
companyfs1:/tmp# ps aux | grep [n]ut
nut 30369 0.0 0.1 1720 756 ? S 11:31 0:00 /s...
2020 Feb 18
2
UPS shuts down after restart
...oger, Hi all,
> Does upsmon.conf specify a shutdown on LB?
I think so. You mean SHUTDOWNCMD?
The relevant parts of my upsmon.conf (notifications removed):
MONITOR ups at localhost 1 upsmaster secret master
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
POLLFREQ 5
POLLFREQALERT 2
HOSTSYNC 15
DEADTIME 40
POWERDOWNFLAG /etc/killpower
RBWARNTIME 43200
NOCOMMWARNTIME 1800
FINALDELAY 1
> What happens if you let the battery power the system until LB is reached?
It's the same :-(
> How old is this battery?
About half a year. But I already went into this issue some months befo...
2015 Jul 14
1
New questions
...all is required in this file. ?Lookingat just the first part of the example from Price, I see :
[CODE]# /etc/ups/upsmon.conf?MONITOR Eaton-66781 at localhost 1 upsmaster sekret master?MINSUPPLIES 1?SHUTDOWNCMD "/sbin/shutdown -h +0"?NOTIFYCMD /usr/sbin/upssched?POLLFREQ 5?POLLFREQALERT 5?HOSTSYNC 15?DEADTIME 15?POWERDOWNFLAG /etc/killpower[CODE]
I have modified the MONITOR line as appropriate for my system but wonder about a coupleof entries. ?The referenced binary '/usr/sbin/upssched' appears to be in '/sbin' not '/usr/sbin' .Is that the '/sbin/upssched' the...