Apologies for resurrecting an old thread and likely poor formatting - I
wasn't subscribed to the list at the time and have copied it out of the
archives
(http://lists.alioth.debian.org/pipermail/nut-upsuser/2010-July/006104.html).
I've been unable to locate any further progress on this UPS (Liebert
10af:0001) - a thread from 2009
(http://lists.alioth.debian.org/pipermail/nut-upsdev/2009-November/004252.html)
seemed to work for a Liebert PSA 650 model from then, but this 2010 thread seems
to have unearthed an incompatible model - I've just purchased two Liebert
PSA 1500 which exhibit exactly the same issues as below. I've put some
output inline.
I've checked out trunk and there seems to be no progress there. I'm
happy to help debugging the driver, is there still some way we can progress
this?
All I get from upsc is:
battery.charge.low: 38
battery.charge.warning: 38
battery.type: PbAc
device.mfr: Emerson Network Power
device.model: LiebertPSA
device.serial:
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.version: 2.6.2-3254
driver.version.data: Belkin HID 0.12
driver.version.internal: 0.35
ups.mfr: Emerson Network Power
ups.model: LiebertPSA
ups.productid: 0001
ups.serial:
ups.status: OB
ups.vendorid: 10af
Many thanks, Tim.
> Tue Jul 13 19:54:03 UTC 2010
> Citeren Michelle Wright <michelle.wright op gmail.com>:
>
> > $ sudo /lib/nut/usbhid-ups -DDD -a maxfun
> > Network UPS Tools - Generic HID driver 0.34 (2.4.3)
> > USB communication driver 0.31
>
> [...]
>
> > 0.341940 Report[get]: (3 bytes) => 1d 8b 00
> > 0.341960 Path: UPS.PowerSummary.Voltage, Type: Feature,
ReportID:
> > 0x1d, Offset: 0, Size: 16, Value: 0.000001
>
> The UPS is reporting a battery voltage of 1 uV here, most likely
> because Liebert got the exponent of this value wrong. I assume they
> meant something like 13.9 V, since 00 8B (hex) equals 139 (decimal).
> We can fix this though, but this will require a dedicated sub driver.
I get:
0.413899 Report[get]: (3 bytes) => 1d 08 01
0.413920 Path: UPS.PowerSummary.Voltage, Type: Feature, ReportID: 0x1d, Offset:
0, Size: 16, Value: 0.000003
>
> > 0.345939 Report[get]: (3 bytes) => 1f 0c 00
> > 0.345956 Path: UPS.PowerSummary.ConfigVoltage, Type: Feature,
> > ReportID: 0x1f, Offset: 0, Size: 16, Value: 0.000000
>
> Same here. The nominal battery voltage is probably 12 V, but what is
> reported is 0.12 uV, since 00 0C (hex) equals 12 (decimal). Can be
> fixed too.
0.417897 Report[get]: (3 bytes) => 1f 18 00
0.417916 Path: UPS.PowerSummary.ConfigVoltage, Type: Feature, ReportID: 0x1f,
Offset: 0, Size: 16, Value: 0.000000
>
> > 0.350081 Report[buf]: (2 bytes) => 07 0d
> > 0.350095 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type:
> > Feature, ReportID: 0x07, Offset: 2, Size: 1, Value: 0.000000
> > 0.350106 Report[buf]: (2 bytes) => 07 0d
> > 0.350120 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type:
> > Input, ReportID: 0x07, Offset: 2, Size: 1, Value: 0.000000
>
> Although I didn't expect otherwise, the UPS is reporting that AC is
> not present (that's why you see NUT reporting OB instead of OL). Try
> if these value change to '1.000000' if you unplug the mains.
I tried this - unfortunately no they do not. I get this with power disconnected:
0.422018 Report[buf]: (2 bytes) => 07 0d
0.422034 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature,
ReportID: 0x07, Offset: 2, Size: 1, Value: 0.000000
0.422046 Report[buf]: (2 bytes) => 07 0d
0.422061 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Input,
ReportID: 0x07, Offset: 2, Size: 1, Value: 0.000000
With the upsd and upsmon running, I get a console message that I'm on
battery which stays that way regardless of whether the AC is connected or
not.> In that
> case Liebert seems to report the status reversed from what is
> specified in the HID PDC specifications (which doesn't surprise me at
> all, given the broken battery voltage reporting).
>
> > 0.350131 Report[buf]: (2 bytes) => 07 0d
> > 0.350145 Path: UPS.PowerSummary.PresentStatus.BatteryPresent,
Type:
> > Feature, ReportID: 0x07, Offset: 3, Size: 1, Value: 0.000000
> > 0.350156 Report[buf]: (2 bytes) => 07 0d
> > 0.350170 Path: UPS.PowerSummary.PresentStatus.BatteryPresent,
Type:
> > Input, ReportID: 0x07, Offset: 3, Size: 1, Value: 0.000000
>
> I assume the UPS contains a battery and that this value is reversed as
well.
0.422073 Report[buf]: (2 bytes) => 07 0d
0.422088 Path: UPS.PowerSummary.PresentStatus.BatteryPresent, Type: Feature,
ReportID: 0x07, Offset: 3, Size: 1, Value: 0.000000
0.422101 Report[buf]: (2 bytes) => 07 0d
0.422116 Path: UPS.PowerSummary.PresentStatus.BatteryPresent, Type: Input,
ReportID: 0x07, Offset: 3, Size: 1, Value: 0.000000
My UPS contains a battery, yes :)>
> > 0.353937 Report[get]: (3 bytes) => 2b 63 09
> > 0.353954 Path: UPS.Output.Voltage, Type: Feature, ReportID:
0x2b,
> > Offset: 0, Size: 16, Value: 0.000024
>
> Most likely the same problem as for the battery voltage. It looks more
> like the output voltage should be 240.3 V, instead of 24.03 uV.
0.425897 Report[get]: (3 bytes) => 2b 60 09
0.425916 Path: UPS.Output.Voltage, Type: Feature, ReportID: 0x2b, Offset: 0,
Size: 16, Value: 0.000024
>
> > 0.361937 Report[get]: (3 bytes) => 20 68 09
> > 0.361954 Path: UPS.Input.Voltage, Type: Feature, ReportID: 0x20,
> > Offset: 0, Size: 16, Value: 0.000024
>
> Same here. Input voltage is probably 240.8 V instead of 24.08 uV.
0.433903 Report[get]: (3 bytes) => 20 68 09
0.433925 Path: UPS.Input.Voltage, Type: Feature, ReportID: 0x20, Offset: 0,
Size: 16, Value: 0.000024
>
> > 0.365937 Report[get]: (3 bytes) => 38 f5 01
> > 0.365955 Path: UPS.Input.Frequency, Type: Feature, ReportID:
0x38,
> > Offset: 0, Size: 16, Value: 501.000000
>
> Something similar here too. The input frequency is probably 50.1 Hz,
> instead of 501 Hz.
0.437896 Report[get]: (3 bytes) => 38 f3 01
0.437916 Path: UPS.Input.Frequency, Type: Feature, ReportID: 0x38, Offset: 0,
Size: 16, Value: 499.000000
>
> > 0.630102 upsdrv_updateinfo...
> > 0.881839 libusb_get_interrupt: Connection timed out
> > 0.881854 Got 0 HID objects...
> > 0.881863 Quick update...
>
> NUT attempts to read from the interrupt pipeline here, but at this
> time there are no messages queued. This is normal, nothing to worry
> about.
>
> The good news is that we can probably support this UPS (sort of),
> provided you're willing to help us finding and fixing all it's
quirks.
> It will require checking out the development version from SVN and
> frequent compiling from sources. You'd also need to be able to take
> the UPS out of service from time to time for testing a new version of
> the driver. Let us know if you are interested in helping getting this
> device supported.
No problem, happy to do this.
>
> Best regards, Arjen
> --
> Please keep list traffic on the list