2013 Jun 10
2
several problems with Powercom BNT-500AP
...tStatus.NeedReplacement, Type: Input, ReportID: 0x0a, Offset: 6, Size: 1, Value: 1
It happened for 9 times, but the message appeared only on first.
Broadcast Message from nut at rasp
(somewhere) at 17:33 ...
UPS BNT500AP at localhost on battery
occurred when UPS.PowerSummary.PresentStatus.ACPresent turned to 0 on this line:
10921.069403 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Input, ReportID: 0x0a, Offset: 2, Size: 1, Value: 0
Broadcast Message from nut at rasp
(somewhere) at 17:33 ...
UPS BNT500AP at localhost on line power
There were 3 more "on battery" ev...
2013 Jun 11
0
several problems with Powercom BNT-500AP
...ect, upsmon throttles the REPLBATT event:
http://www.networkupstools.org/docs/man/upsmon.conf.html (search for RBWARNTIME)
> Broadcast Message from nut at rasp
> (somewhere) at 17:33 ...
>
> UPS BNT500AP at localhost on battery
> occurred when UPS.PowerSummary.PresentStatus.ACPresent turned to 0 on this line:
> 10921.069403 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Input, ReportID: 0x0a, Offset: 2, Size: 1, Value: 0
If you turn up the debugging level from 2 to 3, the driver will do a hex dump of the report buffer. Offset and size are bits, so if the ACPresent bi...
2023 Nov 12
1
What is the arduino sub-driver intended to be used for?
...built. With the changes from that thread (I had a PR
merged), I was able to get usbhid-ups to recognize my device and could
setup NUT the rest of the way. My intended configuration is to run NUT on a
Raspberry Pi, have that device be master and then have clients of that NUT
install take action when ACPresent goes from true to false.
The problem I ran into is `upsc diyups at locahost` was always showing
ups.status as "OB". I ran tests and confirmed the raw reports
included "UPS.PowerSummary.PresentStatus.ACPresent correctly showing 1 and
0 as appropriate as well as correctly reporting t...
2023 Nov 12
1
What is the arduino sub-driver intended to be used for?
...ges from that thread (I had a
> PR merged), I was able to get usbhid-ups to recognize my device and could
> setup NUT the rest of the way. My intended configuration is to run NUT on a
> Raspberry Pi, have that device be master and then have clients of that NUT
> install take action when ACPresent goes from true to false.
>
> The problem I ran into is `upsc diyups at locahost` was always showing
> ups.status as "OB". I ran tests and confirmed the raw reports
> included "UPS.PowerSummary.PresentStatus.ACPresent correctly showing 1 and
> 0 as appropriate as well...
2013 Nov 27
0
several problems with Powercom BNT-500AP
...started this topic. I've finally tested it on Linux desktop PC.
Nut version 2.6.4-2.3
Basically the behavior is the same as on raspberry pi. It reports "battery needs to be replaced" regularly and I got "on battery" message
114107.780504 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Input, ReportID: 0x0a, Offset: 2, Size: 1, Value: 0
(on line nr. 1044540 in log)
after ~ 31 hours of testing along with immediate "low battery (critical)"
not sure, but probably because of
114107.780620 Path: UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Input...
2023 Nov 13
1
What is the arduino sub-driver intended to be used for?
...read (I had a
>> PR merged), I was able to get usbhid-ups to recognize my device and could
>> setup NUT the rest of the way. My intended configuration is to run NUT on a
>> Raspberry Pi, have that device be master and then have clients of that NUT
>> install take action when ACPresent goes from true to false.
>>
>> The problem I ran into is `upsc diyups at locahost` was always showing
>> ups.status as "OB". I ran tests and confirmed the raw reports
>> included "UPS.PowerSummary.PresentStatus.ACPresent correctly showing 1 and
>> 0 as...
2013 Jun 08
0
several problems with Powercom BNT-500AP
On Jun 8, 2013, at 12:57 PM, M?rti?? Pu??tis wrote:
> I'll take a longer driver log. This page (http://www.networkupstools.org/support.html) says that to take a driver log NUT should be stopped, so I won't be able to tell when these events occurred within a driver log.
Hmm, I didn't realize it said that, but I think that's to prevent having two copies of the same driver
2017 Oct 17
0
Junda-tech
...t; "UPS.PowerSummary.DesignCapacity", NULL, "%.0f", 0, NULL },
> { "unmapped.ups.powersummary.fullchargecapacity", 0, 0,
> "UPS.PowerSummary.FullChargeCapacity", NULL, "%.0f", 0, NULL },
> { "unmapped.ups.powersummary.presentstatus.acpresent", 0, 0,
> "UPS.PowerSummary.PresentStatus.ACPresent", NULL, "%.0f", 0, NULL },
> { "unmapped.ups.powersummary.presentstatus.charging", 0, 0,
> "UPS.PowerSummary.PresentStatus.Charging", NULL, "%.0f", 0, NULL },
> { "unmappe...
2013 Jun 08
2
several problems with Powercom BNT-500AP
Thanks for the support.
Here's list of when transition to battery with return to utility power within a few seconds occurred in last few days:
Wednesday
1:41
11:48
11:54
12:59
13:42
14:42
18:13
18:14
Thursday
5:23
Friday
5:12
7:39
7:43
Saturday
7:34
Here's list of when messages that battery needs replacement occurred:
Wednesday
20:34
Thursday
9:07
23:09
Friday
18:25
Saturday
7:32
19:47
2011 Sep 24
4
LiebertPSP
...xed too.
0.417897 Report[get]: (3 bytes) => 1f 18 00
0.417916 Path: UPS.PowerSummary.ConfigVoltage, Type: Feature, ReportID: 0x1f, Offset: 0, Size: 16, Value: 0.000000
>
> > 0.350081 Report[buf]: (2 bytes) => 07 0d
> > 0.350095 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type:
> > Feature, ReportID: 0x07, Offset: 2, Size: 1, Value: 0.000000
> > 0.350106 Report[buf]: (2 bytes) => 07 0d
> > 0.350120 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type:
> > Input, ReportID: 0x07, Offset: 2, Size: 1, Value: 0.000000
>
> Al...
2019 Dec 08
3
Tripp Lite SMART1500LCD repeatedly disconnecting and reconnecting
...612 Path: UPS.PowerSummary.PresentStatus.Voltage, Type:
Feature, ReportID: 0x31, Offset: 0, Size: 16, Value: 1138
0.142600 Path: UPS.PowerSummary.PresentStatus.ShutdownImminent,
Type: Input, ReportID: 0x32, Offset: 0, Size: 1, Value: 0
0.142760 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type:
Input, ReportID: 0x32, Offset: 1, Size: 1, Value: 1
0.142906 Path: UPS.PowerSummary.PresentStatus.Charging, Type: Input,
ReportID: 0x32, Offset: 2, Size: 1, Value: 1
0.143052 Path: UPS.PowerSummary.PresentStatus.Discharging, Type:
Input, ReportID: 0x32, Offset: 3, Size: 1, Valu...
2015 Jan 09
0
persistent "low battery" condition
On Jan 8, 2015, at 11:43 PM, Graham Menhennitt <graham at menhennitt.com.au> wrote:
> Hello Nutters,
>
> I'm running nut 2.7.2 on FreeBSD 10-stable (via the FreeBSD port) with an APC Back-UPS CS 350 connected via USB. I get persistent (every few minutes) messages logged "battery is low" but I don't understand why. I don't think it's for the reason
2015 Jan 12
2
persistent "low battery" condition
...: 0, Size: 8, Value: 2
771.853725 Path: UPS.ManufacturerDate, Type: Feature, ReportID:
0x35, Offset: 0, Size: 16, Value: 12935
771.864707 Path: UPS.Output.ConfigActivePower, Type: Feature,
ReportID: 0x52, Offset: 0, Size: 16, Value: 210
771.873644 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type:
Feature, ReportID: 0x07, Offset: 2, Size: 1, Value: 1
771.873720 Path: UPS.PowerSummary.PresentStatus.Discharging, Type:
Feature, ReportID: 0x07, Offset: 1, Size: 1, Value: 0
771.873751 Path: UPS.PowerSummary.PresentStatus.Charging, Type:
Feature, ReportID: 0x07, Offset: 0, Size: 1...
2015 Jan 09
2
persistent "low battery" condition
...63.201247 Path: UPS.PowerSummary.DelayBeforeReboot, Type:
Feature, ReportID: 0x13, Offset: 0, Size: 24, Value: 0
163.210345 Path: UPS.Output.DelayBeforeStartup, Type: Feature,
ReportID: 0x28, Offset: 0, Size: 16, Value: 0
163.221472 Path: UPS.PowerSummary.PresentStatus.ACPresent,
Type: Feature, ReportID: 0x07, Offset: 2, Size: 1, Value: 1
163.221585 Path: UPS.PowerSummary.PresentStatus.Discharging,
Type: Feature, ReportID: 0x07, Offset: 1, Size: 1, Value: 0
163.221614 Path: UPS.PowerSummary.PresentStatus.Charging, Type:
Feature, ReportID: 0x07...
2016 May 04
2
New UPS Support: Eaton 5S 1000
...Offset: 40, Size: 8, Value: 6
5.727946 Path: UPS.PowerSummary.PercentLoad, Type: Feature, ReportID:
0x07, Offset: 0, Size: 8, Value: 0
5.727964 Path: UPS.PowerSummary.PowerSummaryID, Type: Feature, ReportID:
0x0b, Offset: 104, Size: 8, Value: 1
5.777970 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature,
ReportID: 0x01, Offset: 0, Size: 1, Value: 1
5.777987 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Input,
ReportID: 0x01, Offset: 0, Size: 1, Value: 1
5.777997 Path:
UPS.PowerSummary.PresentStatus.BelowRemainingCapacityLimit, Type: Feature,
ReportID: 0x01, Offset: 1,...
2023 Nov 15
2
What is the arduino sub-driver intended to be used for?
...t;>> PR merged), I was able to get usbhid-ups to recognize my device and could
>>> setup NUT the rest of the way. My intended configuration is to run NUT on a
>>> Raspberry Pi, have that device be master and then have clients of that NUT
>>> install take action when ACPresent goes from true to false.
>>>
>>> The problem I ran into is `upsc diyups at locahost` was always showing
>>> ups.status as "OB". I ran tests and confirmed the raw reports
>>> included "UPS.PowerSummary.PresentStatus.ACPresent correctly showing 1 an...
2017 Oct 11
4
Junda-tech
Hi,
I have an UPS with only the marking D1000 on it and it came with
Junda-Tech's UpsMate.
Its USB id is 3344:0025, which is apparently a microprocessor.
I've could get some of the HID interactions as described on the website,
but there are some outstanding.
Junda-Tech does not respond to any queries.
Does anybody else have the same or a similar UPS with more information?
What is the
2020 Oct 23
2
Nut-upsuser Digest, Vol 184, Issue 8
..., Offset: 24, Size: 16, Value: 300
0.037734 Path: UPS.PowerSummary.ConfigVoltage, Type: Feature, ReportID:
0x09, Offset: 0, Size: 8, Value: 24
0.038485 Path: UPS.PowerSummary.Voltage, Type: Feature, ReportID: 0x0a,
Offset: 0, Size: 8, Value: 24
0.039229 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Input,
ReportID: 0x0b, Offset: 0, Size: 1, Value: 1
0.039344 Path: UPS.PowerSummary.PresentStatus.Charging, Type: Input,
ReportID: 0x0b, Offset: 1, Size: 1, Value: 0
0.039448 Path: UPS.PowerSummary.PresentStatus.Discharging, Type: Input,
ReportID: 0x0b, Offset: 2, Size: 1, Value: 0...
2016 May 03
2
New UPS Support: Eaton 5S 1000
Oops... changing that to --with-user=nut solved one problem. I have the
driver, upsd and upsmon running now. Thank you!
Now I'm back to another issue, every 2 seconds I get in the logs:
May 3 13:45:23 myhost upsd[2587]: Connected to UPS [eaton]:
usbhid-ups-eaton
It seems happy to do this forever.
On Tue, May 3, 2016 at 8:17 AM, Charles Lepple <clepple at gmail.com> wrote:
> On
2016 Dec 03
2
Problem installing NUT on 16.04
...Size: 16, Value: 300
0.132561 Path: UPS.PowerSummary.ConfigVoltage, Type: Feature,
ReportID: 0x09, Offset: 0, Size: 8, Value: 24
0.132643 Path: UPS.PowerSummary.Voltage, Type: Feature, ReportID:
0x0a, Offset: 0, Size: 8, Value: 24
0.132765 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type:
Input, ReportID: 0x0b, Offset: 0, Size: 1, Value: 1
0.132770 Path: UPS.PowerSummary.PresentStatus.Charging, Type:
Input, ReportID: 0x0b, Offset: 1, Size: 1, Value: 0
0.132774 Path: UPS.PowerSummary.PresentStatus.Discharging, Type:
Input, ReportID: 0x0b, Offset: 2, Size: 1, V...