Hi Alex,
I've forwarded your request to the nut-upsuser mailing list.
Please follow the discussion there.
I'm also not sure to have well understood your issue.
Don't hesitate to explain it a bit more if I'm wrong...
Alex wrote:> ASP Linux Server II.
>UPS POWERCOM SMART KING 800A.
>
>
>Has Putted (deliver) NUT. The Driver (according to ?????) fentonups. Like
works orderly.>But can not understand as correct to adjust.
>
>Is Necessary include/disconnect the server on timetable and at disappearing
of voltage of feeding. As I has >understood to is necessary by force
extinguish UPS in determined time through cron.
yes it's necessary to poweroff the UPS in case of shutdown for power
failure.
But, during the system shutdown, you finally power it off through an init
script.
Generally, there is a nut script that call to "upsdrvctl shutdown"...
>Can Not find, where assign time through which UPS must be enclosed.
>The Command upsmon -c fsd switches off the computer, translates UPS in mode
"cut-in in time" and includes its >in 5 minutes. But where me to
change this
importance.>
>Earlier given UPS work at server with NOWEL. In driver possible there was
adjust cut-in/unhooking on time and >weekdays.
fentonups doesn't support such an option. It only has support for low
battery level, based
upon voltage (Set low battery level, in volts : -x lowbattvolt=<value>).
If some models supported by this driver can support such a feature, you are
welcomed
to improve the driver to handle this.
Arnaud Quette
--
Linux / Unix Expert - MGE UPS SYSTEMS - R&D Dpt
Network UPS Tools (NUT) Project Leader - http://www.networkupstools.org/
Debian Developer - http://people.debian.org/~aquette/
OpenSource Developer - http://arnaud.quette.free.fr/