2006 Apr 03
1
Re: F6H500ukUNV working with fentonups driver
Hi Patrick,
2006/4/2, Patrick Beard <p.beard@blueyonder.co.uk>:
> Hi Arnaud,
>
> Just wanted to let you know the the Belkin F6H500ukUNV is working for me
> with the fentonups driver.
>
> http://catalog.belkin.com/IWCatSectionView.process?IWAction=Load&Merchant_Id=&Section_Id=202840
>
> I originally tried it with the genericups driver with upstype=7 but this
> gave me 'On battery' 'Low Battery' all the time. I went through all the...
2006 Jan 27
0
[PATCH] fentonups patch to make it work with some powercom ups's
Hi list
here is the patch to make fentonups recognize some PowerCOM's UPS's, and
to setup terminal lines for them (at least for SMK-1500a) as powercom's
original upsmon do. fentonups -x powercom works correctly with SMK-1500a
(it screamed ''Communications with UPS lost - check cabling' or 'Short
read during U...
2008 May 18
1
REGRESSION: New "megatec" driver does't work for UPS that was managed by old fentonups driver
Hi there,
A couple years ago, I had patched the "fentonups" nut driver to allow it to
work with my Unitek Alpha 500 UPS.
My patch had been accepted and incorporated in the standard fentonups driver.
I have had no time to stay involved in the "nut" project since (and besides
this I'm not a developper...).
2 days ago I upgraded from...
2006 Apr 26
1
RE nut 2.0 fentonups and Xanto S3000R
...stools.org/
Debian Developer - http://people.debian.org/~aquette/
OpenSource Developer - http://arnaud.quette.free.fr/
Henning Brauer <henning@openbsd.org>
04/26/06 12:19 AM
A
arnaud.quette@mgeups.com
cc
bernd@cvs.openbsd.org, Henning Brauer <henning@cvs.openbsd.org>
Objet
nut 2.0 fentonups
this allows the model to be forced for the fentonups driver. I have a
UPS that does not respond to I, but otherwise perfectly follows the
fenton protocol. this makes it work.
the Xanto S3000R is a rackmount 2U UPS, online, 3000VA, which requires
and external 2U battery pack. The manufactur...
2005 Oct 05
1
serial/USB-over-HID layer for fentonups
Do you know some piece of code I could look at to see learn more about
this ?
2005 Oct 05
1
serial/USB-over-HID layer for fentonups
Do you know some piece of code I could look at to see learn more about
this ?
2006 Jun 06
2
RE Fentonups driver - FreeBSD 6.x
...p;D Dpt
Network UPS Tools (NUT) Project Leader - http://www.networkupstools.org/
Debian Developer - http://people.debian.org/~aquette/
OpenSource Developer - http://arnaud.quette.free.fr/
Stefanos Sofroniou <ssofroni@cytanet.com.cy>
06/05/06 10:00 PM
A
arnaud.quette@mgeups.com
cc
Objet
Fentonups driver - FreeBSD 6.x
Dear Sir,
My name is Stefanos Sofroniou and I have sent you another email long time
ago
regards to my UPS. My UPS is UPSilon2000 and for some reason fentonups
driver
does not support it. I have tried various drivers with negative results.
This is what i get from it...
2006 Sep 24
2
Kebo UPS-600A and Kebo UPS-1200M setup
Hello nut-upsuser,
Hope, that its might be useful for someone:
1. Kebo UPS-600A
Driver: genericups
UPStype: 7
Config extras: SD = -RTS or SD = -TX (don't know why but both are
suitable)
2. Kebo UPS-1200M
Driver: fentonups
Config extras: none
Note: Looks like twin brother of Microlab UPS-1200M :)
Driver ask me to report ID string:
"Unknown ups - please report this ID string: #KEBO UPS-1200M VER3.1C"
Sorry, but i don't know where I should send this one
--
Best regards,...
2006 Aug 04
1
RE nut drivers
Hi Alexander,
> I've UPS named PowerMan RealSmart 1000, it is not listed in
> compatibility list. I found that it works with "fentonups" driver and
> have ups.model "Unknown S163-1000". Ithink "1000" is from capacity -
> I've seen in Internet someone have RealSmart 800 identified "S163-800".
> Also PowerMan have "BackPro" series - people write it works with
> generic...
2006 Apr 03
1
Re: F6H500ukUNV working with fentonups driver
>> I tested it by pulling the supply to the ups. It got the 'on and then
>> the 'low battery' upsmon then shutdown my system. The ups however
>> remained on.
>the ups shutoff (hardware ups shutdown) seems not to be working.
>Carlos might have more ideas on the cause...
This might not be a bug - it could be that I reconnected the supply to soon.
I say this
2005 Sep 19
1
Sustainer S-1000C (Powercom protocol)
...er") with the same problems, using
powercom's upsmon works fine, while nut completely refuses to cooperate.
after trying almost everything i somehow hopeless surfed on the official
nut-page, when i saw that there are powercom-products which don't need
the powercom-driver, but the *fentonups one. now with the fentonups
driver everything works just fine. i'm shure it would be a good idea for
you to give the fentonups-driver a try.
greets
christian k?ndig
2006 Mar 09
0
fentonups: add Lestar MD-800E
...ls (NUT) Project Leader - http://www.networkupstools.org/
Debian Developer - http://people.debian.org/~aquette/
OpenSource Developer - http://arnaud.quette.free.fr/
Marek Majchrzak <nobbie __ link-net.pl> wrote:
> Hey!
>
> I wanted You to add Lestar UPS to te list of working ones on fentonups driver:
>
> Lestar MD-800E: works OK.
> ---------------
>
> Network UPS Tools - Fenton UPS driver 1.21 (2.0.0)
> Unknown ups - please report this ID string: #------------- ------ VT02052N
> Detected Unknown ----- on /dev/tty00
>
>
> Thanx for good software :-)
&...
2005 Oct 05
1
NUT does not recognize Effekta MT 1500
...ession of the List,
but I have a pressing question to ask, so please forgive me if
I miss the right tone...
I just installed NUT 2.0.2 and try to get it working with our
Effekta MT 1500. In the Drievers List I found this entry:
"Effekta" "MI/MT/MH" "2502 cable" "fentonups"
I went ahead and created this entry in ups.conf:
[UPS_A]
driver = fentonups
port = /dev/ttyS0
desc = "Haupt-USV"
And tried to start the driver:
> /usr/local/ups/bin/upsdrvctl start
Network UPS Tools - UPS driver controller 2.0.2
Network UPS Tools - Fenton UPS dr...
2006 Jul 24
2
fentonups driver patch for Effekta MHD3000 UPS
..., so the
behavior will be the same as before the patch, although probably it is
wrong. Someone knowing which model are on-line later can set the flags
correctly.
Please also send the reply to my email, because I'm not on the list.
regards,
Gabor
-------------- next part --------------
*** fentonups.c 2005-05-26 14:22:27.000000000 +0200
--- /usr/src/redhat/BUILD/nut-2.0.3/drivers/fentonups.c 2006-07-24 16:20:19.000000000 +0200
***************
*** 30,38 ****
--- 30,52 ----
#define DRV_VERSION "1.22"
static int cap_upstemp = 0;
+ static int is_online = 0;
static float lowvolt...
2006 Apr 05
0
Re: F6H500ukUNV working with fentonups driver
After trying the 'powermust' driver I can confirm it works well with the
F6H500ukUNV ups from Belkin.
I reported my tests but by accident posted them directly to Carlos and not
the mailing list (sorry Carlos).
Anyway brief summary of the powermust driver with the F6H500ukUNV;
Detects Online state.
Reports the Battery charge correctly.
Detects On Battery State.
Detects Low Battery State.
2006 Jul 15
2
Shutdown Problem
...ps from the wall, after a while, the
computer shutdowns very rudely. That it is just turns off. No scrolling down
of processes shutting down It does not seem shutdown cleanly. Any ideas as to
why this may be so?
Config files follow below.
Thanks
Eli
/etc/sysconfig contains
SERVER=yes
MODEL=fentonups
DEVICE=/dev/ttyS0
OPTIONS=""
UPSD_OPTIONS=
/etc/up/ups.conf contains
[Gamatronic_SmartCompact]
driver = fentonups
port = /dev/ttyS0
desc = "Gamatronic SmartCompact
/etc/ups/upsd.users contains
[username]
password = password
allowfrom = localhost
upsmon...
2007 Jan 20
1
Fenton UPS driver -- unknown UPS report
...s a "Power Tech" unit, model number SMK-800, and is
actually a Nikko/PowerTec Smart King LCD 800A.
The UPS works fine using the Fenton serial cable layout, and reports
almost perfect information:
root@anu:~# upsc smk800@localhost
battery.charge: 100.0
battery.voltage: 2.40
driver.name: fentonups
driver.parameter.port: /dev/ttyS0
driver.version: 2.0.4
driver.version.internal: 1.22
input.frequency: 50.0
input.voltage: 246.0
output.voltage: 247.0
ups.load: 038
ups.mfr: M+H
ups.model: Unknown MK-800
ups.status: OL
Everything there is right except 'battery.voltage' -- the unit has a...
2007 Feb 19
2
my ups shuts down when starting upsd
Hi,
I have a Fenton Powerpal L660, when I try and configure nut with either the
metatec or fentonups driver, and start upsd, the UPS instantly turns itself
off.
It used to work, until I changed my motherboard and CPU, which means it has
a different bios and serial port setup.
This is happening with Nut 2.0.1 and also Nut 2.0.5. I have an AMD64 bit
processor, Mandriva 2007 64 bit.
Any suggest...
2006 Dec 25
3
Unitek iZi UPS 525
...ype=21". Trouble is, "genericups" looks more like an enclosure type of
driver rather than a smart one. It starts OK but OL and LB are always ON, no
wonder since the cable has only three wires. :-|
Any hints?
PS. As per "UPS features and support" I've also tried "fentonups", just to
be on the safe side although to me "fenton" looks more like a simple ON/OFF
signaling rather than a complex serial protocol.
PPS. Yes, the UPS has "Linux" written on the box and they do provide some
kind of daemon, it's just that it requires JRE and X! =:-o
2006 Dec 04
4
megatec and some changes to cmdvartab and new-names.txt
I had some free time this weekend, and made some long overdue changes
to "megatec". The thing is, these changes lead to a couple of
questions that I must ask before I go on and "svn commit" them:
1) The blazer, fentonups, esupssmart, ippon, sms and mustek drivers
are now completely covered and all of their functionality should now
be present in megatec, and also every model supported by them should
now be supported by megatec (with additional funcionality). So, I have
changed "driver.list" so that all ha...