Set with upsrw: ups.delay.shutdown=60 is the same as offdelay = 30.
This time was done correctly by UPS.
Set with upsrw: ups.delay.start=90 is the same as ondelay = 40.
The UPS shut down and reset and forget about the settings.
If I use the program in Win 10 settings in the program from Eaton are stable!?
Jan.> -----Original Message-----
> From: Nut-upsuser <nut-upsuser-bounces+icingaj=gmail.com at alioth-
> lists.debian.net> On Behalf Of Roger Price
> Sent: Tuesday, July 3, 2018 4:05 PM
> To: nut-upsuser Mailing List <nut-upsuser at lists.alioth.debian.org>
> Subject: Re: [Nut-upsuser] No run cmd /usbhid-ups -k !
>
> On Tue, 3 Jul 2018, rakoi at mail.telekom.sk wrote:
>
> > UPS is Eaton 5SC 500i.
> > Please do not know how to write some parameters permanently to UPS?
>
> Read man ups.conf and man usbhid-ups and try setting the required values
> in ups.conf. For example
>
> [Eaton]
> driver = usbhid-ups
> port = auto
> desc = "Eaton 5sc 500i"
> offdelay = 30
> ondelay = 40
> lowbatt = 37
>
> Roger
>