2010 Nov 11
1
Setting offdelay and ondelay in Smart-UPS 1500 RM units
...the unit in question (a 1500 VA rack mountable one): Model: Smart-UPS 1500 RM Firmware revision: 617.3.I USB firmware revision: 1.5 Manufacturing date: 2003/06/03 The unit can be monitored with NUT, no problem at this. But when turning it off an back on, the "offdelay" and "ondelay" parameters from "ups.conf" aren't honored. This unit uses a different HID path than the stardard one for sending a "load.on.delay" command. As the driver (usbhid-ups) can't find this command, it has to revert to rebooting the UPS. The HID paths involved are: - &q...
2018 Oct 04
2
after power outage and proper shutdown, UPS turns on before power returns
...> roughly 40 seconds after the UPS shut down, it turns back on and it > > starts supplying power to the load, thus turning back on the devices > > attached to it. This is obviously not something I want. In trying to > > figure out the problem, the closest I've come was the ondelay > > parameter, but that only comes in play after the power returns, so it > > shouldn't apply here. > > Hi Gabriel, > > sorry for the delay - I am still working through a bit of a backlog here. > > We have a few other open CyberPower issues listed here: https://git...
2013 Dec 06
2
Delayed UPS start up after shutdown?
...change the parameter > ups.delay.start into your UPS to set the "Interval to wait before > (re)starting the load (seconds)" > > use upsset to change the value. So far, the ups.delay.start parameter in my MGE Protection Center 675 has always been equal to the driver.parameter.ondelay parameter (which equals the ondelay argument in ups.conf). Furthermore, whenever I have changed the ondelay argument in ups.conf (and restarted NUT) the above parameters have always been set equal to ondelay. Therefore, I would assume that ups.delay.start cannot help. Do you have any reason to...
2019 Apr 10
2
ondelay parameter does not work with NUT on Raspbian and Eaton 5E850iUSBDIN UPS
Thanks for help! Are you happy with your Eaton Elipse ECO 1600? Does it work well with ondelay? I will need some UPS that supports the ondelay parameter. Bartosz śr., 10 kwi 2019 o 13:06 Roger Price <roger at rogerprice.org> napisał(a): > On Wed, 10 Apr 2019, Bartosz wrote: > > > I don't see ups.delay.start anywhere. Here is the output of upsrw: > > > > up...
2006 Jul 13
2
MGE Pulsar Extreme - restart problem
...with Personal Solution-Pac 2 on W2k I thought that there might be a way to achieve it with nut, too. However, after trying "everything", I don't know any further. My ups.conf: driverpath = /bin [Pulsar1000] driver = mge-shut port = /dev/ttyS1 offdelay = 120 # mge-shut: ondelay in s * 10 ondelay = 15 desc = tfp-3 Manually set cold start disabled automatic restart enabled energy savings disabled Any ideas? Thanks for your answers. Axel
2018 Mar 02
1
Work around for power recycling after shutdown.return - TSSHARA UPS - nutdrv_qx driver - megatec protocol
...nitely (and it's also stated in nutdrv_qx's manpage, 'Known problems' section). > When I changed it my system was abe to at least stay off, and stopped making > an instant power recycling. Try the following things and let's see what happens: - 'offdelay=30', 'ondelay=0' (the driver will send 'S.5' to the device), - 'offdelay=120', 'ondelay=0' (the driver will send 'S02' to the device), - 'offdelay=30', 'ondelay=180' (the driver will send 'S.5R0003' to the device), - 'offdelay=120', 'ondelay...
2019 Oct 26
2
Problems with NUT on Raspberry Pi
>> [Roger wrote:] >>> By the way, do you have offdelay and ondelay values in your ups.conf ? >> >> No, I haven’t. I just added. Should I add more lines here? >> >> maxretry = 3 >> >> [ups] >> driver = usbhid-ups >> port = auto >> desc = "CPS" >> pollinterval = 15...
2018 Sep 27
2
after power outage and proper shutdown, UPS turns on before power returns
...down. Power is still out, however, roughly 40 seconds after the UPS shut down, it turns back on and it starts supplying power to the load, thus turning back on the devices attached to it. This is obviously not something I want. In trying to figure out the problem, the closest I've come was the ondelay parameter, but that only comes in play after the power returns, so it shouldn't apply here. The UPS in question is a CyberPower Value600ELCD. Its USB port is connected to my router which runs an up-to-date Debian testing with nut-{driver,monitor,server} version 2.7.4-8 installed via apt. I'...
2007 May 16
1
mge-shut don't reboot ups by default
Hi I have Pulsar 1000 (MGE) and mge-shut 2.0.5-3. By default mge-shut don;t reboot ups after upsmoc -c fsd, only permanent powerdown. After I add ondelay=30 in config, all nice, ups restarted after 10 sec. But according man mge-shut ondelay measured in tens of seconds and by default equal 3. -- Olleg Samoylov
2013 Dec 06
0
Delayed UPS start up after shutdown?
...ups.delay.start into your UPS to set the "Interval to wait before >> (re)starting the load (seconds)" >> >> use upsset to change the value. > > So far, the ups.delay.start parameter in my MGE Protection Center 675 > has always been equal to the driver.parameter.ondelay parameter (which > equals the ondelay argument in ups.conf). Furthermore, whenever I have > changed the ondelay argument in ups.conf (and restarted NUT) the above > parameters have always been set equal to ondelay. Therefore, I would > assume that ups.delay.start cannot help. Do you...
2018 Feb 02
0
Default value for ondelay
..., then: short off time, it doesn't notice and it > remains off; long off time, it does come back on. I did one minute for "long" but didn't do binary partitioning of the interval to assess the exact > threshold. The default values in ups.conf are currently offdelay = 20 and ondelay = 30. In view of your findings, shouldn't the default ondelay be offdelay+30 or even higher? Roger
2019 Apr 10
0
ondelay parameter does not work with NUT on Raspbian and Eaton 5E850iUSBDIN UPS
BTW, does it have passive cooling? Bartosz śr., 10 kwi 2019 o 16:53 Bartosz <bartoszmail at gmail.com> napisał(a): > Thanks for help! > Are you happy with your Eaton Elipse ECO 1600? > Does it work well with ondelay? > I will need some UPS that supports the ondelay parameter. > Bartosz > > śr., 10 kwi 2019 o 13:06 Roger Price <roger at rogerprice.org> napisał(a): > >> On Wed, 10 Apr 2019, Bartosz wrote: >> >> > I don't see ups.delay.start anywhere. Here is the outp...
2019 Apr 11
1
ondelay parameter does not work with NUT on Raspbian and Eaton 5E850iUSBDIN UPS
On Wed, 10 Apr 2019, Bartosz wrote: > BTW,does it have passive cooling? In the sense that there is no fan, The Eaton Ellipse ECO 1600 has passive cooling. It gets warm but not hot. > Are you happy with your Eaton Elipse ECO 1600? Does it work well with ondelay? "ECO" means that it does not have "buck and boost" or a fancy control panel. I replace my batteries every 3-4 years, and I have had an ECO 1600 die as soon as I tried to use it with the new batteries. I have not specifically tested the delayed restart with this ECO 1600 w...
2013 Mar 08
0
Windows: offdelay/ondelay
Are there plans to change the default offdelay/ondelay for the Windows versions of NUT since it can't be invoked at the end of shutdown? E.g. I have a Win2k3 server that takes just over 4min to shut down, so I set my offdelay to 600 (ondelay is +15 that) to be extra safe. Maybe a 2 min by default would be good? Most (all?) APC non-smart UPS'...
2018 Oct 18
1
after power outage and proper shutdown, UPS turns on before power returns
> > After sending the email, I revisited the usbhid-ups driver man page > > and found the part that specified that ondelay=-1 can be used in the > > scenario I am facing (for some reason, I haven't noticed this when > > initially reading the docs). And sure enough, this works, but the side > > effect is that the UPS won't come back when power returns. I've also > > tried with higher...
2019 Oct 26
3
Problems with NUT on Raspberry Pi
...hear for the "clac". > Is it possible to test the UPS using the provided software? > Problem is, there ist only Windows-software available, there is no Windows-machine in my server-rack. Maybe I will have to get a laptop to work on it. > By the way, do you have offdelay and ondelay values in your ups.conf ? No, I haven’t. I just added. Should I add more lines here? maxretry = 3 [ups] driver = usbhid-ups port = auto desc = "CPS" pollinterval = 15 > > Roger > > PS: Please keep the list traffic on the list. Thanks. So...
2019 Apr 10
2
ondelay parameter does not work with NUT on Raspbian and Eaton 5E850iUSBDIN UPS
Hi, that's a good point, thanks. I don't see ups.delay.start anywhere. Here is the output of upsrw: upsrw Eaton at localhost [outlet.desc] Outlet description Type: STRING Maximum length: 20 Value: Main Outlet [output.voltage.nominal] Nominal output voltage (V) Type: ENUM Option: "200" Option: "208" Option: "220" Option: "230" SELECTED Option:
2018 Oct 04
0
after power outage and proper shutdown, UPS turns on before power returns
...ghly 40 seconds after the UPS shut down, it turns back on and it >>> starts supplying power to the load, thus turning back on the devices >>> attached to it. This is obviously not something I want. In trying to >>> figure out the problem, the closest I've come was the ondelay >>> parameter, but that only comes in play after the power returns, so it >>> shouldn't apply here. >> >> Hi Gabriel, >> >> sorry for the delay - I am still working through a bit of a backlog here. >> >> We have a few other open CyberPowe...
2019 Apr 05
3
ondelay parameter does not work with NUT on Raspbian and Eaton 5E850iUSBDIN UPS
Hi, I have the Eaton 5E850iUSBDIN UPS connected via USB to a Raspberry Pi 3B+. It seems that everything but the ondelay parameter works so far. when I test the setup with this command: upsmon -c fsd The NUT server makes the NUT clients shut down properly and the Raspberry Pi running the NUT server shuts down correctly too. The problem is that after UPS shuts down, it immediatelly brings the power back so the Raspb...
2024 Mar 14
1
driver.parameter.offdelay vs ups.delay.shutdown / driver.parameter.ondelay vs ups.delay.start
Hi, My Cyber Power reports these two values. Each pair has the same value. Would they normally be the same thing? Thanks Alan