2006-Sep-18 14:35 UTC
[Nut-upsuser] tripp lite SMART2200RMXL2U -- empty ups.status
Hello. I'm new to nut and don't know if I've missed something in
setting it up or if my ups isn't quite supported. I'm using these:
- svn version of nut (downloaded on 9/13/06)
- a tripp lite SMART2200RMXL2U
- debian sarge with 2.6.8 kernel
- the tripplite_usb driver (newhidups says my ups is not supported)
I figured out how to get the device perms correct. A sample run is
included below. Any ideas why the ups.status line is empty?
jeff
$ sudo /usr/local/bin/upsdrvctl -DDDDD start
Password:
Network UPS Tools - UPS driver controller 2.1.0
Starting UPS: tripplite
exec: /usr/local/stow/nut-2.1-dev/bin/tripplite_usb -a tripplite
Network UPS Tools - Tripp Lite OMNIVS and SMARTPRO driver 0.6 (2.1.0)
Warning: This is an experimental driver.
Some features may not function correctly.
Detected a UPS: TRIPP LITE/TRIPP LITE SMART2200RMXL2U
Using SMARTPRO protocol (3003)
Unknown battery voltage: 0x3038
Attached to Tripp Lite SMART2200RMXL2U
Unknown value for s[2]: 0x34
$
$ sudo upsd
Network UPS Tools upsd 2.1.0
/usr/local/stow/nut-2.1-dev/etc/upsd.conf is world readable
Connected to UPS [tripplite]: tripplite
/usr/local/stow/nut-2.1-dev/etc/upsd.users is world readable
Synchronizing...done
$
$ upsc tripplite@localhost
battery.voltage: 13.50
battery.voltage.nominal: 12
driver.name: tripplite_usb
driver.parameter.port: /dev/ups
driver.parameter.productid: 0001
driver.version: 2.1.0
driver.version.internal: 0.6
input.voltage: 106
input.voltage.nominal: 120
ups.debug.D: 36 38 38 37 0d 00 00 '6887...'
ups.debug.M: 30 30 37 37 0d 00 00 '0077...'
ups.debug.S: 31 34 30 00 5a 30 0d '140.Z0.'
ups.debug.T: 38 37 32 35 37 31 0d '872571.'
ups.delay.shutdown: 64
ups.firmware: F1115.B
ups.load: 3
ups.mfr: Tripp Lite
ups.model: SMART2200RMXL2U
ups.power.nominal: 2200
ups.status:
$
Charles Lepple
2006-Sep-18 15:48 UTC
[Nut-upsuser] tripp lite SMART2200RMXL2U -- empty ups.status
On 9/18/06, Jeff Knerr <knerr@cs.swarthmore.edu> wrote:> Unknown battery voltage: 0x3038This is interesting...> Attached to Tripp Lite SMART2200RMXL2U > Unknown value for s[2]: 0x34That's the culprit. I have not had much testing time with the RM2U-style UPSes, so I was not able to map all of the status values to NUT ups.status lines. Would you have time to do some off-line testing with this UPS, or is it powering something mission-critical right now? -- - Charles Lepple
Charles Lepple
2006-Sep-19 02:42 UTC
[Nut-upsuser] tripp lite SMART2200RMXL2U -- empty ups.status
On 9/18/06, Jeff Knerr <knerr@cs.swarthmore.edu> wrote:> Unknown battery voltage: 0x3038Do you know the battery configuration for this unit? I think it translates to a nominal battery voltage of 48V (expressed in 6V steps). -- - Charles Lepple
Charles Lepple
2006-Sep-19 03:56 UTC
[Nut-upsuser] tripp lite SMART2200RMXL2U -- empty ups.status
I added some more code to SVN trunk (rev 527). Let me know how it goes. You might not want to limit it to just ups.debug, as I tried to apply some old protocol notes to decoding the values that come back. -- - Charles Lepple