On Apr 11, 2012, at 1:18 PM, MARCIO H. DAVID wrote:
> Currently I have an uninterruptible power supply manufacturer's model
which is a sine NHS, it works with the protocol SEC.
>
> The SEC is a protocol of compatible systems listed in the NUT ..
>
> I would like to Know how to monitor this nobreak Software NUT ..
>
> They could send me a tutorial with the exact setup .. (I use Ubuntu Linux
32-bit)
It's important that you understand how things work, so I won't give you
a complete tutorial. You will still want to read some of the documentation.
This table indicates that the SEC protocol is handled by the gamatronic driver:
http://www.networkupstools.org/stable-hcl.html
http://www.networkupstools.org/docs/man/gamatronic.html
So you would put "driver = gamatronic" in this file:
http://www.networkupstools.org/docs/man/ups.conf.html
You also need to find out which device node (e.g. /dev/ttyS0) corresponds to the
serial port with the UPS.
> No longer required ..
Not sure what you mean here?
--
Charles Lepple
clepple at gmail