2017 Sep 19
2
Patch for phoenixcontact modbus driver
I attach a patch for phoenixcontact_modbus.c
This patch does the following:
* Marks driver as DRV_BETA
* Fixes stale data detection when cable is disconnected
I can open a pull request if needed.
Kind Regards,
-Spiros
p.s.
please consider a faster tag/release schedule as currently linux
repositories include old versions. Sure we can make packages ourselves, but
it's better to have support
2010 Apr 13
3
liebert esp2 new version + crest factor
Hello,
1) I'm planning on adding lots of measurements to the driver liebert-esp2 +
correct support for 3-phase systems. Should I make a large patch based on
the last svn head or send you the whole file? Multiple patches per change
are probably not practical in this case.
2) in http://www.networkupstools.org/doc/2.2.0/new-names.html there is no
crest factor variable. Crest factor is very
2017 Jun 02
0
Release schedule
On June 1, 2017 9:32:34 AM GMT+02:00, Spiros Ioannou <sivann at gmail.com> wrote:
>Hi Devs,
>do you have an estimate for a new release date? We want to deploy linux
>boxes which will include support for the newly contributed
>phoenixcontact_modbus driver. As we would like to create a package for
>both
>CentOS and an embedded Linux device we have, we would prefer if the
2017 Mar 13
2
modbus driver for phoenix contact industrial UPS
Hello,
this is to let you know I will start working on a modbus driver for the
PhoenixContact QUINT-UPS industrial DC UPS, model 2320461.
https://www.phoenixcontact.com/online/portal/us?uri=pxc-oc-itemdetail:pid=2320461&library=usen&pcck=P-22-07-01-01&tab=1
I will reuse some parts of the nutdrv-modbus branch, but this will be a
model specific driver, not a generic one. Unfortunately
2009 Oct 18
3
liebert GTX2 ESP-II serial support
2009/10/15 Farkas Levente <lfarkas at lfarkas.org>
> hi,
> i read your thread at:
>
> http://lists.alioth.debian.org/pipermail/nut-upsdev/2009-January/003772.html
>
> http://lists.alioth.debian.org/pipermail/nut-upsdev/2009-January/003775.html
> we've got exactly the same problem that we need a nut driver for liebert
> ups. is there any progress in this field?
2010 Apr 30
1
please this driver if you have liebert/emerson ESP-II capable ups
As I'm trying to find the correct values for other UPS models and I
only see correct values, please use the attached driver while
compiling nut and please give me an output from upsc.
I would like you to give me the output from upsc along with the
correct values you get from Multilink or the LCD.
The only thing that must be wrong are the multipliers.
Thanks for your effort,
-Spiros
2010 Apr 21
2
liebert-esp2 patch (3-phase support)
Attached. I also attach sample output from upsc OL & OB.
I only tested it with 3-phase in/3-phase out ups.
Thanks,
-Spiros
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.alioth.debian.org/pipermail/nut-upsdev/attachments/20100421/1d18bd30/attachment.htm>
-------------- next part --------------
battery.current: 0.00
battery.runtime: 4860
2009 Jan 26
1
ups emerson liebert GTX2 ESP-II serial protocol demo
2009/1/22 Spiros Ioannou <sivann at gmail.com>
> Cher Arnaud,
>
Hi Spiros,
> I send you a demo that reads info from an Emerson Liebert
> GXT2-10000T230 through the RS-232 port. This uses the "ESP-II (ESP 2)
> Protocol".
> Current supported data includes: measurements (voltage, temperature,
> etc) , ID strings (serial number, etc), status flags (inverter on,
2010 Apr 10
2
Liebert GXT2 NUT driver - patch, multiple fixes
based on r2432, i took this with "svn diff --revision HEAD liebert-esp2.c"
fixes:
1) new way to initialize model, firmware etc. variables, the strok way
failed because some vars had spaces. (e.g. model "Liebert NX")
2) new multipliers for: frequency, nominal power. I get correct readings
now, before I had 500 Hz, and 200VA and now it's ok for me. Test with your
models.
3)
2010 Apr 02
7
Liebert GXT2 NUT driver
Hi guys,
I found the troblue and fix it!
I attached the patch.
The trouble was in the command reply buffer use.
You compute the value that value = reply[6]*256+reply[5] <- it's wrong
The right solution: value = reply[5] * 256 + reply[6];
And other bug,
battery.runtime compute, you divide this value 60 <- it's wrong
right value: divide 1.0
I continue the work on this
2017 Sep 21
0
Patch for phoenixcontact modbus driver
On Sep 19, 2017, at 3:21 AM, Spiros Ioannou <sivann at gmail.com> wrote:
>
> I attach a patch for phoenixcontact_modbus.c
>
> This patch does the following:
>
> * Marks driver as DRV_BETA
> * Fixes stale data detection when cable is disconnected
>
> I can open a pull request if needed.
Looks good to me. Which email address do you want on the commit, gmail or
2017 Mar 14
0
modbus driver for phoenix contact industrial UPS
Hi driver and pull request created, https://github.com/networkupst
ools/nut/pull/404
tested and works fine.
UPS configuration is needed, and included in the man page of the driver.
Is there any indication on the usual time it takes for a driver to be
checked/included on the master?
(We are planning on setting up hundreds of those UPS boxes and it would be
great to have an estimate)
Kind Regards,
2017 Jun 24
2
NUT supporting Modbus TCP
Hi!
I was wonering if there is a driver that supports communicating with a Modbus
aware device over IP. I have a solar/wind invertor that can broadcast its state
and I would like to monitor the batteries. If they discarge to a certain voltage
or come to a defined state, I would perform a shutdown. All of this information
id provided in Modbus holding registers. This could of course be done
2018 May 24
2
Manipulation of data.frame into an array
Hello everyone,
Thank you for this. Nonetheless it is not exactly want i need.
I need mydata[[1]] to provide the values for all 3 variables (Y, X1 and X2) of the first imputation only. As it stands it returns the whole database.
Any ideas?
Best,
ioanna
________________________________
From: Bert Gunter <bgunter.4567 at gmail.com>
Sent: 24 May 2018 16:04
To: Ioanna Ioannou
Cc:
2009 Oct 10
3
MGE NMC and NutShutdownModule (and other stuff)
Hi all,
some time ago I bought at discount price a NMC for managing a few
computers using the programmable outlets features available on my MGE
Evolution, unuseful otherwise (ATM). However, expecially for my server
machine, I don't like very much the NSM client provided by MGE/Eaton and
I'd rather use only NUT from my distribution. So, looking at the
netxml-ups driver, I started adding
2018 May 24
4
Manipulation of data.frame into an array
Hello everyone,
I want to transform a data.frame into an array (lets call it mydata), where: mydata[[1]] is the first imputed dataset...and for each mydata[[d]], the first p columns are covariates X, and the last one is the outcome Y.
Lets assume a simple data.frame:
Imputed = data.frame( X1 = c(1,2,1,2,1,2,1,2, 1,2,1,2,1,2,1,2),
X2 =
2019 Feb 12
4
Monitor Eaton 93PS UPS
I also operate an HP T1500 G3 which it's an Eaton made UPS. Connected on
usb i get frequent communication errors and data aquisition stopped. Mine
has a serial connection, also. Operating via serial has no trouble. Maybe
it's something related to usb setting in bios, i.e. Legacy mode, speed
setting, etc.
However on serial mode looks like the eaton or hoe power protector software
does not
2017 Jun 29
1
NUT supporting Modbus TCP
Yeah, I have its datasheet (it's a Xantrex XW invertor by the way). I do not know why creating a more-or-less generic driver is an issue. Of course, there are Modbus beasts that can scare everyone but mostly one would need to read either intreger or float numbers out of Modbus registers in order to decide whether or not to start or stop the shutdown process.
24 ???? 2017 ?. 19:25:14
2018 May 24
0
Manipulation of data.frame into an array
This is one of those instances where a less superficial knowledge of R's
technical details comes in really handy.
What you need to do is convert the data frame to a single (numeric) vector
for, e.g. a matrix() call. This can be easily done by noting that a data
frame is also a list and using do.call():
## imp is the data frame:
do.call(c,imp)
X11 X12 X13 X14 X15 X16 X17 X18 X19
2019 Feb 11
2
Monitor Eaton 93PS UPS
Hello,
we try to use Network UPS tools to monitor a network connected Eaton
93PS UPS. It basically works but we get frequent "Data is stale -
check driver" warnings with a "data is no longer stale" shortly after
in the log. We tried both snmp-ups and netxml-ups driver and both
raise the same error. If have captured the communication between nut
and UPS but all