Displaying 20 results from an estimated 800 matches similar to: "blazer_ser: UPS behind seriell ethernet converter"
2015 Dec 30
0
USV effekta MKD1000
Hi NUT-Team,
I have an effekta MKD1000 USV and I want to connect with NUT over serial device to this USV.I have used blazer_ser as driver but I cannot get a connection to the USV.
When I have a look to the driverlist then the effekta MKD1000 is not listed.In a window-System I can connect to the USV with the UPS management system from generex.
Can you please help me to connect with NUT to the USV.
2014 Apr 29
1
blazer_ser battery.high / battery.low
Hello list,
we've got a PowerWalker VI 1000E/RT LCD UPS and like to use it with NUT
using the blazer_ser driver.
For the blazer_ser driver to display percentage, one has to add
battery.voltage.high and battery.voltage.low voltages to the ups config.
Here's what I received from the powerwalker customer service:
Battery-Low Voltage: 21.6VDC
Battery Shutdown: 19.2VDC
Now my questions:
1.
2018 Jan 25
0
HCL Zinto 800 supported by blazer_ser and blazer_usb
Hi,
today I have tested the Zinto 800 with blazer_ser and blazer_usb on
Citrix Server 7.0. Both works fine.
upsc-Output (blazer_ser):
battery.charge: 94
battery.voltage: 25.70
battery.voltage.high: 26.00
battery.voltage.low: 20.80
battery.voltage.nominal: 24.0
device.mfr:
device.model: ZINTO 800
device.type: ups
driver.name: blazer_ser
driver.parameter.pollinterval: 2
driver.parameter.port:
2011 Apr 28
1
Problem with blazer_ser/megatec when upgrading to 2.6.0 from 2.4
Hello
First things first, thanks for great work with NUT.
For years I used Informer compact 3kVA UPS
http://www.informups.com/informer_compact.html with nut/megatec serial
driver, but it stopped working when I switched to blazer_ser with
2.6.0 upgrade.
I'm using 2.6.0 on gentoo.
Blazer_ser seems to connect with UPS, but upsmon reports driver not connected.
uname -a
Linux localhost
2012 Nov 17
1
[HCL] Aviem Power RT 1000-3000VA supported by blazer_ser
Manufacturer: Aviem Power RT 1000-3000VA
Description: Rack/Tower Intelligent Online LCD UPS.
connected with serial cable.
#upsc
battery.voltage: 24.96
battery.voltage.low: 21.5
battery.voltage.nominal: 24.0
beeper.status: enabled
device.mfr:
device.model:
device.type: ups
driver.name: blazer_ser
driver.parameter.pollinterval: 2
driver.parameter.port: /dev/ttyUSB1
driver.version: 2.6.3
2015 Feb 10
2
[HCL] Artronic art 1000 bl supported by blazer_ser
Hi Artronic art 1000 bl is supported partially by blazer_ser:
battery.voltage: 13.40battery.voltage.nominal: 12.0
beeper.status: enabled
device.type: ups
driver.name: blazer_ser
driver.parameter.pollinterval: 2
driver.parameter.port: /dev/ttyS0
driver.version: 2.6.3
driver.version.internal: 1.51
input.current.nominal: 4.0
input.frequency: 50.1
input.frequency.nominal: 50
input.voltage: 232.9
2013 May 11
1
blazer_ser problem on windows NUT 2.6.5-3780M
Hi,
I have a bunch of UPSs, most connected to pcs with Linux working 100% with
NUT.
The only one I have a problem with, is connected to Windows 7 64bit, and I
used the straight MSI installed from the website
named NUT-Installer-2.6.5-4.msi
Took me a while to find a way to get it to work, but it is ugly for now.
Just starting up the service results in a NUT not working at all, and I
tracked it
2014 Jun 02
0
blazer_ser battery.high / battery.low
On Jun 2, 2014, at 12:25 PM, Andreas Lausch / TBT wrote:
>
> Hi,
>
> thanks for the reply.
>
> On 2014-05-29 05:21, Charles Lepple wrote:
>>> Now my questions:
>>> 1. should the blazer_ser's high voltage be the voltage during charging
>>> or right after I've unplugged it from the mains?
>> sounds like during charging (or more
2015 Feb 25
0
[HCL] Artronic art 1000 bl supported by blazer_ser
On Feb 10, 2015, at 5:24 PM, Miroslav Todorov <miro0218 at yahoo.com> wrote:
> Hi Artronic art 1000 bl is supported partially by blazer_ser:
>
When you say "partially supported", what is not supported? Are any of the values incorrect?
--
Charles Lepple
clepple at gmail
2012 Jun 09
3
[HCL] REDi/Centralion Blazer 600 VA (BLAZER600c) supported by blazer_ser
The REDi Blazer 600VA (BLAZER600c) UPS found here [ro_RO]:
http://www.emag.ro/ups-redi-blazer-600va-blazer600c/pd/EX5X2BBBM/
which is actually a Centralion Blazer 600VA [en_TW]:
http://www.centralion.com/html/product/back-Product-ups-blazer400.htm
works with the blazer_ser driver
----------shell output----------
# upsrw ups
# upscmd -l ups
Instant commands supported on UPS [ups]:
beeper.toggle -
2014 Jun 02
2
blazer_ser battery.high / battery.low
Hi,
thanks for the reply.
On 2014-05-29 05:21, Charles Lepple wrote:
>> Now my questions:
>> 1. should the blazer_ser's high voltage be the voltage during charging
>> or right after I've unplugged it from the mains?
> sounds like during charging (or more accurately, during float charging at the end of the cycle):
>
>
2007 Jan 11
1
nut-upsd on mac os
Hello.
I have an cheap seriell to usb adapter with the Prolific chipset
hooked on my mac, but I don't know which tty to configure. OS X
regognizes the device in its system profiler.
/dev/ttys0 seems wrong.
Can someone please enlighten me?
Thank you for your help!
Greetings,
Robert Welz
2011 Sep 19
1
[windows port] blazer_ser issues, select_read() from serial semantics
Hi,
I tried using 2.6.1 version for windows with a Megatec-compatible UPS
and was surprised to find out it doesn't work at all.
The reason for that is blazer_ser using ser_get_buf specifying a buffer
large enough to accept any reasonably possible response, setting
buflen accordingly. That calls select_read() and it's supposed to wait
until something is available and then to read up all
2004 Jun 11
3
Einlesen von Daten unter R
Sehr geehrte Damen und Herren,
An der Fachhochschule Winterthur wurde f??r mich im Rahmen einer
Diplomarbeit (Prof. Ruckstuhl) ein R-Programm zur Auswertung von
IR-Spektren (line-shape-Analyse zur quantitativen Analyse von
Gasmischungen) entwickelt. Die Daten werden einer Excel-Tabelle
entnommen. Bisher werden die spektroskopischen Daten ??ber den Inhalt von
64 Kan??len ??ber die
2006 Jul 24
2
fentonups driver patch for Effekta MHD3000 UPS
Hi ups-devel,
As I looked throw www.networkupstools.org site, haven't found any
pointers where to send patches, so I hope this is the right place.
(Please let me know weather this is the right place.)
The patch contains a minor change in the logic of the driver, our
Effekta MHD 3000 UPS continuously writes status data to the serial port,
so one has to send a CR character and empty the
2005 Oct 05
1
NUT does not recognize Effekta MT 1500
Hello everybody,
this is my first post to this list - normally I take some time
to read some messages first to get an impression of the List,
but I have a pressing question to ask, so please forgive me if
I miss the right tone...
I just installed NUT 2.0.2 and try to get it working with our
Effekta MT 1500. In the Drievers List I found this entry:
"Effekta" "MI/MT/MH"
2014 Jun 02
2
blazer_ser battery.high / battery.low
On Jun 2, 2014, at 6:48 PM, Charles Lepple wrote:
> On Jun 2, 2014, at 12:25 PM, Andreas Lausch / TBT wrote:
>
>>
>> Hi,
>>
>> thanks for the reply.
>>
>> On 2014-05-29 05:21, Charles Lepple wrote:
>>>> Now my questions:
>>>> 1. should the blazer_ser's high voltage be the voltage during charging
>>>> or right
2014 Jun 03
0
blazer_ser battery.high / battery.low
On 2014-06-03 00:58, Charles Lepple wrote:
>> I'm pretty sure I wouldn't rely on a charge percentage derived this way ;-)
It's nice to see how much time one has left, event if it's not perfectly
accurate.
>> As mentioned in the other thread about the tripplite_usb driver, apart from having two sets of calibration constants, one for OL and one for OB, there is no
2013 Aug 11
2
N-Power MEV-3000LT compatibility report and problem
Hello list,
first of all, I'd like to report that my UPS
N-Power MEV-3000LT
(http://www.380v.ru/catalogue/micro-ups/mega-vision , in Russian),
which is not in the hardware compatibility list, is mostly supported
by the blazer_ser driver. I have very strong grounds to believe that
this (and other) N-Power UPS'es are rebranded for Russian and
Italian markets from their counterparts
2010 Dec 02
1
(no subject)
I am have a nice result whith blazer_ser driver! respect!
# ./nut start
Network UPS Tools - UPS driver controller 2.4.1
Network UPS Tools - Megatec/Q1 protocol serial driver 1.51 (2.4.1)
Supported UPS detected with megatec protocol
Vendor information read in 1 tries
Battery runtime will not be calculated (runtimecal not set)
<================= !!!
Starting nut.
Network UPS Tools upsd 2.4.1