N-Power MEV-3000LT compatibility report and problem
On Aug 11, 2013, at 2:12 PM, ????????? ???????? wrote: > I see no problem with how the device communicates the Blazer/Megatec protocol. > I must have found a bug in the driver. It is possible that the shutdown was tested with a different implementation of the protocol. What do you get from the "I" command? On Aug 11, 2013, at 11:25 AM, ????????? ???????? wrote: > So I
2013 Aug 11
0
N-Power MEV-3000LT compatibility report and problem
Hello, sorry for messing up the things. I mean many copies of the same text in my previous message and mixing up the command names, it turned out that I forgot the protocol details after so many years. I found my records, connected a serial terminal to the UPS and found that the device itself works as expected so my problem cannot be explained with device incompatibility. Below is excerpt from
2013 Aug 11
1
N-Power MEV-3000LT compatibility report and problem
Hello, the code below the failing part mentions this flavor of protocol, drivers/blazer_ser.c:463 /* * If a command is invalid, it will be echoed back. * As an exception, Best UPS units will report "ACK" in case of success! */ I prepared a patch, it adds a similar check and also checks (in both occurencies) for blazer_command()<0, the latter
2013 Aug 11
0
N-Power MEV-3000LT compatibility report and problem
Hello, > What do you get from the "I" command? A string of 8 spaces. >> So I believe the compatibility list deserves two new lines. > >Probably best to delay adding this to the HCL until we can get the driver to shut down the UPS properly. I debugged the problem. From the source, drivers/blazer.c:418 /* * If a command is invalid, it
2014 Apr 29
1
blazer_ser battery.high / battery.low
Hello list, we've got a PowerWalker VI 1000E/RT LCD UPS and like to use it with NUT using the blazer_ser driver. For the blazer_ser driver to display percentage, one has to add battery.voltage.high and battery.voltage.low voltages to the ups config. Here's what I received from the powerwalker customer service: Battery-Low Voltage: 21.6VDC Battery Shutdown: 19.2VDC Now my questions: 1.
2011 Apr 28
1
Problem with blazer_ser/megatec when upgrading to 2.6.0 from 2.4
Hello First things first, thanks for great work with NUT. For years I used Informer compact 3kVA UPS http://www.informups.com/informer_compact.html with nut/megatec serial driver, but it stopped working when I switched to blazer_ser with 2.6.0 upgrade. I'm using 2.6.0 on gentoo. Blazer_ser seems to connect with UPS, but upsmon reports driver not connected. uname -a Linux localhost
2014 May 04
1
blazer_ser: UPS behind seriell ethernet converter
Hi, I'm trying to get an Effekta UPS (works directly with blazer_ser) working behind a seriell to ethernet converter (Brainboxes ES-246). I've set the converter to 2400 baud, 8N1, no flow control. On the linux side I started socat and blazer_ser. All I got are timeouts after 12 seconds. I can see network traffic with tcpdump but I've no idea what to do to get this working. Does
2018 Jan 25
0
HCL Zinto 800 supported by blazer_ser and blazer_usb
Hi, today I have tested the Zinto 800 with blazer_ser and blazer_usb on Citrix Server 7.0. Both works fine. upsc-Output (blazer_ser): battery.charge: 94 battery.voltage: 25.70 battery.voltage.high: 26.00 battery.voltage.low: 20.80 battery.voltage.nominal: 24.0 device.mfr: device.model: ZINTO 800 device.type: ups driver.name: blazer_ser driver.parameter.pollinterval: 2 driver.parameter.port:
2012 Nov 17
1
[HCL] Aviem Power RT 1000-3000VA supported by blazer_ser
Manufacturer: Aviem Power RT 1000-3000VA Description: Rack/Tower Intelligent Online LCD UPS. connected with serial cable. #upsc battery.voltage: 24.96 battery.voltage.low: 21.5 battery.voltage.nominal: 24.0 beeper.status: enabled device.mfr: device.model: device.type: ups driver.name: blazer_ser driver.parameter.pollinterval: 2 driver.parameter.port: /dev/ttyUSB1 driver.version: 2.6.3
2013 May 11
1
blazer_ser problem on windows NUT 2.6.5-3780M
Hi, I have a bunch of UPSs, most connected to pcs with Linux working 100% with NUT. The only one I have a problem with, is connected to Windows 7 64bit, and I used the straight MSI installed from the website named NUT-Installer-2.6.5-4.msi Took me a while to find a way to get it to work, but it is ugly for now. Just starting up the service results in a NUT not working at all, and I tracked it
2015 Feb 10
2
[HCL] Artronic art 1000 bl supported by blazer_ser
Hi Artronic art 1000 bl is supported partially by blazer_ser: battery.voltage: 13.40battery.voltage.nominal: 12.0 beeper.status: enabled device.type: ups driver.name: blazer_ser driver.parameter.pollinterval: 2 driver.parameter.port: /dev/ttyS0 driver.version: 2.6.3 driver.version.internal: 1.51 input.current.nominal: 4.0 input.frequency: 50.1 input.frequency.nominal: 50 input.voltage: 232.9
2010 Dec 02
1
(no subject)
I am have a nice result whith blazer_ser driver! respect! # ./nut start Network UPS Tools - UPS driver controller 2.4.1 Network UPS Tools - Megatec/Q1 protocol serial driver 1.51 (2.4.1) Supported UPS detected with megatec protocol Vendor information read in 1 tries Battery runtime will not be calculated (runtimecal not set) <================= !!! Starting nut. Network UPS Tools upsd 2.4.1
2011 Aug 26
1
Unsupported UPS Orvaldi 520PL?
Hello, I am new to UPS stuff, please be patient with me ;-) Archlinux i686, kernel 3.0-ARCH #1 SMP PREEMPT. nut 2.6.1 installed from source via Arch's AUR repository. Mother board GA D525TUD with two serial ports, both enabled in BIOS. I got some old Orvaldi 520 PL UPS [1], which is supposed to be supported by the vendor [2] with sw called UPSmart. The statically compiled i386 binary ran
2013 Apr 02
3
blazer driver: Possible bugs with battery packs
Hello all, long time away from this list, glad to be around again! I have this Powercom Vanguard VGN VGD-20K31. Some details of this model: * 3-phase input, single phase output * Model has 240V / 12V9AH x 20 x 2SET, plus another set of 20 batteries. All in all, 3 sets * Serial connection to Windows 2k3 server with UPSMon Now I was strongly considering replacing the bundled no-good upsmoon
2020 Jul 07
2
New UPS to the DB
Hi, I have an OEM of KStar UDC9101S which is Megatec protocol rs232 capable unit. So I use blazer_ser protocol=megatec /dev/ttyUSB0 with no issue to get NUT running. Please direct me what command should I issue to collect the data in order to include the UPS to device database? P.S. tryed /lib/nut/blazer_ser -DD... but no difference from a regular output has being added by the driver.
2014 Feb 19
0
nut driver for SMS (brazil) UPS
Hi Charles, I'll try the blazer_ser and the nutdrv_qx with version 2.7.1 later. Below, the result of 'lsusb -vvv' requested: Bus 004 Device 002: ID 04b4:5500 Cypress Semiconductor Corp. HID->COM RS232 Adapter Device Descriptor: bLength 18 bDescriptorType 1 bcdUSB 1.00 bDeviceClass 0 (Defined at Interface level)
2015 Nov 19
2
Contact-closure UPS
Hi Charles, I am done with few things: I made the cable - looks good, because I see some activities. I upgraded NUT to 2.7.3. but I have no success to start driver(this are the outputs) nut.cfg MODE = netserver ups.conf [infosec] driver = nutdrv_qx (or blazer_ser) port = /dev/ttyS1 desc = "XP Pro 2500 RM" output(nutdrv_qx cmd upsdrvctl -DDD start) Network UPS
2014 Jun 02
0
blazer_ser battery.high / battery.low
On Jun 2, 2014, at 12:25 PM, Andreas Lausch / TBT wrote: > > Hi, > > thanks for the reply. > > On 2014-05-29 05:21, Charles Lepple wrote: >>> Now my questions: >>> 1. should the blazer_ser's high voltage be the voltage during charging >>> or right after I've unplugged it from the mains? >> sounds like during charging (or more
2012 Jun 09
3
[HCL] REDi/Centralion Blazer 600 VA (BLAZER600c) supported by blazer_ser
The REDi Blazer 600VA (BLAZER600c) UPS found here [ro_RO]: http://www.emag.ro/ups-redi-blazer-600va-blazer600c/pd/EX5X2BBBM/ which is actually a Centralion Blazer 600VA [en_TW]: http://www.centralion.com/html/product/back-Product-ups-blazer400.htm works with the blazer_ser driver ----------shell output---------- # upsrw ups # upscmd -l ups Instant commands supported on UPS [ups]: beeper.toggle -
2015 Nov 16
2
Contact-closure UPS
Hi Charles, >----- Original Message ----- >From: "Charles Lepple" <clepple at gmail.com> >To: "R?bert SZAKSZ" <robert at szaksz.eu> >Cc: nut-upsuser at lists.alioth.debian.org >Sent: Monday, November 16, 2015 3:20:17 PM >Subject: Re: [Nut-upsuser] Contact-closure UPS > >[please use reply-all when responding - the list does not modify the