search for: wiezbicki

Displaying 14 results from an estimated 14 matches for "wiezbicki".

2016 Jan 13
2
[HCL] NHS Laser Senoidal 5000VA supported by gamatronic
...ease the UPS load or not. It's a value calculated from the UPS to notice the User how much time he have until the UPs battery achieve the depleted status. The battery.run.low can be higher than battery.runtime, do you agree? ----------------------------------------------------------- Thiago Wiezbicki NHS Sistemas de Energia Av. Juscelino Kubitschek de Oliveira, 5270 Cidade Industrial - Curitiba - PR Fone/Fax: +55 41 2141-9262 http://www.nhs.com.br ----- Mensagem original ----- De: "Charles Lepple" <clepple at gmail.com> Para: "Thiago Wiezbicki - NHS" <thiago.w...
2016 Jan 08
2
[HCL] NHS Laser Senoidal 5000VA supported by gamatronic
...ominal: 05000 > ups.status: ALARM OB This value is high because we don't have a load in the output of the UPS, therefore, with this load the time until the UPS achieve the low battery status is 59940 seconds. Best Regards. ----------------------------------------------------------- Thiago Wiezbicki NHS Sistemas de Energia Av. Juscelino Kubitschek de Oliveira, 5270 Cidade Industrial - Curitiba - PR Fone/Fax: +55 41 2141-9262 http://www.nhs.com.br
2014 Nov 22
2
[HCL] NHS Expert C Online 6000 supported by gamatronic
...: 0.0 output.frequency: 60.0 output.voltage: 120.9 ups.alarm: Input Bad ups.firmware: EXOL(02).21 ups.id: 92C08623BD6513AF ups.load: 000 ups.mfr: NHS Sistemas de Energia ups.model: EXPERT GIII 8kVA ups.power.nominal: 08000 ups.status: ALARM OB Best Regards, ------------------------------ Thiago Wiezbicki NHS Sistemas Eletr?nicos Av. Juscelino Kubitschek de Oliveira, 5270 Cidade Industrial, Curitiba - PR - Brasil Fone/Fax: +55 41 2141 9262 <callto:41%202141%209262> www.nhs.com.br 2014-11-17 11:55 GMT-02:00 Charles Lepple <clepple at gmail.com>: > On Nov 12, 2014, at 5:46 AM, Thiago...
2014 Nov 23
0
[HCL] NHS Expert C Online 6000 supported by gamatronic
On Nov 22, 2014, at 5:16 AM, Thiago Wiezbicki <thiagowzb at gmail.com> wrote: > Below , it's a second upsc command using our UPS on battery and with device ID, battery time, battery low time that UPS calcs correctly. Let me remember now, We have the same UPS in 6, 8, 10 and 12 kVA version, and it's names are : Expert C Onl...
2014 Nov 26
1
[HCL] NHS Expert C Online 6000 supported by gamatronic
What information Do I need to provide more, beyond upsc and shutdown tests for add these devices on HCL ? Thanks, ------------------------------ Thiago Wiezbicki -------------- next part -------------- An HTML attachment was scrubbed... URL: <http://lists.alioth.debian.org/pipermail/nut-upsdev/attachments/20141125/07793b94/attachment-0001.html>
2015 Dec 29
2
[HCL] NHS Laser Senoidal 5000VA supported by gamatronic
...d: 000 ups.mfr: NHS Sistemas de Energia ups.model: Laser Senoidal 5000VA ups.power.nominal: 05000 ups.status: ALARM OB I've tested and the shutdown occours when??????? ups.status? it's? equal? OB LB Best Regards. ----------------------------------------------------------- Thiago Wiezbicki NHS Sistemas de Energia Av. Juscelino Kubitschek de Oliveira, 5270 Cidade Industrial - Curitiba - PR Fone/Fax: +55 41 2141-9262 http://www.nhs.com.br -------------- next part -------------- An HTML attachment was scrubbed... URL: <http://lists.alioth.debian.org/pipermail/nut-upsdev/attach...
2014 Nov 17
0
[HCL] NHS Expert C Online 6000 supported by gamatronic
On Nov 12, 2014, at 5:46 AM, Thiago Wiezbicki <thiagowzb at gmail.com> wrote: > > > Device Manufacturer: NHS > Device Name: Expert C Online 6000 > > upsc output: > > battery.charge: 100 > battery.current: 0.6 > battery.date: 01012014 > battery.runtime: 00000 Quick question: does "battery.runtime...
2016 Apr 28
2
A "standard" serial protocol?
I'm still working on the interface to the UPS we're selling. USB works great with NUT in Linux, and natively through Windows battery support. Now I'm looking over the serial protocol. I can essentially make it anything I want, and it's VERY tempting to make my own protocol that is intuitive and simple, but I have a feeling every UPS maker does that. So, before I do that...is
2014 Nov 12
2
[HCL] NHS Expert C Online 6000 supported by gamatronic
Device Manufacturer: NHS Device Name: Expert C Online 6000 upsc output: battery.charge: 100 battery.current: 0.6 battery.date: 01012014 battery.runtime: 00000 battery.runtime.low: 59940 battery.temperature: 29 battery.voltage: 210.5 device.mfr: NHS Sistemas de Energia device.model: EXPERT GIII 8kVA device.type: ups driver.name: gamatronic driver.parameter.pollinterval: 20
2016 Jan 09
0
[HCL] NHS Laser Senoidal 5000VA supported by gamatronic
On Jan 8, 2016, at 7:09 AM, Thiago Wiezbicki - NHS <thiago.wiezbicki at nhs.com.br> wrote: > >>> battery.runtime: 00076 >>> battery.runtime.low: 59940 >> >> This seems rather high. This variable is supposed to represent the runtime [in seconds] below which the UPS will signal "LB", but this c...
2016 Jan 14
0
[HCL] NHS Laser Senoidal 5000VA supported by gamatronic
On Jan 13, 2016, at 6:00 AM, Thiago Wiezbicki - NHS <thiago.wiezbicki at nhs.com.br> wrote: > > The battery.run.low can be higher than battery.runtime, do you agree? I agree with that statement, given what the gamatronic driver is currently reporting. However, I think it should report the elapsed time as battery.runtime.elapsed....
2016 Jan 06
0
[HCL] NHS Laser Senoidal 5000VA supported by gamatronic
This is the same as https://github.com/networkupstools/nut/issues/254 , right? (It's on my TODO list. DDL updates take a little longer than HCL updates.) Other comments below. > On Dec 29, 2015, at 1:55 PM, Thiago Wiezbicki - NHS <thiago.wiezbicki at nhs.com.br> wrote: > > Device Manufacturer: NHS > Device Name: Laser Senoidal 5000VA > > upsc output when the UPS is in normal condition: > > battery.charge: 100 > battery.current: 0.4 > battery.date: 12292015 > battery.runtime: 0000...
2016 May 02
0
A "standard" serial protocol?
...entation: http://networkupstools.org/protocols/sec.html http://networkupstools.org/protocols/sec-protocol.html http://networkupstools.org/protocols/sec-standard.html http://networkupstools.org/protocols/us9003.html Regards. ----------------------------------------------------------- Thiago Wiezbicki De: "Rob Groner" <rgroner at RTD.com> Para: "nut-upsdev" <nut-upsdev at lists.alioth.debian.org> Enviadas: Quinta-feira, 28 de abril de 2016 13:03:43 Assunto: [Nut-upsdev] A "standard" serial protocol? I?m still working on the interface to the U...
2014 Dec 08
1
Centralized Monitoring of Question
Hello Sir/Madam, I have a question related to UPS monitoring by SNMP cards via NUT(Network UPS Tools). We have a few SNMP Cards (MEGATEK) that connecting to a number of UPS`s. We need a centralized program to monitoring of our UPS`s. We want to know that, NUT can help us? Operating System: Windows or Linux SNMP Card type: Netagent model for MEGATEK company (www.megatec.com.tw). Yours