Contact-closure UPS
...t protocol, I still think that is worth trying first. But it's up to you.
I am not 100% sure that smart protocol is capable, because the only one place where it is mentioned is the picture I sended you.
Question for contact cable http://web.archive.org/web/20100106160328/http://ups.miem.edu.ru/ups_faq5.html type 5.2.1 is to set
CP[RTS] OL[CTS] LB[DCD] SD[DTR] is this correct?
Best regards,
Robert SZAKSZ.
2015 Nov 16
2
Contact-closure UPS
...o configure CP[???], OL[???], LB[???], SD[???]?
>> No one from predefined 21 types worked for me.
>>
>
>The RUPS 2000 cable type in genericups seems to correspond to a crossed cable as shown in 5.2.1 below:
>
>http://web.archive.org/web/20100106160328/http://ups.miem.edu.ru/ups_faq5.html
>
>You might also be able to connect up the TxD and RxD lines, and use the nutdrv_qx (not available until after v2.6.5), megatec or blazer_ser drivers:
>
>PC UPS Description
>== === ===========
>2 9 TxD
>3 6 RxD
>5 7 Ground
>
>--
>Charles Lepple
>clepple at...
2015 Nov 16
2
Contact-closure UPS
Hello,
I have one UPS Infosec XP Pro 2500 RM and it works with windows sw RUPS2000.
Now I want to install this UPS as virtual server on vmware ESXi vMA - (SUSE SLES 11SP2 linux).
On this linux I have NUT 2.6.0 and I stopped now with configuration of genericups driver.
Working cable (direct cable pin1-pin1 ... pin9-pin9) connection on Windows:
PIN | PC | UPS
2015 Nov 16
0
Contact-closure UPS
...d the question is, how to configure CP[???], OL[???], LB[???], SD[???]?
> No one from predefined 21 types worked for me.
>
The RUPS 2000 cable type in genericups seems to correspond to a crossed cable as shown in 5.2.1 below:
http://web.archive.org/web/20100106160328/http://ups.miem.edu.ru/ups_faq5.html
You might also be able to connect up the TxD and RxD lines, and use the nutdrv_qx (not available until after v2.6.5), megatec or blazer_ser drivers:
PC UPS Description
== === ===========
2 9 TxD
3 6 RxD
5 7 Ground
--
Charles Lepple
clepple at gmail
2015 Nov 17
0
Contact-closure UPS
...cable mentioned by you - above 3 wire cable)?
If I am reading the code correctly, it does not need anything other than Tx/Rx/Ground (ser_open() sets CLOCAL, which ignores modem control lines). So that cable should work.
> or
> http://web.archive.org/web/20100106160328/http://ups.miem.edu.ru/ups_faq5.html (cable 5.4.1)?
The loopback connections would be for the modem control lines (hardware handshaking, which your UPS probably does not do). Other than that, I think the DB-9 pinout is the same.
nutdrv_qx would be best, but blazer_ser is the next newest driver.
--
Charles Lepple
clepple at gm...
2015 Nov 21
0
Contact-closure UPS
...100% sure that smart protocol is capable, because the only one place where it is mentioned is the picture I sended you.
But your original email mentioned "UPS TxD" and "UPS RxD"...
> Question for contact cable http://web.archive.org/web/20100106160328/http://ups.miem.edu.ru/ups_faq5.html type 5.2.1 is to set
> CP[RTS] OL[CTS] LB[DCD] SD[DTR] is this correct?
Probably. The testing procedure at http://www.networkupstools.org/docs/man/genericups.html#_testing_compatibility should help in case some of the signals need a "-".
--
Charles Lepple
clepple at gmail
2015 Nov 21
2
Contact-closure UPS
>On Nov 20, 2015, at 12:17 PM, R?bert SZAKSZ <robert at szaksz.eu> wrote:
>>
>> No progress has been made:
>>
>> cable is UPS - PC
>> 6 - 3
>> 7 - 5
>> 9 - 2
>>
>
>Maybe pins 4 and 7 (ground) both need to be connected on the UPS side?
I connected both to pin 5
>Unfortunately, I don't think there is a safe way (in software)
2015 Nov 19
2
Contact-closure UPS
...cable mentioned by you - above 3 wire cable)?
If I am reading the code correctly, it does not need anything other than Tx/Rx/Ground (ser_open() sets CLOCAL, which ignores modem control lines). So that cable should work.
> or
> http://web.archive.org/web/20100106160328/http://ups.miem.edu.ru/ups_faq5.html (cable 5.4.1)?
The loopback connections would be for the modem control lines (hardware handshaking, which your UPS probably does not do). Other than that, I think the DB-9 pinout is the same.
nutdrv_qx would be best, but blazer_ser is the next newest driver.
--
Charles Lepple
clepple at gm...