search for: ups_1500

Displaying 17 results from an estimated 17 matches for "ups_1500".

2020 Jan 08
4
Hardware compatibility report: APC Smart-UPS_1500
Gene's posting: https://alioth-lists.debian.net/pipermail/nut-upsuser/2020-January/011654.html contains a NUT 2.7.4 update for the APC Smart-UPS_1500 device dump at https://networkupstools.org/ddl/APC/Smart-UPS_1500.html Please note the changes since the 2.7.2 report, e.g. ups.delay.start is no longer supported. Roger
2020 Jan 08
0
Hardware compatibility report: APC Smart-UPS_1500
On Wednesday 08 January 2020 15:44:10 Roger Price wrote: > Gene's posting: > https://alioth-lists.debian.net/pipermail/nut-upsuser/2020-January/011 >654.html contains a NUT 2.7.4 update for the APC Smart-UPS_1500 device > dump at https://networkupstools.org/ddl/APC/Smart-UPS_1500.html > > Please note the changes since the 2.7.2 report, e.g. ups.delay.start > is no longer supported. > > Roger > No matter, thats 2.7.2 I'm running. Cheers, Gene Heskett -- "There are four boxes t...
2020 Jan 08
1
unexpected UPS status
On Wed, 8 Jan 2020, Gene Heskett wrote: > On Wednesday 08 January 2020 06:44:03 Roger Price wrote: >> I am surprised that there is no ups.delay.start for this UPS. > My new APC Smart-UPS_1500 doesn't have it either. Hello Gene, The NUT 2.7.2 "device dump library" entry for the APC Smart-UPS 1500 at https://networkupstools.org/ddl/APC/Smart-UPS_1500.html shows an entry for ups.delay.start, so could you submit the output of the commands upsc <ups>, upsrw <ups&gt...
2024 May 24
2
APC SMC1500 question
Hello mailing List. I manage 2 UPS via NUT, an APC Smart-UPS_1500 and an ?EATON 5S 1500. I can get load information on the EATON but not on the APC. Actually upsc doesn?t give much information on the APC. Does someone know whether this is a driver limitation or a configuration issue ? Many thanks for your views. Laurent PS: my goal is to monitor the UPS...
2020 Jan 08
2
unexpected UPS status
On Tue, 7 Jan 2020, Eyal Lebedinsky wrote: > On 2020-01-07 23:01, Roger Price wrote: >> There is no report for variable "ups.delay.start" in your upsc output. >> What does command "upsc <ups> ups.delay.start" report? > > $ upsc eaton ups.delay.start > Init SSL without certificate database > Error: Variable not supported by UPS I am surprised
2019 Sep 14
2
Changing UPS to a bigger APC 1500 1000WA, what driver?
...g it as far under the table as I can get it on a 30% heart. Yeah, I'm getting on, I'll be 85 in about 2 weeks. Heart surgury will be scheduled in the next few days to replace a worn out, leaky aortic valve. Piece if cake if my veins are big enough. So what driver do I use with a Smart-UPS_1500??? Never mind it was found and accessed by the bootup! upsc my usp reports: gene at coyote:~$ upsc myups Init SSL without certificate database <<- whats this mean? battery.charge: 88 battery.charge.low: 10 battery.charge.warning: 50 battery.runtime: -1 battery.runtime.low: 150 battery.type:...
2020 Jul 21
0
ups is not reporting load %
...d-build$ upsc myups Init SSL without certificate database battery.charge: 99 battery.charge.low: 10 battery.charge.warning: 50 battery.runtime: 0 battery.runtime.low: 150 battery.type: PbAc battery.voltage: 27.1 battery.voltage.nominal: 24.0 device.mfr: American Power Conversion device.model: Smart-UPS_1500 device.serial: 3S1906X11389 device.type: ups driver.name: usbhid-ups driver.parameter.offdelay: 120 driver.parameter.ondelay: 0 driver.parameter.pollfreq: 30 driver.parameter.pollinterval: 2 driver.parameter.port: auto driver.parameter.synchronous: no driver.version: 2.7.4 driver.version.data: APC...
2024 May 25
1
APC SMC1500 question
d tbsky <tbskyd at gmail.com> > > Laurent Taieb via Nut-upsuser > > > > Hello mailing List. > > > > I manage 2 UPS via NUT, an APC Smart-UPS_1500 and an EATON 5S 1500. > > > > I can get load information on the EATON but not on the APC. > > > > Actually upsc doesn?t give much information on the APC. > > > > Does someone know whether this is a driver limitation or a configuration issue ? > > if you ca...
2023 Jun 19
1
had to reinstall on new drive, lost all nut related .conf's
...0 bDeviceSubClass 0 bDeviceProtocol 0 bMaxPacketSize0 64 idVendor 0x051d American Power Conversion idProduct 0x0003 UPS bcdDevice 0.01 iManufacturer 1 American Power Conversion iProduct 2 Smart-UPS_1500 FW:UPS 03.5 / ID=1015 iSerial 3 3S1906X11389 Where do I start and what do I added to which files in /etc/nut so I can type "upsc myups" and get a status report? Its been years since I dived thru all these flaming hoops the last time. Thanks. Cheers, Gene Heskett....
2023 Jun 20
1
had to reinstall on new drive, lost all nut related .conf's
...> ? bDeviceProtocol???????? 0 > ? bMaxPacketSize0??????? 64 > ? idVendor?????????? 0x051d American Power Conversion > ? idProduct????????? 0x0003 UPS > ? bcdDevice??????????? 0.01 > ? iManufacturer?????????? 1 American Power Conversion > ? iProduct??????????????? 2 Smart-UPS_1500 FW:UPS 03.5 / ID=1015 > ? iSerial???????????????? 3 3S1906X11389 > > Where do I start and what do I added to which files in /etc/nut so I can > type "upsc myups" and get a status report?? Its been years since I dived > thru all these flaming hoops the last time. > &...
2019 Dec 09
0
new mobo, ups doesn't connect
...e:nut$ upsc myups Init SSL without certificate database battery.charge: 100 battery.charge.low: 10 battery.charge.warning: 50 battery.runtime: 0 battery.runtime.low: 150 battery.type: PbAc battery.voltage: 26.3 battery.voltage.nominal: 24.0 device.mfr: American Power Conversion device.model: Smart-UPS_1500 device.serial: 3S1906X11389 device.type: ups driver.name: usbhid-ups driver.parameter.offdelay: 120 driver.parameter.ondelay: 0 driver.parameter.pollfreq: 30 driver.parameter.pollinterval: 2 driver.parameter.port: auto driver.parameter.synchronous: no driver.version: 2.7.4 driver.version.data: APC...
2019 Dec 09
2
new mobo, ups doesn't connect
On Sunday 08 December 2019 21:48:03 Charles Lepple wrote: > On Dec 7, 2019, at 7:01 PM, Gene Heskett <gheskett at shentel.net> wrote: > > What driver do I now put in /etc/nut/ups.conf? hid-generic doesn't > > seem to want to talk to it, and the original name _(usbhid-ups) > > doesn't work from new mobo. Oh wait, I can't spell. But that didn't > >
2019 Dec 08
4
new mobo, ups doesn't connect
...ware. dmesg now says this: 71068.842780] usb 1-9: new full-speed USB device number 10 using xhci_hcd [71069.012577] usb 1-9: New USB device found, idVendor=051d, idProduct=0003 [71069.012579] usb 1-9: New USB device strings: Mfr=1, Product=2, SerialNumber=3 [71069.012579] usb 1-9: Product: Smart-UPS_1500 FW:UPS 03.5 / ID=1015 [71069.012580] usb 1-9: Manufacturer: American Power Conversion [71069.012581] usb 1-9: SerialNumber: 3S1906X11389 [71069.126796] hid-generic 0003:051D:0003.0003: hiddev0,hidraw2: USB HID v1.11 Device [American Power Conversion Smart-UPS_1500 FW:UPS 03.5 / ID=1015] on usb-0...
2020 Jan 08
0
unexpected UPS status
...command "upsc <ups> ups.delay.start" report? > > > > $ upsc eaton ups.delay.start > > Init SSL without certificate database > > Error: Variable not supported by UPS > > I am surprised that there is no ups.delay.start for this UPS. > My new APC Smart-UPS_1500 doesn't have it either. > > $ upsrw eaton > > [outlet.desc] > > [output.voltage.nominal] > > [ups.delay.shutdown] > > [ups.start.battery] > > It looks as if this UPS unit is not capable of delaying a restart on > wall power return until a given charge lev...
2024 May 25
1
APC SMC1500 question
...:00, ? d tbsky ? <tbskyd at gmail.com <mailto:tbskyd at gmail.com>> a ?crit : d tbsky <tbskyd at gmail.com <mailto:tbskyd at gmail.com>> > > Laurent Taieb via Nut-upsuser > > > > Hello mailing List. > > > > I manage 2 UPS via NUT, an APC Smart-UPS_1500 and an EATON 5S 1500. > > > > I can get load information on the EATON but not on the APC. > > > > Actually upsc doesn?t give much information on the APC. > > > > Does someone know whether this is a driver limitation or a configuration issue ? > > if you can...
2023 Jun 20
1
had to reinstall on new drive, lost all nut related .conf's
...??????? 0 >> ?? bMaxPacketSize0??????? 64 >> ?? idVendor?????????? 0x051d American Power Conversion >> ?? idProduct????????? 0x0003 UPS >> ?? bcdDevice??????????? 0.01 >> ?? iManufacturer?????????? 1 American Power Conversion >> ?? iProduct??????????????? 2 Smart-UPS_1500 FW:UPS 03.5 / ID=1015 >> ?? iSerial???????????????? 3 3S1906X11389 >> >> Where do I start and what do I added to which files in /etc/nut so I >> can type "upsc myups" and get a status report?? Its been years since I >> dived thru all these flaming hoops the...
2023 Feb 20
1
Issue with two UPS APC managed from a single PC.
Is that with both UPSes on same machine? A quick guess would be that insufficient data points to identify the device are configured (vendorid, productid, serial...) in ups.conf, so both drivers connect to the first match. I'd expect them to conflict and one would die or both loop reconnecting, if both are running at once, though. Also, which NUT version? Custom build from GitHub or an