Displaying 14 results from an estimated 14 matches for "szaksz".
2015 Nov 16
2
Contact-closure UPS
Hi Charles,
>----- Original Message -----
>From: "Charles Lepple" <clepple at gmail.com>
>To: "R?bert SZAKSZ" <robert at szaksz.eu>
>Cc: nut-upsuser at lists.alioth.debian.org
>Sent: Monday, November 16, 2015 3:20:17 PM
>Subject: Re: [Nut-upsuser] Contact-closure UPS
>
>[please use reply-all when responding - the list does not modify the reply-to header.]
>
>> On Nov 16,...
2015 Nov 21
2
Contact-closure UPS
>On Nov 20, 2015, at 12:17 PM, R?bert SZAKSZ <robert at szaksz.eu> wrote:
>>
>> No progress has been made:
>>
>> cable is UPS - PC
>> 6 - 3
>> 7 - 5
>> 9 - 2
>>
>
>Maybe pins 4 and 7 (ground) both need to be connected on the UPS side?
I connected both to pin 5
>Unfortunately,...
2015 Nov 21
2
Contact-closure UPS
>> On Nov 21, 2015, at 2:43 AM, R?bert SZAKSZ <robert at szaksz.eu> wrote:
>>
>> I mesured it and on DC and it shows 0 V (zero V).
>> May be the information (pls. see attachment) that UPS PIN1 should bee keept HI is mandatory. Should I connect it to PC PIN4 DTR?
>
>Certainly possible. blazer_ser and nutdrv_qx sh...
2015 Nov 19
2
Contact-closure UPS
...0.003112 1 remaining attempts
0.003716 exec: /usr/lib/ups/driver/blazer_ser -a infosec
Network UPS Tools - Megatec/Q1 protocol serial driver 1.56 (2.7.3)
No supported UPS detected
12.135176 Driver failed to start (exit status=1)
Please what I am doing wrong?
Best regards,
Robert SZAKSZ.
----- Original Message -----
From: "Charles Lepple" <clepple at gmail.com>
To: "R?bert SZAKSZ" <robert at szaksz.eu>
Cc: nut-upsuser at lists.alioth.debian.org
Sent: Tuesday, November 17, 2015 3:56:58 AM
Subject: Re: [Nut-upsuser] Contact-closure UPS
On Nov 16, 2...
2015 Nov 20
2
Contact-closure UPS
...ut (0)
29.161413 qx_process_answer: short reply (input.voltage)
29.161734 send: 'Q1'
30.163172 read: timeout (0)
30.163194 qx_process_answer: short reply (input.voltage)
30.163200 Device not supported!
30.163204 Device not supported!
Best regards,
Robert SZAKSZ
----- Original Message -----
From: "Charles Lepple" <clepple at gmail.com>
To: "R?bert SZAKSZ" <robert at szaksz.eu>
Cc: nut-upsuser at lists.alioth.debian.org
Sent: Friday, November 20, 2015 1:39:17 PM
Subject: Re: [Nut-upsuser] Contact-closure UPS
On Nov 19, 201...
2015 Nov 16
2
Contact-closure UPS
.... described as UPS RxD and 2. 3 seconds Hi (UPS shutdown)
Pin7 | RTS | UPS ground
Pin8 | CTS | N/A
Pin9 | RI | described as UPS TxD
And the question is, how to configure CP[???], OL[???], LB[???], SD[???]?
No one from predefined 21 types worked for me.
Thank for help,
Robert SZAKSZ.
2015 Nov 16
0
Contact-closure UPS
[please use reply-all when responding - the list does not modify the reply-to header.]
> On Nov 16, 2015, at 8:24 AM, R?bert SZAKSZ <robert at szaksz.eu> wrote:
>
> Hello,
>
> I have one UPS Infosec XP Pro 2500 RM and it works with windows sw RUPS2000.
> Now I want to install this UPS as virtual server on vmware ESXi vMA - (SUSE SLES 11SP2 linux).
> On this linux I have NUT 2.6.0 and I stopped now with...
2015 Nov 17
0
Contact-closure UPS
On Nov 16, 2015, at 3:57 PM, R?bert SZAKSZ <robert at szaksz.eu> wrote:
>
> Thank you for your answer, so I want to try make the "smart" cable, but should I use:
> http://www.networkupstools.org/ups-protocols/megatec.html (cable mentioned by you - above 3 wire cable)?
If I am reading the code correctly, it does no...
2015 Nov 20
0
Contact-closure UPS
On Nov 19, 2015, at 12:04 PM, R?bert SZAKSZ <robert at szaksz.eu> wrote:
> output(nutdrv_qx cmd upsdrvctl -DDD start)
>
> Network UPS Tools - UPS driver controller 2.7.3
> 0.000000
> If you're not a NUT core developer, chances are that you're told to enable debugging
> to see why a driver isn't working...
2015 Nov 21
0
Contact-closure UPS
On Nov 20, 2015, at 12:17 PM, R?bert SZAKSZ <robert at szaksz.eu> wrote:
>
> No progress has been made:
>
> cable is UPS - PC
> 6 - 3
> 7 - 5
> 9 - 2
>
Maybe pins 4 and 7 (ground) both need to be connected on the UPS side?
> for ./blazer_ser -DDDDD -a infosec
> 0.000000 send_to_all: SETINFO driv...
2015 Nov 21
0
Contact-closure UPS
> On Nov 21, 2015, at 2:43 AM, R?bert SZAKSZ <robert at szaksz.eu> wrote:
>
> I mesured it and on DC and it shows 0 V (zero V).
> May be the information (pls. see attachment) that UPS PIN1 should bee keept HI is mandatory. Should I connect it to PC PIN4 DTR?
Certainly possible. blazer_ser and nutdrv_qx should set DTR high an...
2015 Nov 21
0
Contact-closure UPS
On Nov 21, 2015, at 8:54 AM, R?bert SZAKSZ <robert at szaksz.eu> wrote:
>> If the UPS is capable of the smart protocol, I still think that is worth trying first. But it's up to you.
> I am not 100% sure that smart protocol is capable, because the only one place where it is mentioned is the picture I sended you.
But your...
2015 Dec 18
0
Contact-closure UPS
On Dec 17, 2015, at 4:51 PM, R?bert SZAKSZ <robert at szaksz.eu> wrote:
>
> Which output PIN on PC side is during whole communication on drivers blazer_ser or nutdrv_qx stable on Logical 0 (+12V)?
> I want make small power source with one resistor (1k) and 3V zenner diode and put on UPS Pin1.
I always forget which signals...
2015 Dec 18
0
Contact-closure UPS
On Dec 17, 2015, at 4:51 PM, R?bert SZAKSZ <robert at szaksz.eu> wrote:
>
> and I find out that on UPS pin 1 should be about 3V.
> If the voltage is not presented the UPS interface doesn't work.
Actually, does it have a maximum voltage listed? Often, vendors will list the minimum threshold voltage, so if it can accept 3...