search for: portonvictor

Displaying 11 results from an estimated 11 matches for "portonvictor".

2014 Nov 26
2
"Communications with UPS advice@localhost lost" when using an other USB device
...lp to eliminate this buggy behavior. Shall we consider this very message as a bug report, or should I report a bug otherwise somewhere? My /etc/nut/ups.conf : maxretry = 3 [advice] driver = blazer_usb port = /dev/ttyS0 vendorid = 0665 productid = 5161 -- Victor Porton - http://portonvictor.org
2014 Nov 26
0
"Communications with UPS advice@localhost lost" when using an other USB device
...very message as a bug report, or should I report a bug otherwise somewhere? > > My /etc/nut/ups.conf : > > maxretry = 3 > > [advice] > ????driver = blazer_usb > ????port = /dev/ttyS0 > ????vendorid = 0665 > ????productid = 5161 > > -- > Victor Porton - http://portonvictor.org > > _______________________________________________ > Nut-upsuser mailing list > Nut-upsuser at lists.alioth.debian.org > http://lists.alioth.debian.org/cgi-bin/mailman/listinfo/nut-upsuser -- Victor Porton - http://portonvictor.org
2014 Nov 26
2
"Communications with UPS advice@localhost lost" when using an other USB device
...wise somewhere? >> >> ?My /etc/nut/ups.conf : >> >> ?maxretry = 3 >> >> ?[advice] >> ?????driver = blazer_usb >> ?????port = /dev/ttyS0 >> ?????vendorid = 0665 >> ?????productid = 5161 >> >> ?-- >> ?Victor Porton - http://portonvictor.org >> >> ?_______________________________________________ >> ?Nut-upsuser mailing list >> ?Nut-upsuser at lists.alioth.debian.org >> ?http://lists.alioth.debian.org/cgi-bin/mailman/listinfo/nut-upsuser > > -- > Victor Porton - http://portonvictor.org > &gt...
2014 Dec 01
2
Do I need to configure times and percents?
...-u <username> set username for command authentication -p <password> set password for command authentication <ups> UPS identifier - <upsname>[@<hostname>[:<port>]] Call without -s to show all possible read/write variables. -- Victor Porton - http://portonvictor.org
2014 Nov 29
2
Do I need to configure times and percents?
...s and the protocol, do I need to adjust time and/or percentage parameters, to be sure my computer will be turned off automatically after a reasonable time after failing electricity? My UPS is Advice PRS850. If I need to adjust the parameters, please explain the details. -- Victor Porton - http://portonvictor.org
2014 Dec 01
2
Do I need to configure times and percents?
...input.voltage: 234.9 input.voltage.fault: 234.9 input.voltage.nominal: 230 output.voltage: 234.9 ups.beeper.status: enabled ups.delay.shutdown: 30 ups.delay.start: 180 ups.load: 18 ups.productid: 5161 ups.status: OL ups.type: offline / line interactive ups.vendorid: 0665 -- Victor Porton - http://portonvictor.org
2014 Dec 01
0
Do I need to configure times and percents?
On Dec 1, 2014, at 4:11 AM, Victor Porton <porton at narod.ru> wrote: > battery.voltage: 13.70 > battery.voltage.high: 13.00 > battery.voltage.low: 10.40 These are the voltage thresholds for the UPS, so theoretically the UPS will send the LB signal when the battery voltage goes lower than 10.40 Volts. Also, if battery.charge works, you can use "ignorelb" if you want to
2014 Dec 01
0
Do I need to configure times and percents?
On Dec 1, 2014, at 9:19 AM, Victor Porton <porton at narod.ru> wrote: > 01.12.2014, 14:50, "Charles Lepple" <clepple at gmail.com>: >> Does "upsrw -l advice" show anything? > > $ upsrw -l advice > upsrw: invalid option -- 'l' I suppose I should read the documentation every once in a while :-) "upsrw advice" I was thinking of
2014 Dec 01
1
Do I need to configure times and percents?
...upsrw -l advice >> ?upsrw: invalid option -- 'l' > > I suppose I should read the documentation every once in a while :-) > > "upsrw advice" "upsrw advice" outputs nothing. > I was thinking of "upscmd -l advice". -- Victor Porton - http://portonvictor.org
2014 Dec 01
0
Do I need to configure times and percents?
On Nov 29, 2014, at 7:32 AM, Victor Porton <porton at narod.ru> wrote: > On Debian Linux jessie: > > After buying an UPS and installation of nut-server and nut-client at my PC and configuring the ports and the protocol, do I need to adjust time and/or percentage parameters, to be sure my computer will be turned off automatically after a reasonable time after failing electricity?
2014 Nov 26
0
"Communications with UPS advice@localhost lost" when using an other USB device
On Nov 25, 2014, at 8:17 PM, Victor Porton <porton at narod.ru> wrote: > Well, also below in dmesg: > > [ 190.249219] usb 3-1.3: usbfs: USBDEVFS_CONTROL failed cmd blazer_usb rqt 33 rq 9 len 8 ret -110 -110 is -ETIMEDOUT. > 26.11.2014, 03:05, "Victor Porton" <porton at narod.ru>: >> A fragment of dmesg output (here idVendor=0665, idProduct=5161 is the