2006 Jul 11
2
notifycmd problem
hello,
i've got a problem with the notifycmd
here is a part of my upsmon.conf :
NOTIFYCMD /usr/local/ups/bin/nut_notify
NOTIFYMSG ONLINE "UPS %s is getting line power"
NOTIFYMSG ONBATT "UPS %s is on battery"
NOTIFYMSG REPLBATT "The UPS %s battery is bad and needs to be replaced"
NOTIFYMSG LOWBATT "UPS %s is being shutdown by the master"
NOTIFYMSG FSD "Someone pulled the plug on %s&...
2010 Jan 09
2
problem with mailing (nut 2.4.1 and a powermust650 -> megatec_usb)
...ept for the mailing
when something happens. My upsmon looks like this:
MONITOR powermust650 at localhost 1 local controller master
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
NOTIFYCMD /root/upsmailer
POLLFREQ 10
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 45
POWERDOWNFLAG /etc/killpower
NOTIFYMSG ONLINE "UPS %s on line power"
NOTIFYMSG ONBATT "UPS %s on battery"
NOTIFYMSG LOWBATT "UPS %s battery is low"
NOTIFYMSG FSD "UPS %s: forced shutdown in progress"
NOTIFYMSG COMMOK "Communications with UPS %s established...
2017 Jun 09
2
Apple Mac slave
...from the NAS and connecting it (if possible) to the Mac. After setting to
80 and a power off-on cycle is the value 80 or 10?
> 3. Users from the NAS are warned, not yet the Mac user.? Only when
> executing automatic power-fail shutdown.?
In upsmon.conf on the Mac, what are the values of NOTIFYMSG ONBATT and
NOTIFYFLAG ONBATT? Does program wall work on the Mac? It fails on a lot
of Linux boxes with graphical interfaces - to get a message to the user,
you have to use notify-send, which means setting up upssched.
> 7. No they didn?t restart. I know there is a setting on the NAS to
>...
2017 Jun 09
0
Apple Mac slave
On Fri, 9 Jun 2017, Robbie van der Walle wrote:
> # NOTIFYMSG - change messages sent by upsmon when certain events occur
> #
> # You can change the default messages to something else if you like.
> #
> # NOTIFYMSG <notify type> "message"
> #
> # NOTIFYMSG ONLINE "UPS %s on line power"
> # NOTIFYMSG ONBATT "U...
2012 Jan 28
2
No shutdown on empty battery
...LanSafe III, so the failure did get reported correctly. However,
the nut did not shut down the system.
My upsmon.conf is:
MONITOR upsb1 at localhost 1 upsmon suprpass master
MINSUPPLIES 1
SHUTDOWNCMD "init 0"
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG /etc/killpower
NOTIFYMSG ONLINE "UPS %s on line power"
NOTIFYMSG ONBATT "UPS %s on battery"
NOTIFYMSG LOWBATT "UPS %s battery is low"
NOTIFYMSG FSD "UPS %s: forced shutdown in progress"
NOTIFYMSG COMMOK "Communications with UPS %s established...
2015 Oct 27
0
The system doesn't shutdown
...lhost 1 upsmaster ********* master
MINSUPPLIES 1
SHUTDOWNCMD "logger -t upsmon.conf \"SHUTDOWNCMD calling /sbin/shutdown to shut down system\" ; /sbin/shutdown -h +0"
NOTIFYCMD /usr/sbin/upssched
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG /etc/ups/killpower
NOTIFYMSG ONLINE "UPS %s on line power"
NOTIFYMSG ONBATT "UPS %s on battery"
NOTIFYMSG LOWBATT "UPS %s battery is low"
NOTIFYMSG FSD "UPS %s: forced shutdown in progress"
NOTIFYMSG COMMOK "Communications with UPS %s established"
NOTIFYMSG COMMBAD "Commu...
2020 Apr 28
2
Tripp-Lite SMART1500LCD: powers off with /etc/killpower...then powers back on...
...-------------------------------------------------------------------------
upsmon.conf
RUN_AS_USER root
MONITOR Tripp_Lite at localhost 1 upsmon xxxxxx master
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 5
DEADTIME 15
POWERDOWNFLAG /etc/killpower
#
NOTIFYMSG ONLINE "UPS %s on line power"
NOTIFYMSG ONBATT "UPS %s on battery"
NOTIFYMSG LOWBATT "UPS %s battery is low"
NOTIFYMSG FSD "UPS %s: forced shutdown in progress"
NOTIFYMSG COMMOK "Communications with UPS %s established"
NOTIFYMSG COMMBAD "Commun...
2015 Jul 15
3
No messages
...?I open LXterminal, pull the wall plug, and I get no messagesin the terminal.
?MONITOR Asium_p700 at localhost 1 upsmon jsamcr master?MINSUPPLIES 1?SHUTDOWNCMD "/sbin/shutdown -h +0"?NOTIFYCMD /sbin/upssched?POLLFREQ 5?POLLFREQALERT 5?HOSTSYNC 15?DEADTIME 15?POWERDOWNFLAG /etc/killpower
# NOTIFYMSG - change messages sent by upsmon when certain events occur# You can change the default messages to something else if you like.
?NOTIFYMSG ONLINE "UPS 1 on line power"?NOTIFYMSG ONBATT? "UPS 1 on battery"?NOTIFYMSG LOWBATT? "UPS 1 battery is low"?NOTIFYMSG FSD "UPS...
2023 Jun 11
1
Upssched 100% CPU after updating Debian 12
...calhost 1 upsmaster xxx primary
MONITOR heartbeat at localhost 0 upsmaster xxx primary
MINSUPPLIES 1
NOTIFYCMD /sbin/upssched
SHUTDOWNCMD "/sbin/shutdown -h +0"
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG /etc/killpower
RBWARNTIME 43200
NOCOMMWARNTIME 300
FINALDELAY 5
NOTIFYMSG ONLINE "UPS %s: On line power."
NOTIFYMSG ONBATT "UPS %s: On battery."
NOTIFYMSG LOWBATT "UPS %s: Battery is low."
NOTIFYMSG REPLBATT "UPS %s: Battery needs to be replaced."
NOTIFYMSG FSD "UPS %s: Forced shutdown in progress."
NOTIFYMSG SHUTDOWN &qu...
2017 Jun 08
5
Apple Mac slave
On Thu, 8 Jun 2017, Robbie van der Walle wrote:
> The "upsrw" command contacts upsd, so it sounds like you should be able to add a user to upsd.users on the NAS, and then run something like
> this on the Mac:
>
> ??upsrw -s battery.charge.low=80 -u upsmaster -s sekret UPS at synology
>
> Per?http://networkupstools.org/docs/man/upsd.users.html?,
2012 Apr 11
1
NOTIFYCMD doesn't work from Windows service
...e) everything works fine.
Here is my upsmon.conf:
MONITOR central at 10.35.0.180 1 user password slave
MINSUPPLIES 1
SHUTDOWNCMD "C:\\NUT\\shutdown.bat"
NOTIFYCMD "C:\\NUT\\shutdown.bat"
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG "C:\\killpower"
NOTIFYMSG ONLINE ONLINE
NOTIFYMSG ONBATT ONBATT
NOTIFYMSG LOWBATT LOWBATT
NOTIFYMSG FSD FSD
NOTIFYFLAG ONLINE SYSLOG+WALL+EXEC
NOTIFYFLAG ONBATT SYSLOG+WALL+EXEC
NOTIFYFLAG LOWBATT SYSLOG+WALL+EXEC
NOTIFYFLAG FSD SYSLOG+WALL+EXEC
RBWARNTIME 43200
NOCOMM...
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 04
2
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
...ings upsmon needs:
1. A fall-through <notify type> of "UNKNOWN" so that all status changes,
no matter how wierd, can be caught. Such a catch-all <notify type> would
also have caught the "ALARM" from the old battery.
2. A UPS specific option in the NOTIFYFLAG and NOTIFYMSG declarations as
already provided by the AT declaration in upssched.conf. This would make
it possible to have messages and action specific to a UPS, in a multi-UPS
configuration.
I would like to be able to specify
NOTIFYMSG myups at localhost ONBATT "%s: local UPS on battery"...
2020 Mar 10
2
Fwd: Windows upssched does not work
...ent
--- upsmon.conf
MONITOR ups_1000 at 192.168.3.95 1 <user> <password> slave
MINSUPPLIES 1
SHUTDOWNCMD "C:\\WINDOWS\\system32\\shutdown.exe /t 600 /s /d u:6:11"
NOTIFYCMD C:\\NUT\\notify.cmd
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
POWERDOWNFLAG C:\\NUT\\killpower
NOTIFYMSG ONLINE "UPS %s on line power"
NOTIFYMSG ONBATT "UPS %s on battery"
NOTIFYMSG LOWBATT "UPS %s battery is low"
NOTIFYMSG FSD "UPS %s: forced shutdown in progress"
NOTIFYMSG COMMOK "Communications with UPS %s established"
NOTIFYMSG C...
2016 Apr 26
0
[PATCH] upsmon: Add NOTIFYMSG to env of NOTIFYCMD
...smon.c 2016-04-25 20:17:44.392925130 -0600
+++ upsmon.c+ 2016-04-25 20:18:21.512871526 -0600
@@ -151,6 +151,7 @@
setenv("UPSNAME", "", 1);
setenv("NOTIFYTYPE", ntype, 1);
+ setenv("NOTIFYMSG", notice, 1);
if (system(exec) == -1) {
upslog_with_errno(LOG_ERR, "%s", __func__);
}
2013 Mar 08
0
HowTo use upssched right.
Hi,
I want to test the events off my UPS.
I define
In upsmon.conf:
RUN_AS_USER root
NOTIFYCMD /sbin/upssched
NOTIFYMSG ONLINE "UPS %s on line power"
NOTIFYMSG ONBATT "UPS %s on battery"
NOTIFYMSG LOWBATT "UPS %s battery is low"
# NOTIFYMSG FSD "UPS %s: forced shutdown in progress"
NOTIFYMSG COMMOK "Communications with UPS %s established"
NOTIFYMSG COMMBAD "Comm...
2017 Oct 18
2
debian 8 "jessie" nut 2.7.2 slaves not shutting down
OS name and version,
MASTER SYSTEM has three APC smart UPS 3000 UPS connected via USB
debian 8 "jessie" Linux pdxvhtst01 3.16.0-4-amd64 #1 SMP Debian 3.16.43-2+deb8u5 (2017-09-19) x86_64 GNU/Linux
SLAVE SYSTEMS monitoring MASTER via IP
debian 8 "jessie" Linux geaaetst01
2015 Oct 27
2
The system doesn't shutdown
Yes, that was the power off test. However the upssched-cmd script gave
absolutely no signs of activity. Even it's logger lines don't show up in
journalctl. No any permission error messages - nothing. Only the 2 messages
from upsmon - on battery and then on line power.
Here is the nut-report:
http://www.filehosting.org/file/details/518300/NUT.report
---
George Anchev
On Tue, Oct 27,
2017 Oct 18
2
debian 8 "jessie" nut 2.7.2 slaves not shutting down
....conf
MONITOR TOPAPC at localhost 1 upsmon pass master
MONITOR MIDAPC at localhost 1 upsmon pass master
MONITOR BOTAPC at localhost 1 upsmon pass master
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h now"
NOTIFYCMD /bin/notifynetadmins
POLLFREQ 5
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 15
NOTIFYMSG ONLINE "UPS %s on line power"
NOTIFYMSG ONBATT "UPS %s on battery"
NOTIFYMSG LOWBATT "UPS %s battery is low"
NOTIFYMSG FSD "UPS %s: forced shutdown in progress"
NOTIFYMSG COMMOK "Communications with UPS %s established&...
2023 Jun 10
1
Fopen upsmon.pid - no such file or directory - Nut 2.8.0 built from source
..._AS_USER root
MONITOR ups at localhost 1 upsmonitor ****m**** primery
MONITOR heartbeat at localhost 0 heartbeat ****m****
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +2"
NOTIFYCMD /etc/nut/upssched-cmd
POLLFREQ 10
POLLFREQALERT 5
HOSTSYNC 15
DEADTIME 30
POWERDOWNFLAG /etc/killpower
NOTIFYMSG ONLINE "online"
NOTIFYMSG ONBATT "onbatt"
NOTIFYMSG LOWBATT "lowbatt"
NOTIFYMSG FSD "fsd"
NOTIFYMSG COMMOK "commok"
NOTIFYMSG COMMBAD "commbad"
NOTIFYMSG SHUTDOWN "shutdown"
NOTIFYM...
2020 Jun 21
2
Server did not shut down