Displaying 7 results from an estimated 7 matches for "gxt4".
Did you mean:
ext4
2024 Sep 22
1
[HCL] Liebert GXT4-1500RT120 supported by usbhid-ups
Liebert GXT4-1500RT120
upsc output:
battery.charge: 100
battery.charge.low: 30
battery.charge.warning: 40
battery.type: PbAcbattery.voltage: 54
battery.voltage.nominal: 48
device.mfr: Emerson Network Power
device.model: Liebert GXT4
device.serial: 1710600384AFBA3
device.type: ups
driver.debug: 0
driver.flag.a...
2017 Jun 02
2
Fwd: Emerson Liebert GXT4
Hello,
we have a Emerson Liebert GXT4, that we like to connect to our servers
to shut them down if there is a power failure (which happens quite often
in our area).
I couldn't get the GXT4 working with usbhid-ups driver. So I need some
advise to continue to get this device working. The GXT3 seems to be
working ok with NUT (http://...
2017 Jun 03
0
Fwd: Emerson Liebert GXT4
On Jun 2, 2017, at 8:28 AM, zefanjas <nut at zefanjas.de> wrote:
> I couldn't get the GXT4 working with usbhid-ups driver. So I need some
> advise to continue to get this device working. The GXT3 seems to be
> working ok with NUT (http://networkupstools.org/ddl/Liebert/GXT3.html).
>
> Here is my ups.conf
>
> [ups]
> driver = usbhid-ups
> port = usb-0000:00:1d...
2017 Jun 05
2
Fwd: Emerson Liebert GXT4
...quot;upscmd -l ups" output, we can update the DDL.
#upsc ups
Init SSL without certificate database
battery.charge: 100
battery.charge.low: 20
battery.charge.warning: 0
battery.type: PbAc
battery.voltage: 1.0
battery.voltage.nominal: 0.0
device.mfr: Emerson Network Power
device.model: Liebert GXT4
device.serial: 1607000058AFC23
device.type: ups
driver.name: usbhid-ups
driver.parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.parameter.productid: 0000
driver.version: 2.7.2
driver.version.data: Belkin HID 0.16
driver.version.internal: 0.38
ups.mfr: Emers...
2017 Apr 17
1
New UPS information - Liebert GXT4 via US
Hi UPS List members,
I have purchased a number of Emerson Power / Liebert GXT4 UPS units.
I have these working correctly under nut, but limited detsils are being reported.
I am happy to supply information on the USB communications to improve the reported details
I can use WireShark to capture the comms between the supplied Windows GUI tool and the UPS
Please advise the...
2017 Jun 05
0
Fwd: Emerson Liebert GXT4
On Jun 4, 2017, at 8:32 PM, zefanjas <nut at zefanjas.de> wrote:
>
> Hi,
>
> thanks for your helpful reply. I've added the productid in the ups.conf
> and it seems to work (better) now.
>
>
>> After starting the driver and upsd, what does "upsc ups" return? If you can also include "upsrw ups" and "upscmd -l ups" output, we can
2017 Jun 05
1
Fwd: Emerson Liebert GXT4
Hi,
>> #upsc ups
>>
>> Init SSL without certificate database
>> battery.charge: 100
>> battery.charge.low: 20
>> battery.charge.warning: 0
>> battery.type: PbAc
>> battery.voltage: 1.0
>> battery.voltage.nominal: 0.0
>
> Similar to Mike's report on the CPS UPS, the HID descriptor for this device is buggy:
>
> Logical