Displaying 20 results from an estimated 41 matches for "configactivepow".
Did you mean:
configactivepower
2007 Aug 11
1
apc-hid.c: watts_to_av_conversion
...without knowing the phase relation between RMS voltage and -current.
Could it be that for this particular UPS this works out to be correct by
coincidence? Now that we have "ups.realpower.nominal", I think we should
change line 215
{ "ups.power.nominal", 0, 0, "UPS.Output.ConfigActivePower", NULL, "%s",
HU_FLAG_OK, watts_to_av_conversion }, /* CyberPower */
to
{ "ups.realpower.nominal", 0, 0, "UPS.Output.ConfigActivePower", NULL,
"%.0f", HU_FLAG_OK, NULL }, /* CyberPower */
Chances are, it also supports
{ "ups.power.nominal&qu...
2006 Aug 07
0
Re: your Tripp-Lite AVR550U
...lue: 100.000000
> Path: UPS.PowerSummary.PresentStatus.ShutdownImminent, Type: Input,
> Value: 0.000000
> Can't find object UPS.PowerSummary.PresentStatus.008400d0
> Path: UPS.PowerSummary.PresentStatus.008400d0, Type: Input
> Can't find object UPS.PowerSummary.PresentStatus.ConfigActivePower
> Path: UPS.PowerSummary.PresentStatus.ConfigActivePower, Type: Input
> Can't find object UPS.PowerSummary.PresentStatus.ConfigPercentLoad
> Path: UPS.PowerSummary.PresentStatus.ConfigPercentLoad, Type: Input
> Can't find object UPS.PowerSummary.PresentStatus.0084004b
> Pat...
2006 Jul 08
1
Re: your Tripp-Lite AVR550U
...lue: 100.000000
> Path: UPS.PowerSummary.PresentStatus.ShutdownImminent, Type: Input,
> Value: 0.000000
> Can't find object UPS.PowerSummary.PresentStatus.008400d0
> Path: UPS.PowerSummary.PresentStatus.008400d0, Type: Input
> Can't find object UPS.PowerSummary.PresentStatus.ConfigActivePower
> Path: UPS.PowerSummary.PresentStatus.ConfigActivePower, Type: Input
> Can't find object UPS.PowerSummary.PresentStatus.ConfigPercentLoad
> Path: UPS.PowerSummary.PresentStatus.ConfigPercentLoad, Type: Input
> Can't find object UPS.PowerSummary.PresentStatus.0084004b
> Pat...
2006 Sep 22
1
Ablerex 625L USB version
...alue: 0.000000
Path: 00860004.Flow.FlowID, Type: Feature, Value: 0.000000
Path: 00860004.Flow.ConfigVoltage, Type: Feature, Value: 0.000000
Path: 00860004.Flow.ConfigFrequency, Type: Feature, Value: 0.000000
Path: 00860004.Flow.ConfigApparentPower, Type: Feature, Value: 0.000000
Path: 00860004.Flow.ConfigActivePower, Type: Feature, Value: 0.000000
Path: 00860004.Flow.DelayBeforeStartup, Type: Feature, Value: 0.000000
Path: 00860004.Flow.DelayBeforeShutdown, Type: Feature, Value: 0.000000
Path: 00860004.BatterySystem.BatterySystemID, Type: Feature, Value:
0.000000
Path: 00860004.BatterySystem.PresentStatus.U...
2006 Nov 11
1
Help with newhidups subdriver for Dynex UPS
...ath: UPS.Output.DelayBeforeShutdown, Type: Feature, Value: -1.000000
Path: UPS.Output.DelayBeforeStartup, Type: Feature, Value: 0.000000
Path: UPS.Output.Boost, Type: Feature, Value: 0.000000
Path: UPS.Output.Overload, Type: Feature, Value: 0.000000
Path: UPS.Output., Type: Feature
Path: UPS.Output.ConfigActivePower, Type: Feature, Value: 450.000000
Can't find object UPS.Battery.ConfigVoltage
Can't find object UPS.Battery.Temperature
Can't find object UPS.Battery.ManufacturerDate
Can't find object UPS.PowerSummary.APCBattReplaceDate
Can't find object UPS.Battery.APCBattReplaceDate
Can'...
2011 Dec 28
0
1350PFCLCD Boost and Overload info
...oad, Type: Feature, ReportID: 0x17, Offset: 1, Size: 1, Value: 0.000000
In the output from the driver?
The first one says if the UPS is using AVR (active voltage regulation) to
increase the voltage. The official driver calls it "Line Interaction".
Can you multiply:
Path: UPS.Output.ConfigActivePower, Type: Feature, ReportID: 0x18, Offset: 0, Size: 16, Value: 810.000000
With
Path: UPS.Output.PercentLoad, Type: Feature, ReportID: 0x13, Offset: 0, Size: 8, Value: 26.000000
To show load in watts?
And finally I have:
Path: UPS.Output.Voltage, Type: Feature, ReportID: 0x12, Offset: 0, Siz...
2008 Apr 01
1
Incorrect battery status on MGE Pulsar M 3000
...igFrequency, Type: Feature, ReportID: 0x14, Offset: 0,
Size: 8, Value: 50.000000
Path: UPS.Flow.[1].ConfigVoltage, Type: Feature, ReportID: 0x15, Offset: 0,
Size: 8, Value: 230.000000
Path: UPS.Flow.[1].FlowID, Type: Feature, ReportID: 0x0b, Offset: 0, Size: 8,
Value: 1.000000
Path: UPS.Flow.[4].ConfigActivePower, Type: Feature, ReportID: 0x74, Offset:
0, Size: 16, Value: 2700.000000
Path: UPS.Flow.[4].ConfigApparentPower, Type: Feature, ReportID: 0x75, Offset:
0, Size: 16, Value: 3000.000000
Path: UPS.Flow.[4].ConfigFrequency, Type: Feature, ReportID: 0x36, Offset: 0,
Size: 8, Value: 50.000000
Path: U...
2020 Oct 23
2
Nut-upsuser Digest, Vol 184, Issue 8
...foreStartup, Type: Feature, ReportID:
0x16, Offset: 0, Size: 16, Value: -60
0.069506 Path: UPS.Output.Boost, Type: Feature, ReportID: 0x17, Offset:
0, Size: 1, Value: 0
0.070068 Path: UPS.Output.Overload, Type: Feature, ReportID: 0x17,
Offset: 1, Size: 1, Value: 0
0.072352 Path: UPS.Output.ConfigActivePower, Type: Feature, ReportID:
0x18, Offset: 0, Size: 16, Value: 810
0.075028 Path: UPS.Output.ConfigApparentPower, Type: Feature, ReportID:
0x19, Offset: 0, Size: 16, Value: 1350
0.077881 Path: UPS.Output.ff010043, Type: Feature, ReportID: 0x1a,
Offset: 0, Size: 8, Value: 1
0.078350 Path: UP...
2018 Sep 01
0
Adding drivers to NUT?
...Transfer
- battery.charge.warning / UPS.PowerSummary.WarningCapacityLimit
- battery.charge.low / UPS.PowerSummary.RemainingCapacityLimit
2. Do the following ones return punctual data, or only the nominal
value? If the latter, do they change, or they are static?
- ups.realpower / UPS.Output.ConfigActivePower
- ups.realpower / UPS.Flow.ConfigApparentPower
3. Are the following ones static?
- input.voltage.nominal / UPS.Input.ConfigVoltage
- input.voltage.nominal / UPS.Flow.ConfigVoltage
- battery.voltage.nominal / UPS.PowerSummary.ConfigVoltage
- battery.voltage.nominal / UPS.BatterySyst...
2007 Jan 26
1
newhidups output for Geek Squad GS1285U
...th: UPS.Output.DelayBeforeShutdown, Type: Feature, Value: -60.000000
Path: UPS.Output.DelayBeforeStartup, Type: Feature, Value: 0.000000
Path: UPS.Output.Boost, Type: Feature, Value: 0.000000
Path: UPS.Output.Overload, Type: Feature, Value: 0.000000
Path: UPS.Output., Type: Feature
Path: UPS.Output.ConfigActivePower, Type: Feature, Value: 238.000000
Can't find object UPS.Battery.ConfigVoltage
Can't find object UPS.Battery.Temperature
Can't find object UPS.Battery.ManufacturerDate
Can't find object UPS.PowerSummary.APCBattReplaceDate
Can't find object UPS.Battery.APCBattReplaceDate
Can'...
2006 Feb 10
1
newhidups capture - Atlantis-Land HID UPS
Hello Charles!
As promised, I just checked out the CVS and recompiled everything. In
the attached .txt is what is coming out from my UPS. I am wondering
about all those zeroes.
Also, this morning I plan to connect the UPS to a Win box running the
monitoring program supplied with the UPS (UPSilon2000) and a USB sniffer
program. If you have any suggestions on what to look for in the data,
2020 Oct 21
1
Can't get CyberPower UPS to work with Raspberry Pi 4
...foreStartup, Type: Feature, ReportID:
0x16, Offset: 0, Size: 16, Value: -60
0.039904 Path: UPS.Output.Boost, Type: Feature, ReportID: 0x17, Offset:
0, Size: 1, Value: 0
0.039941 Path: UPS.Output.Overload, Type: Feature, ReportID: 0x17,
Offset: 1, Size: 1, Value: 0
0.040657 Path: UPS.Output.ConfigActivePower, Type: Feature, ReportID:
0x18, Offset: 0, Size: 16, Value: 810
0.041407 Path: UPS.Output.ConfigApparentPower, Type: Feature, ReportID:
0x19, Offset: 0, Size: 16, Value: 1350
0.042160 Path: UPS.Output.ff010043, Type: Feature, ReportID: 0x1a,
Offset: 0, Size: 8, Value: 1
0.042202 Path: UP...
2019 Jun 11
2
UPS shuts down on NUT boot with low battery [APS Back-UPS RS 550G]
..., Size: 16, Value: -1
> 0.078529 Path: UPS.PowerConverter.PercentLoad, Type: Feature, ReportID: 0x50, Offset: 0, Size: 8, Value: 26
> 0.079478 Path: UPS.PowerConverter.ff860024, Type: Feature, ReportID: 0x51, Offset: 0, Size: 8, Value: 226
> 0.080454 Path: UPS.PowerConverter.ConfigActivePower, Type: Feature, ReportID: 0x52, Offset: 0, Size: 16, Value: 330
> 0.081163 Path: UPS.ff860001.ff860023, Type: Feature, ReportID: 0x60, Offset: 0, Size: 16, Value: 0
> 0.081788 Path: UPS.ff860001.ff860026, Type: Feature, ReportID: 0x61, Offset: 0, Size: 8, Value: 138
> 0.0829...
2008 Feb 24
2
usbhid-ups using wrong value for battery voltage for Pulsar Evolution 500?
...0x27,
Offset: 0, Size: 16, Value: 120.000000
Path: UPS.PowerSummary.Voltage, Type: Feature, ReportID: 0x2b, Offset:
16, Size: 16, Value: 119.000000
And some flow information:
Path: UPS.Flow.[4].ConfigFrequency, Type: Feature, ReportID: 0x14,
Offset: 8, Size: 8, Value: 60.000000
Path: UPS.Flow.[4].ConfigActivePower, Type: Feature, ReportID: 0x14,
Offset: 16, Size: 16, Value: 350.000000
Path: UPS.Flow.[4].ConfigApparentPower, Type: Feature, ReportID: 0x14,
Offset: 32, Size: 16, Value: 500.000000
Path: UPS.Flow.[4].ConfigCurrent, Type: Feature, ReportID: 0x14,
Offset: 48, Size: 16, Value: 4.160000
Path: UPS.F...
2018 Sep 03
0
Adding drivers to NUT?
...PS.PowerSummary.WarningCapacityLimit
> > - battery.charge.low / UPS.PowerSummary.RemainingCapacityLimit
> > 2. Do the following ones return punctual data, or only the nominal
> > value? If the latter, do they change, or they are static?
> > - ups.realpower / UPS.Output.ConfigActivePower
> > - ups.realpower / UPS.Flow.ConfigApparentPower
> > 3. Are the following ones static?
> > - input.voltage.nominal / UPS.Input.ConfigVoltage
> > - input.voltage.nominal / UPS.Flow.ConfigVoltage
> > - battery.voltage.nominal / UPS.PowerSummary.ConfigVolt...
2014 Mar 24
2
Incorrect Values From usbhid-ups
...pe: Feature,
ReportID: 0x16, Offset: 0, Size: 16, Value: -60
0.264214 Path: UPS.Output.Boost, Type: Feature, ReportID: 0x17,
Offset: 0, Size: 1, Value: 0
0.264223 Path: UPS.Output.Overload, Type: Feature, ReportID:
0x17, Offset: 1, Size: 1, Value: 0
0.264306 Path: UPS.Output.ConfigActivePower, Type: Feature,
ReportID: 0x18, Offset: 0, Size: 16, Value: 900
0.264388 Path: UPS.Output.ff010043, Type: Feature, ReportID:
0x1a, Offset: 0, Size: 8, Value: 1
0.264396 Path: UPS.Output.ff010043, Type: Input, ReportID:
0x1a, Offset: 0, Size: 8, Value: 1
0.264417 Report des...
2019 Jun 11
0
UPS shuts down on NUT boot with low battery [APS Back-UPS RS 550G]
...6, Value: -1
>> 0.078529 Path: UPS.PowerConverter.PercentLoad, Type: Feature, ReportID: 0x50, Offset: 0, Size: 8, Value: 26
>> 0.079478 Path: UPS.PowerConverter.ff860024, Type: Feature, ReportID: 0x51, Offset: 0, Size: 8, Value: 226
>> 0.080454 Path: UPS.PowerConverter.ConfigActivePower, Type: Feature, ReportID: 0x52, Offset: 0, Size: 16, Value: 330
>> 0.081163 Path: UPS.ff860001.ff860023, Type: Feature, ReportID: 0x60, Offset: 0, Size: 16, Value: 0
>> 0.081788 Path: UPS.ff860001.ff860026, Type: Feature, ReportID: 0x61, Offset: 0, Size: 8, Value: 138
>>...
2013 Aug 07
1
FreeNAS , NUT and APC BK500EI problem.
...AlarmControl,
Type: Feature, ReportID: 0x14, Offset: 0, Size: 8, Value: 2
1.144427
Report[buf]: (3 bytes) => 35 2e 42
1.144433 Path: UPS.ManufacturerDate,
Type: Feature, ReportID: 0x35, Offset: 0, Size: 16, Value: 16942
1.144471 Report[buf]: (3 bytes) => 52 2c 01
1.144479 Path:
UPS.Output.ConfigActivePower, Type: Feature, ReportID: 0x52, Offset: 0,
Size: 16, Value: 300
1.144501 Report[buf]: (3 bytes) => 07 0c 00
1.144507 Path: UPS.PowerSummary.PresentStatus.ACPresent, Type: Feature,
ReportID: 0x07, Offset: 2, Size: 1, Value: 1
1.144533 Report[buf]: (3
bytes) => 07 0c 00
1.144541 Path:
UPS...
2005 Dec 07
5
Atlantis-Land UPS with Cypress CY7C63723 chip (cypress_m8 driver) support
Hello everybody!
I am trying to get an Atlantis-Land OnePower Line Interactive S1501
UPS (actually it is made by Ablerex) to talt to my Linux box through its
USB port (no more RS-232...), either using the supplied program
(UPSilon2000, works under Win and Linux) or whatever else.
The UPSilon2000 program apparently works OK *if* it can talk to the
UPS via a serial port; since my UPS has
2005 Dec 07
5
Atlantis-Land UPS with Cypress CY7C63723 chip (cypress_m8 driver) support
Hello everybody!
I am trying to get an Atlantis-Land OnePower Line Interactive S1501
UPS (actually it is made by Ablerex) to talt to my Linux box through its
USB port (no more RS-232...), either using the supplied program
(UPSilon2000, works under Win and Linux) or whatever else.
The UPSilon2000 program apparently works OK *if* it can talk to the
UPS via a serial port; since my UPS has