search for: blazer_ser

Displaying 20 results from an estimated 124 matches for "blazer_ser".

2014 Apr 29
1
blazer_ser battery.high / battery.low
Hello list, we've got a PowerWalker VI 1000E/RT LCD UPS and like to use it with NUT using the blazer_ser driver. For the blazer_ser driver to display percentage, one has to add battery.voltage.high and battery.voltage.low voltages to the ups config. Here's what I received from the powerwalker customer service: Battery-Low Voltage: 21.6VDC Battery Shutdown: 19.2VDC Now my questions: 1. should the...
2012 Nov 17
1
[HCL] Aviem Power RT 1000-3000VA supported by blazer_ser
Manufacturer: Aviem Power RT 1000-3000VA Description: Rack/Tower Intelligent Online LCD UPS. connected with serial cable. #upsc battery.voltage: 24.96 battery.voltage.low: 21.5 battery.voltage.nominal: 24.0 beeper.status: enabled device.mfr: device.model: device.type: ups driver.name: blazer_ser driver.parameter.pollinterval: 2 driver.parameter.port: /dev/ttyUSB1 driver.version: 2.6.3 driver.version.internal: 1.51 input.current.nominal: 5.0 input.frequency: 50.0 input.frequency.nominal: 50 input.voltage: 224.3 input.voltage.fault: 0.0 input.voltage.nominal: 220 output.voltage: 230.7 ups.de...
2015 Feb 10
2
[HCL] Artronic art 1000 bl supported by blazer_ser
Hi Artronic art 1000 bl is supported partially by blazer_ser: battery.voltage: 13.40battery.voltage.nominal: 12.0 beeper.status: enabled device.type: ups driver.name: blazer_ser driver.parameter.pollinterval: 2 driver.parameter.port: /dev/ttyS0 driver.version: 2.6.3 driver.version.internal: 1.51 input.current.nominal: 4.0 input.frequency: 50.1 input.frequenc...
2014 May 04
1
blazer_ser: UPS behind seriell ethernet converter
Hi, I'm trying to get an Effekta UPS (works directly with blazer_ser) working behind a seriell to ethernet converter (Brainboxes ES-246). I've set the converter to 2400 baud, 8N1, no flow control. On the linux side I started socat and blazer_ser. All I got are timeouts after 12 seconds. I can see network traffic with tcpdump but I've no idea what to do to g...
2011 Apr 28
1
Problem with blazer_ser/megatec when upgrading to 2.6.0 from 2.4
Hello First things first, thanks for great work with NUT. For years I used Informer compact 3kVA UPS http://www.informups.com/informer_compact.html with nut/megatec serial driver, but it stopped working when I switched to blazer_ser with 2.6.0 upgrade. I'm using 2.6.0 on gentoo. Blazer_ser seems to connect with UPS, but upsmon reports driver not connected. uname -a Linux localhost 2.6.36-gentoo-r7 #3 SMP Tue Feb 8 18:39:54 CET 2011 x86_64 Intel(R) Core(TM)2 CPU 6400 @ 2.13GHz GenuineIntel GNU/Linux Configuration: cat up...
2014 Jun 02
2
blazer_ser battery.high / battery.low
Hi, thanks for the reply. On 2014-05-29 05:21, Charles Lepple wrote: >> Now my questions: >> 1. should the blazer_ser's high voltage be the voltage during charging >> or right after I've unplugged it from the mains? > sounds like during charging (or more accurately, during float charging at the end of the cycle): > > http://www.networkupstools.org/docs/man/blazer.html#_extra_arguments Are y...
2015 Feb 25
0
[HCL] Artronic art 1000 bl supported by blazer_ser
On Feb 10, 2015, at 5:24 PM, Miroslav Todorov <miro0218 at yahoo.com> wrote: > Hi Artronic art 1000 bl is supported partially by blazer_ser: > When you say "partially supported", what is not supported? Are any of the values incorrect? -- Charles Lepple clepple at gmail
2018 Jan 25
0
HCL Zinto 800 supported by blazer_ser and blazer_usb
Hi, today I have tested the Zinto 800 with blazer_ser and blazer_usb on Citrix Server 7.0. Both works fine. upsc-Output (blazer_ser): battery.charge: 94 battery.voltage: 25.70 battery.voltage.high: 26.00 battery.voltage.low: 20.80 battery.voltage.nominal: 24.0 device.mfr: device.model: ZINTO 800 device.type: ups driver.name: blazer_ser driver.paramet...
2014 Jun 02
0
blazer_ser battery.high / battery.low
On Jun 2, 2014, at 12:25 PM, Andreas Lausch / TBT wrote: > > Hi, > > thanks for the reply. > > On 2014-05-29 05:21, Charles Lepple wrote: >>> Now my questions: >>> 1. should the blazer_ser's high voltage be the voltage during charging >>> or right after I've unplugged it from the mains? >> sounds like during charging (or more accurately, during float charging at the end of the cycle): >> >> http://www.networkupstools.org/docs/man/blazer.html#_extra...
2012 Jun 09
3
[HCL] REDi/Centralion Blazer 600 VA (BLAZER600c) supported by blazer_ser
The REDi Blazer 600VA (BLAZER600c) UPS found here [ro_RO]: http://www.emag.ro/ups-redi-blazer-600va-blazer600c/pd/EX5X2BBBM/ which is actually a Centralion Blazer 600VA [en_TW]: http://www.centralion.com/html/product/back-Product-ups-blazer400.htm works with the blazer_ser driver ----------shell output---------- # upsrw ups # upscmd -l ups Instant commands supported on UPS [ups]: beeper.toggle - Toggle the UPS beeper load.off - Turn off the load immediately load.on - Turn on the load immediately shutdown.return - Turn off the load and return when power is back shut...
2013 May 11
1
blazer_ser problem on windows NUT 2.6.5-3780M
...blem with, is connected to Windows 7 64bit, and I used the straight MSI installed from the website named NUT-Installer-2.6.5-4.msi Took me a while to find a way to get it to work, but it is ugly for now. Just starting up the service results in a NUT not working at all, and I tracked it down to the blazer_ser driver not finding the UPS. Debugging shows some problem with the communication on my serial-usb port. What I have found is, that it doesn't work until I add 4x debug flags. eg: -DDDD Here is a copy of my ups.conf: [myups] driver = blazer_ser port = com6 desc = "Proline UPS" Here...
2019 Aug 06
4
Monitor UPS Brand SMS
Hi Users NUT, I want monitor a UPS of brand SMS (Sinus Double 8 KVA) using a raspberry-pi. In compatibility list, is listed to use the blazer_ser driver. I use a USB adapter to RS-232 conected in to the No-Breake. Follow the comands e confs. root at rasp:/home/pi# lsusb *Bus 001 Device 004: ID 067b:2303 Prolific Technology, Inc. PL2303 Serial Port* Bus 001 Device 003: ID 0424:ec00 Standard Microsystems Corp. SMSC9512/9514 Fast Ethernet Adap...
2013 Aug 11
2
N-Power MEV-3000LT compatibility report and problem
Hello list, first of all, I'd like to report that my UPS N-Power MEV-3000LT (http://www.380v.ru/catalogue/micro-ups/mega-vision , in Russian), which is not in the hardware compatibility list, is mostly supported by the blazer_ser driver. I have very strong grounds to believe that this (and other) N-Power UPS'es are rebranded for Russian and Italian markets from their counterparts produced by Powerbank Electronics Corporation in Taiwan (http://www.powerbank.com.tw/products.php?cat=65&lang=en). I believe they are the...
2011 Sep 19
1
[windows port] blazer_ser issues, select_read() from serial semantics
Hi, I tried using 2.6.1 version for windows with a Megatec-compatible UPS and was surprised to find out it doesn't work at all. The reason for that is blazer_ser using ser_get_buf specifying a buffer large enough to accept any reasonably possible response, setting buflen accordingly. That calls select_read() and it's supposed to wait until something is available and then to read up all the data from port, returning the number of bytes read. But the wind...
2014 Jun 02
2
blazer_ser battery.high / battery.low
...014, at 6:48 PM, Charles Lepple wrote: > On Jun 2, 2014, at 12:25 PM, Andreas Lausch / TBT wrote: > >> >> Hi, >> >> thanks for the reply. >> >> On 2014-05-29 05:21, Charles Lepple wrote: >>>> Now my questions: >>>> 1. should the blazer_ser's high voltage be the voltage during charging >>>> or right after I've unplugged it from the mains? >>> sounds like during charging (or more accurately, during float charging at the end of the cycle): >>> >>> http://www.networkupstools.org/docs/man/bl...
2014 Jun 03
0
blazer_ser battery.high / battery.low
On 2014-06-03 00:58, Charles Lepple wrote: >> I'm pretty sure I wouldn't rely on a charge percentage derived this way ;-) It's nice to see how much time one has left, event if it's not perfectly accurate. >> As mentioned in the other thread about the tripplite_usb driver, apart from having two sets of calibration constants, one for OL and one for OB, there is no
2015 Nov 16
2
Contact-closure UPS
...enericups seems to correspond to a crossed cable as shown in 5.2.1 below: > >http://web.archive.org/web/20100106160328/http://ups.miem.edu.ru/ups_faq5.html > >You might also be able to connect up the TxD and RxD lines, and use the nutdrv_qx (not available until after v2.6.5), megatec or blazer_ser drivers: > >PC UPS Description >== === =========== >2 9 TxD >3 6 RxD >5 7 Ground > >-- >Charles Lepple >clepple at gmail Thank you for your answer, so I want to try make the "smart" cable, but should I use: http://www.networkupstools.org/ups-protocols/megate...
2020 Jul 07
2
New UPS to the DB
Hi, I have an OEM of KStar UDC9101S which is Megatec protocol rs232 capable unit. So I use blazer_ser protocol=megatec /dev/ttyUSB0 with no issue to get NUT running. Please direct me what command should I issue to collect the data in order to include the UPS to device database? P.S. tryed /lib/nut/blazer_ser -DD... but no difference from a regular output has being added by the driver. -----------...
2013 Jun 06
6
Best Axxium Pro, Model Series 0650?
Hi There, We have this rather large-ish floor-standing Best Axxium Pro, Model Series 0650. I tried using both the "bestups" and "blazer_ser" drivers with it, but no go. So before I go any further: *Should* one of these work with it and, if not, do I have any options? (E.g.: Modify a current driver, resuscitate one that was started and abandoned, etc.? I can code.) My test platform was nut 2.4.3-1ubuntu3.2 under Ubuntu 10.04 LTS...
2015 Dec 18
3
Powermust 1400 USB
On 12/17/2015 10:50 PM, hyouko at gmail.com wrote: > Can you try the nutdrv_qx driver with a debug level of 5 (i.e. five D > flags, nutdrv_qx -a upsname -DDDDD )? Attached is a logfile. -------------- next part -------------- A non-text attachment was scrubbed... Name: nutdrv_qx.log Type: text/x-log Size: 5727 bytes Desc: not available URL: