Displaying 20 results from an estimated 550 matches for "beeper".
Did you mean:
deeper
2007 Aug 13
1
instcmd "beeper.off "
While working on the mge-hid subdriver, I wanted to add the
'beeper.mute' command. Unfortunately, the description I intended to use
was used already by the 'beeper.off' instcmd:
CMDDESC beeper.off "Temporarily mute the UPS beeper"
Now of course we could add another instcmd 'beeper.reallyoff', but
instead I would prefer to bite the b...
2012 Sep 19
2
Unable to disable beeper on Powercom Imperial IMP-525AP
Hi ALL,
Powercom Imperial IMP-525AP seems to be fully compatible with NUT.
Unfortunately, I can not disable beeper.
upscmd -u {NUT_USER} -p {NUT_PASSWORD} powercom beeper.toggle
returns *OK*, however, ups.beeper.status=enabled
Thank you,
Sergey
==========
Additional info:
1)
$ upsc powercom
battery.charge: 100
battery.charge.low: 10
battery.charge.warning: 30
battery.date: 2010/01/01
battery.runtime: 2432
ba...
2014 Aug 10
0
Power race? with Eaton 5E and how to auto-mute beeper
On Jul 26, 2014, at 9:58 AM, Leith Bade <leith at leithalweapon.geek.nz> wrote:
> First the beeper is annoying and loud and I worry it will wake everyone up at night. I read that you can mute the beeper temporarily (and this works) but that most UPSs do not allow you to permanently turn it off (I tried using upsrw but it said beeper.status was read only).
Can you send the variable list of upsrw...
2014 Jul 26
4
Power race? with Eaton 5E and how to auto-mute beeper
...ve a brand new Eaton 5E UPS purchased in Australia.
Details:
Eaton 5E
Model: 5E650iUSB-AU
Date: best I can find is the shipping date to supplier on box label - May
2014
OS:
Ubuntu 14.04 Server edition
Nut 2.7.1
Installed via apt-get install nut
I have two problems I would like to fix.
First the beeper is annoying and loud and I worry it will wake everyone up
at night. I read that you can mute the beeper temporarily (and this works)
but that most UPSs do not allow you to permanently turn it off (I tried
using upsrw but it said beeper.status was read only).
So is there a way to auto-mute the beep...
2009 May 08
1
Battery test feature of APC Back-UPS RS series
Hi all,
I use an APC Back-UPS RS 800, overall my experience with NUT is very
good but there is one feature I am missing: the ability to ask the UPS
for a battery test. upscmd -l shows the following commands available:
$ upscmd -l rs800
Instant commands supported on UPS [rs800]:
beeper.disable - Disable the UPS beeper
beeper.enable - Enable the UPS beeper
beeper.mute - Temporarily mute the UPS beeper
beeper.off - Obsolete (use beeper.disable or beeper.mute)
beeper.on - Obsolete (use beeper.enable)
load.off - Turn off the load immediately
load.off.delay - Turn off the load with a...
2016 Dec 03
3
Problem installing NUT on 16.04
...st address. The "LISTEN 127.0.0.1 3493" line in upsd.conf is sufficient for local control and monitoring, and you can remove "LISTEN ::1 3493".
OK, did that restarted services and:
mythuser at amethi:/etc/nut$ upscmd -l CyberUPS1
Instant commands supported on UPS [CyberUPS1]:
beeper.disable - Disable the UPS beeper
beeper.enable - Enable the UPS beeper
beeper.mute - Temporarily mute the UPS beeper
beeper.off - Obsolete (use beeper.disable or beeper.mute)
beeper.on - Obsolete (use beeper.enable)
load.off - Turn off the load immediately
load.off.delay - Turn off the load with a...
2019 Jan 01
2
Turn on UPS via USB
...ameter.port: auto
driver.parameter.serial: 4B1207P41794
driver.parameter.vendorid: 051d
driver.version: 2.6.5
driver.version.data: APC HID 0.95
driver.version.internal: 0.37
input.sensitivity: medium
input.transfer.high: 139
input.transfer.low: 88
input.voltage: 118.0
input.voltage.nominal: 120
ups.beeper.status: disabled
ups.delay.shutdown: 20
ups.firmware: 867.L6 .D
ups.firmware.aux: L6
ups.load: 0
ups.mfr: American Power Conversion
ups.mfr.date: 2012/02/18
ups.model: Back-UPS NS 1250G
ups.productid: 0002
ups.realpower.nominal: 750
ups.serial: 4B1207P41794
ups.status: OL OFF
ups.test.result: No te...
2012 Apr 26
1
[HCL] CyberPower Systems PR6000LCDRTXL5U supported by usbhid-ups
....parameter.pollfreq: 30
driver.parameter.pollinterval: 2
driver.parameter.port: auto
driver.version: 2.6.3
driver.version.data: CyberPower HID 0.3
driver.version.internal: 0.35
input.transfer.high: 254
input.transfer.low: 147
input.voltage: 240.0
input.voltage.nominal: 112
output.voltage: 207.0
ups.beeper.status: enabled
ups.delay.shutdown: 20
ups.delay.start: 30
ups.load: 46
ups.mfr: CyberPower Systems
ups.model: PR6000LCDRTXL5U
ups.productid: 0601
ups.realpower.nominal: 4500
ups.status: OL
ups.timer.shutdown: 0
ups.timer.start: 0
ups.vendorid: 0764
# upsrw
[battery.charge.low]
Remaining batt...
2008 Dec 01
1
APC Back-UPS CS 500 power cycle
...omaticly turn on after power is back.
A 'upsdrvctl shutdown' in the halt.local does not turn off the ups. A
'upscmd apc load.off.delay 5' works, but the ups does not turn on after
power is back.
Here the output of 'upscmd -l apc' :
Instant commands supported on UPS [apc]:
beeper.disable - Disable the UPS beeper
beeper.enable - Enable the UPS beeper
beeper.mute - Temporarily mute the UPS beeper
beeper.off - Obsolete (use beeper.disable or beeper.mute)
beeper.on - Obsolete (use beeper.enable)
load.off - Turn off the load immediately
load.off.delay - Turn off the load with a...
2007 Oct 11
1
Silence Beeper => Which small UPS's actually support it?
Hello,
I'm looking for a UPS that the beeper can be silenced with nut
via ups.beeper.status variable for a HTPC close to bedrooms.
I have googled extensively and there is not a lot of information
about which UPS's actually support this feature. There are few
references to UPS's that apparently list ups.beeper.status as being...
2012 Nov 23
1
Unable to disable beeper on Powercom Imperial IMP-525AP [SOLVED]
Hi Arnaud,
I received several replies from technical support.
It turned out that according to the UPS serial number it had been
manufactured in 2012. So, the device should support the ability to disable
the beeper.
But still I can not disable the beeper using the latest version of UPSMON
Plus in Windows:
http://www.pcm.ru/data/download/public/soft/setup_upsmon_v2.9.rar (don't
know why; the device was tested on XP/Win7 with different USB cables)
[WORKAROUND]
However, beeper can be disabled with the button...
2019 Jan 02
4
Turn on UPS via USB
...stop
>> the beeping.
>> So the system is still up on 1 PSU, and can talk to both UPS. Can't I turn
>> on the load via USB?
>
> None of the supported commands seem to do the job.
>
> # upscmd -l aixapc
> Instant commands supported on UPS [aixapc]:
>
> beeper.disable - Disable the UPS beeper
> beeper.enable - Enable the UPS beeper
> beeper.mute - Temporarily mute the UPS beeper
> beeper.off - Obsolete (use beeper.disable or beeper.mute)
> beeper.on - Obsolete (use beeper.enable)
> load.off - Turn off the load immediately
> load.off.del...
2015 Jul 27
0
[HCL] Eaton 5E1100i supported by usbhid-ups
...: 0463
driver.version: 2.7.1
driver.version.data: MGE HID 1.32
driver.version.internal: 0.38
input.voltage: 227.0
outlet.1.status: on
outlet.desc: Main Outlet
outlet.id: 1
outlet.switchable: no
output.frequency: 49.9
output.frequency.nominal: 50
output.voltage: 228.0
output.voltage.nominal: 230
ups.beeper.status: enabled
ups.delay.shutdown: 20
ups.firmware: 01.04.0018
ups.load: 8
ups.mfr: EATON
ups.model: 5E 1100i
ups.power.nominal: 1100
ups.productid: ffff
ups.start.battery: yes
ups.status: OL CHRG
ups.timer.shutdown: -1
ups.vendorid: 0463
*upsrw eaton5e*
[outlet.desc]
Outlet description
Type: STR...
2014 Aug 10
1
Power race? with Eaton 5E and how to auto-mute beeper
...laces the Nova. Do they perhaps share
hardware/firmware?
Thanks,
Leith Bade
leith at leithalweapon.geek.nz
On 10 August 2014 10:16, Charles Lepple <clepple at gmail.com> wrote:
> On Jul 26, 2014, at 9:58 AM, Leith Bade <leith at leithalweapon.geek.nz> wrote:
>
>> First the beeper is annoying and loud and I worry it will wake everyone up at night. I read that you can mute the beeper temporarily (and this works) but that most UPSs do not allow you to permanently turn it off (I tried using upsrw but it said beeper.status was read only).
>
> Can you send the variable list...
2013 Aug 08
0
shutdown.* and load.*, and how to possibly add more instcmd for bcmxcp
....battery.start")
18 ("load.off")
16 ("load.on")
11 ("test.battery.stop")
8 ("shutdown.stop")
8 ("shutdown.reboot")
6 ("test.panel.start")
5 ("test.failure.start")
5 ("beeper.enable")
4 ("shutdown.reboot.graceful")
4 ("reset.input.minmax")
4 ("beeper.mute")
3 ("test.failure.stop")
3 ("test.battery.start.quick")
3 ("test.battery.start.deep")
3 ("bypass.s...
2017 May 14
0
[HCL] Cyber Power Systems CP1500AVRLCDa supported by usbhid-ups
...iver.parameter.productid: 0501
driver.parameter.serial: CTHGN200xxxx
driver.parameter.synchronous: no
driver.parameter.vendorid: 0764
driver.version: 2.7.4
driver.version.data: CyberPower HID 0.4
driver.version.internal: 0.41
input.voltage: 121.0
input.voltage.nominal: 120
output.voltage: 137.0
ups.beeper.status: enabled
ups.delay.shutdown: 20
ups.delay.start: 30
ups.load: 18
ups.mfr: CPS
ups.model: CP1500AVRLCDa
ups.productid: 0501
ups.realpower.nominal: 900
ups.serial: CTHGN200xxxx
ups.status: OL
ups.test.result: No test initiated
ups.timer.shutdown: -60
ups.timer.start: -60
ups.vendorid: 0764...
2018 Sep 26
0
[HCL] Cyber Power Systems AVRG750U supported by usbhid-ups
...val: 15
driver.parameter.port: auto
driver.parameter.productid: 0501
driver.parameter.synchronous: no
driver.parameter.vendorid: 0764
driver.version: 2.7.4
driver.version.data: CyberPower HID 0.4
driver.version.internal: 0.41
input.voltage: 121.0
input.voltage.nominal: 120
output.voltage: 129.0
ups.beeper.status: enabled
ups.delay.shutdown: 60
ups.delay.start: 120
ups.load: 2
ups.mfr: CPS
ups.model: AVRG750U
ups.productid: 0501
ups.realpower.nominal: 450
ups.serial: <REDACTED>
ups.status: OL
ups.test.result: Done and passed
ups.timer.shutdown: -60
ups.timer.start: -60
ups.vendorid: 0764
upsrw...
2020 Jan 08
0
Hardware compatability report: Eaton Ellipse ECO 1600
...2
outlet.1.status: on
outlet.1.switchable: no
outlet.2.desc: PowerShare Outlet 2
outlet.2.id: 3
outlet.2.status: on
outlet.2.switchable: no
outlet.desc: Main Outlet
outlet.id: 1
outlet.power: 25
outlet.switchable: no
output.frequency.nominal: 50
output.voltage: 230.0
output.voltage.nominal: 230
ups.beeper.status: enabled
ups.delay.shutdown: 20
ups.delay.start: 30
ups.firmware: 01
ups.load: 19
ups.mfr: EATON
ups.model: Ellipse ECO 1600
ups.power.nominal: 1600
ups.productid: ffff
ups.serial: 000000000
ups.status: OL
ups.timer.shutdown: 0
ups.timer.start: 0
ups.vendorid: 0463
upsrw reports:
[battery....
2016 Dec 03
0
Problem installing NUT on 16.04
...3" line in upsd.conf is sufficient
>> for local control and monitoring, and you can remove "LISTEN ::1 3493".
>
> OK, did that restarted services and:
>
> mythuser at amethi:/etc/nut$ upscmd -l CyberUPS1
> Instant commands supported on UPS [CyberUPS1]:
>
> beeper.disable - Disable the UPS beeper
> beeper.enable - Enable the UPS beeper
> beeper.mute - Temporarily mute the UPS beeper
> beeper.off - Obsolete (use beeper.disable or beeper.mute)
> beeper.on - Obsolete (use beeper.enable)
> load.off - Turn off the load immediately
> load.off.del...
2019 Jan 02
0
Turn on UPS via USB
...ck in, but turned off the load - presumably to stop
> the beeping.
> So the system is still up on 1 PSU, and can talk to both UPS. Can't I turn
> on the load via USB?
None of the supported commands seem to do the job.
# upscmd -l aixapc
Instant commands supported on UPS [aixapc]:
beeper.disable - Disable the UPS beeper
beeper.enable - Enable the UPS beeper
beeper.mute - Temporarily mute the UPS beeper
beeper.off - Obsolete (use beeper.disable or beeper.mute)
beeper.on - Obsolete (use beeper.enable)
load.off - Turn off the load immediately
load.off.delay - Turn off the load with a...