Displaying 20 results from an estimated 4396 matches for "battery".
2011 Mar 31
2
Cyberpower CP850PFCLCD 120% battery charge
Hello all,
I have a CyberPower Systems CP850PFCLCD that I'm hooking up to NUT 2.4.3
from apt running under Ubuntu 10.04. Using the usbhid-ups driver, things
*seem* to work at first glance, but there are some odd issues. The most
notable issue is that the battery.charge indicator reads 120 when at full
charge. I came across this post here:
http://lists.alioth.debian.org/pipermail/nut-upsuser/2007-September/003222.htmlbut
it looks like the user never supplied the necessary data.
The other issue that I found was that the LB flag is sent way to early when
I...
2009 Aug 05
9
Battery condition tools CentOS/Dell
Hello all:
Does anyone know of a tool/project that will allow me to read the
battery condition (not the charge status) on a Dell laptop battery?
Under XP there is a utility that warns that the battery is still
holding a charge but that the battery is degraded and should be
replaced.
Also, not sure if this is possible, but I would like to control how
the laptop charges the battery....
2024 Nov 13
4
Eaton 5PX 3rd party batteries
On 11/12/2024 10:58 AM, Dan Langille via Nut-upsuser wrote:
> Hello,
>
> nut recently told me that the batteries need replacing in my Eaton 5PX2200RT (ups) and 5PXEBM48RT (external battery pack). According to my notes, it has been just over 4 years since I installed them. Looking at on-line sales, these seem to use batteries in a pre-packaged plastic shell. I don't recall if that's what's in my units or not.
>
> Do you have any experience with replacing / filling s...
2024 Nov 13
1
Eaton 5PX 3rd party batteries
...Harlan Stenn via Nut-upsuser <
nut-upsuser at alioth-lists.debian.net> wrote:
> On 11/12/2024 10:58 AM, Dan Langille via Nut-upsuser wrote:
> > Hello,
> >
> > nut recently told me that the batteries need replacing in my Eaton
> 5PX2200RT (ups) and 5PXEBM48RT (external battery pack). According to my
> notes, it has been just over 4 years since I installed them. Looking at
> on-line sales, these seem to use batteries in a pre-packaged plastic shell.
> I don't recall if that's what's in my units or not.
> >
> > Do you have any experience wi...
2012 Feb 13
3
RFC: new variable battery.status (was: [PATCH] upscode2: Report ABM Status)
2012/2/6 thomas schorpp <thomas.schorpp at googlemail.com>:
> Hi,
Hi Thomas,
> I want the driver report the battery status from ABM charging controllers
> -patch attached- :
thanks for your patch.
since it introduces a new variable (battery.status.abm), I prefer to
step back and think to something useful more widely.
thus, I'm thinking about a generic "battery.status" that would have
the foll...
2024 Nov 12
3
Eaton 5PX 3rd party batteries
Hello,
nut recently told me that the batteries need replacing in my Eaton 5PX2200RT (ups) and 5PXEBM48RT (external battery pack). According to my notes, it has been just over 4 years since I installed them. Looking at on-line sales, these seem to use batteries in a pre-packaged plastic shell. I don't recall if that's what's in my units or not.
Do you have any experience with replacing / filling such shells...
2014 Feb 19
3
Logic problem in NUT with upscode2 driver
Hi All,
I have what is probably a 12 year old (or older) Compaq R3000 UPS
plugged into a FreeBSD 8 system running NUT version 2.6.5
This UPS contains a total of 16 batteries in 2 banks of 8,
each battery is 6 volts and the bank produces 50 volts.
The UPS monitors battery voltage and the battery charger in
the UPS works like this. For about 2 days it will apply a
charge/float/topping voltage of 55.2 volts to the batteries.
During that time the battery voltage measures 55.2 volts
both with a vol...
2014 Nov 04
2
RFC: new variable battery.status
...YOUTHANKYOUTHANKYOUTHANKYOU!!!!!!
There was a smaller patch posted to the list for lines
-1389,9 +1390,10
a couple years ago, it helped some - BUT - it was still buggy.
I have a Compaq R3000, I will get this patch integrated pronto and test
Note that since the UPS relies on the voltage from the battery pack to
determine state of charge, it is quite useful to add in the battery pack
voltage to the logs as such:
--- upslog.c.orig 2012-07-31 10:38:58.000000000 -0700
+++ upslog.c 2014-02-20 09:23:14.000000000 -0800
@@ -50,6 +50,7 @@
static flist_t *fhead = NULL;
#define DEFAULT...
2016 May 14
2
Low Battery event not occurring
>
> battery.charge: 3
> battery.charge.low: 10
> battery.charge.warning: 30
> battery.runtime: 93
> battery.temperature: 32.9
> battery.type: PbAC
> battery.voltage: 46.4
> battery.voltage.nominal: 48.0
Is it possible that battery.charge is really 30% rather than 3%?
The 3016 protocol mo...
2019 Sep 06
5
"battery is low" logged
I got around to unplugging my UPS and I found it doesn't last nearly as
long as estimated.
Is the "upsmon[1446]: UPS desktop_ups at localhost battery is low" logged
when "battery.runtime:" = "battery.runtime.low: 120"?
Does any make better batteries that don't go down faster when they get old?
battery.charge: 100
battery.charge.low: 10
battery.charge.warning: 50
battery.date: not set
battery.mfr.date: 2015/09/19...
2014 Nov 03
0
RFC: new variable battery.status (was: [PATCH] upscode2: Report ABM Status)
Hi,
Am 13.02.2012 um 18:58 schrieb Arnaud Quette:
> 2012/2/6 thomas schorpp <thomas.schorpp at googlemail.com>:
>> Hi,
>
> Hi Thomas,
>
>> I want the driver report the battery status from ABM charging controllers
>> -patch attached- :
>
> For now, I've tracked your patch here:
> https://alioth.debian.org/tracker/index.php?func=detail&aid=313541&group_id=30602&atid=411544
>
Thanks, but no anonymous read access, so not very useful linkin...
2014 Nov 04
0
RFC: new variable battery.status
Hi Ted,
Am 04.11.2014 um 04:12 schrieb Ted Mittelstaedt:
>
> Note that since the UPS relies on the voltage from the battery pack to
> determine state of charge, it is quite useful to add in the battery pack
> voltage to the logs as such:
>
> --- upslog.c.orig 2012-07-31 10:38:58.000000000 -0700
> +++ upslog.c 2014-02-20 09:23:14.000000000 -0800
> @@ -50,6 +50,7 @@
> static flist_t...
2006 Mar 24
13
UPS Batteries
Hello,
This may be a really stupid question, but can a gel type marine battery be used in a UPS?
Thanks
2014 Apr 22
6
[OT] how do I remove a battery
I've got an MSI K9N Platinum MS 7250 VER 1.1
motherboard with a dead battery.
The battery mounts vertically:
http://www.cs.ndsu.nodak.edu/~hennebry/computer/battery.png
To me, the tab on the right would seem to need moving.
It does not want to move.
I am reluctant to apply any more force than I
already have without knowing how to apply it.
How do I remove the battery?
--...
2009 Feb 28
2
APC SMART-UPS 1500 always reporting LB
...ave a client who's APC SMART-UPS 1500 (circa 2000) is always reporting LB. The batteries were old so they were replaced two weeks ago with brand new batteries. UPS still reported low batteries...
I ran a calibration and a test on the unit (using the nut upscmd utility)
During those tests, the battery charge on the unit goes to zero and slowly starts making its way back up 100%. Then, the "LB" ups.status will come and go every few hours until it finally stays on. All battery leds on the unit are flashing also indicating that the UPS thinks there is a low battery condition - which corre...
2024 Nov 13
2
Eaton 5PX 3rd party batteries
resending, sorry, I mangled the list address.
On Tue, Nov 12, 2024, at 11:49 PM, Harlan Stenn wrote:
> - put each battery on a charger for several hours
Do you have a recommendation for a battery charger? Or a list of features to look for?
> Anyway, when I have a set of replacement new batteries, I then:
>
> - put each battery on a charger for several hours
> - rotating thru the entire set at least twic...
2007 Sep 05
2
Krauler UP-D1200VA
...a string in 52-nut-usbups.rules from:
SUBSYSTEM!="usb_device", GOTO="nut-usbups_rules_end"
to:
SUBSYSTEM!="usb*", GOTO="nut-usbups_rules_end"
to make hotplugging work on my Gentoo 2007.0, kernel 2.6.22.1 and default
Gentoo udev rules.
There are 3 issues.
1. Battery charge. I attach a patch to the latest svn revision that adds
information for my Krauler's battery. The battery charge reported by nut
should
be almost the same as reported by UPSilon2000 for Windows software, thx to
USB SnoopyPro. I had to change "int nominal" to "float nominal...
2008 Oct 27
1
Megatec and Batteries
Hi to all,
I am new on the lists but using nut on megatec for last two and half years.
Looking at archives I saw that there is a lot of people confused about battery voltage and I want to help them to clear out some stuff in their heads.
This story is based on my experience with UPS devices from 600VA to 20kVA, from single phase systems to three phase systems, with battery packs from 1 battery to 62 batteries in both technologies interactive (aka stand-by)...
2015 Dec 29
2
[HCL] NHS Laser Senoidal 5000VA supported by gamatronic
Device Manufacturer: NHS
Device Name: Laser Senoidal 5000VA
upsc output when the UPS is in normal condition:
battery.charge: 100
battery.current: 0.4
battery.date: 12292015
battery.runtime: 00000
battery.runtime.low: 59940
battery.temperature: 00
battery.voltage: 163.4
device.mfr: NHS Sistemas de Energia
device.model: Laser Senoidal 5000VA
device.type: ups
driver.name: gamatronic
driver.parameter.polli...
2023 Jan 17
1
PR to test for users of Qx devices (blazer and nutdrv_qx)
...upsuser <nut-upsuser at alioth-lists.debian.net>
>
> Cheers,
>
> One PR waiting to get into 2.8.1 release timeframe is https://github.com/networkupstools/nut/pull/1652 stemming from issue https://github.com/networkupstools/nut/issues/1279
>
> The gist of it is that "battery.voltage" and "battery.charge" were not always reported correctly with nutdrv-qx driver (might be handled better by blazer drivers though), and the overrides tried by issue posters did not help them with original state of NUT codebase.
I tried it on three ups: 10kv online, 3kv online...