I'm sorry about a wrong place to address, because my problem most likely is in a hardware, not the NUT software. I had tried to contact the MGE support team, but got no answer. I have purchased the MGE Ellipse 650 UPS, and after testing it with the Linux/NUT package (v. 2.0, mge-shut driver) found out that the battery.charge indicator and related things (battery.lifetime, low battery signal) don't function properly. Replacing the unit did not help. After switching the UPS on battery.charge ALWAYS shows 85%, unrelated of real battery status. Then, in the ON LINE state this variable slowly counts up, and in the ON BATTERY state counts down (more faster). That's all! If the battery have REALLY fully charged, the battery.charge reaches 30% and triggers the LOW BATTERY signal in ~20 min, reaches 0% in ~30 min, but the UPS can provide power, for example, above 1 hour. If the battery have ran down before, the UPS can drop power after 2 min on battery run with battery.charge=78% and without LOW BATTERY warning! Sorry, but I want to have a UPS with battery monitoring, not a clock with alarm! This behavior makes the computer interface and software totally useless (except for the OL/OB status)! With best regards, Jabonovsky Alexander, the system administrator