2010-Mar-03 19:03 UTC
[Nut-upsdev] using upscode2 driver with Powerware 5119 RM
I've got a Powerware 5119 RM UPS. driver.list says to use "genericups upstype=20", however I know this UPS supports the UPS Code II protocol, so I wanted to use the upscode2 driver. It took some hacking but finally it works. I'm using NUT 2.4.1 and upscode2 driver version 0.87 (however the latest r2350 version of upscode2.c isn't significantly different, so I think all my results still apply). Here's the hardware: Apple G5 Xserve running Mac OS X Server 10.5.8 IOGEAR GUC2322 USB-to-serial adapter (uses Moschip 78XX) Powerware Model PW5119, P/N 05144717-5501, purchased 12/2000 so maybe old firmware? Here's what upsc says about this UPS: ups.mfr: Powerware ups.model: UPS 1440 VA FW -0039 ups.power.nominal: 1440.00 ups.serial: TS381A0198 Here's what I have in ups.conf: driver = upscode2 port = /dev/tty.MCS78XX_Port0.0 manufacturer = "Powerware" desc = "Powerware 5119 RM on myhostname" output_pace = 300 use_crlf Setting output_pace to 300 seemed to make communications more robust. YMMV. UPS Code II spec says you need use_crlf, but it seems to work even without it. The upscode2 driver worked great for normal status, except it failed to power down the UPS. After much debugging I discovered the following problems: 1. The driver successfully sends the UPPC powerdown command, followed by the security string, and then exits. However the UPS ignored the UPPC command and never shut down. By performing a UPTP command right after the UPPC then the UPPC is recognized! Maybe the UPS doesn't like the serial communication being dropped so abruptly? 2. UPS Code II spec says you can view the values of UPSD and UPPC by sending the command string followed by a parameter of "0". However for my UPS this sets the value to 0! In order to view the value you must send "0000". So in upsc_commandlist I changed upsc_getvalue(cp->upsc, "0", cp->upsp, cp->cmd, NULL); to upsc_getvalue(cp->upsc, "0000", cp->upsp, cp->cmd, NULL); and all works correctly. 3. I want to specify a custom shutdown delay value. I can use upsrw upsrw -s ups.delay.shutdown=60 -u admin -p password UPSNAME and the parameter is correctly stored into the UPS using UPSD. And you can read this value back (if you fixed item 2. above). I do this at boot time. However the driver ignores my setting, and forces UPSD to have a value of "1" just before issuing the UPPC shutdown command. Removing this UPSD allows the custom value to be used correctly. Also I changed the shutdown messages so the ups.delay.* values are reported. With all that, here's what upsdrv_shutdown looks like: void upsdrv_shutdown(void) { if (upsc_commandlist()) { if (!can_upsd || !can_uppc) { fatalx(LOG_EMERG, "Shutdown called, but UPS does not support it"); } } else { upslogx(LOG_EMERG, "Can't determine if shutdown is supported, attempting anyway"); } upslogx(LOG_EMERG, "Emergency shutdown"); char msg[100]; snprintf(msg, 100, "UPS will reboot %ld seconds after shutdown", strtol(dstate_getinfo("ups.delay.reboot"),NULL,10)); upslogx(LOG_EMERG, msg); snprintf(msg, 100, "UPS shutting down in %ld seconds...", strtol(dstate_getinfo("ups.delay.shutdown"),NULL,10)); upslogx(LOG_EMERG, msg); upscsend("UPPC"); /* Powercycle UPS */ upscsend("IJHLDMGCIU"); /* security code */ /* do something so connection doesn't drop right after UPPC command */ upsc_getvalue("UPTP", NULL, "NNAME", "ups.model", NULL); } I'm sure a real C hacker could find a cleaner/better/elegant way to print the messages, but hey I'm a hardware guy. I'm just happy it's all working. -seg
Arjen de Korte
2010-Mar-03 20:53 UTC
[Nut-upsdev] using upscode2 driver with Powerware 5119 RM
Citeren Steve Golson <sgolson op trilobyte.com>:> I'm using NUT 2.4.1 and upscode2 driver version 0.87 (however the > latest r2350 version of upscode2.c isn't significantly different, so > I think all my results still apply).That is no longer the latest version, I just committed r2389 and r2390 based on the information you provided. [...]> However the driver ignores my setting, and forces UPSD to have a > value of "1" just before issuing the UPPC shutdown command. Removing > this UPSD allows the custom value to be used correctly.I attempted to fix this, by setting "ups.delay.shutdown=10" and "ups.delay.reboot=120" when the driver starts monitoring the UPS (in order to have some sensible defaults). If you restart the driver with the -k flag (in order to send the shutdown command), this part of the code will be skipped and the driver will proceed to send the "shutdown.return" instcmd (twice actually, with a one second delay in between) with any "ups.delay.shutdown" that may have been set in the mean time. I agree that it isn't pretty to allow people to set a shutdown delay and then when the time comes to shutdown, completely ignore whatever they requested.> Also I changed the shutdown messages so the ups.delay.* values are reported.I fail to see the benefit of that. The filesystems should have been (re)mounted read-only and we probably don't have network connectivity anymore at that time, so unless someone is watching the console at that time, the messages will be lost forever. The reason why we have them here, is for debugging purposes. Having said that, thanks for your feedback. It's been quite a while since we've seen someone running this driver and it is good to know that it still serves a purpose to maintain it. If you have the time to checkout the latest version from the trunk, I would be grateful. Best regards, Arjen -- Please keep list traffic on the list
Maybe Matching Threads
- Fwd: upscode2.c
- failed after upgrade - upscode2: Missing UPCL after UPCL
- RFC: new variable battery.status (was: [PATCH] upscode2: Report ABM Status)
- RFC: new variable battery.status (was: [PATCH] upscode2: Report ABM Status)
- failed after upgrade - upscode2: Missing UPCL after UPCL