2010 Mar 03
1
using upscode2 driver with Powerware 5119 RM
...ys about this UPS:
ups.mfr: Powerware
ups.model: UPS 1440 VA FW -0039
ups.power.nominal: 1440.00
ups.serial: TS381A0198
Here's what I have in ups.conf:
driver = upscode2
port = /dev/tty.MCS78XX_Port0.0
manufacturer = "Powerware"
desc = "Powerware 5119 RM on myhostname"
output_pace = 300
use_crlf
Setting output_pace to 300 seemed to make communications more robust. YMMV.
UPS Code II spec says you need use_crlf, but it seems to work even without it.
The upscode2 driver worked great for normal status, except it failed to power
down the UPS. After much debugging I discovere...