Charles Lepple
2014-Jan-21 13:54 UTC
[Nut-upsuser] Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 8:05 AM, Rafa? Oleszek wrote:> It does not matter what value I'll put in MONITOR and MINSUPPLIES line. NUT not waiting for both UPS to start timer.Correct. You can think of upssched as operating on raw UPS status, rather than the calculated powervalue that upsmon uses to decide when to shut down. -- Charles Lepple clepple at gmail
Rafal Oleszek
2014-Jan-21 14:27 UTC
[Nut-upsuser] Shutdown when both (all) UPS on battery / low battery
So it's impossible to configure upssched to start timer only if all ups are in status: OB or LB ?> On Jan 21, 2014, at 8:05 AM, Rafa? Oleszek wrote: > >> It does not matter what value I'll put in MONITOR and MINSUPPLIES line. >> NUT not waiting for both UPS to start timer. > > Correct. You can think of upssched as operating on raw UPS status, rather > than the calculated powervalue that upsmon uses to decide when to shut > down. > > -- > Charles Lepple > clepple at gmail > >
Charles Lepple
2014-Jan-23 00:59 UTC
[Nut-upsuser] Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 9:27 AM, Rafal Oleszek wrote:> So it's impossible to configure upssched to start timer only if all ups > are in status: OB or LB ?Not impossible, just not possible inside a single configuration file. You can always put that logic into an external script called by upssched. -- Charles Lepple clepple at gmail
Maybe Matching Threads
- Shutdown when both (all) UPS on battery / low battery
- Shutdown when both (all) UPS on battery / low battery
- Shutdown when both (all) UPS on battery / low battery
- Shutdown when both (all) UPS on battery / low battery
- Shutdown when both (all) UPS on battery / low battery