Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 9:24 AM, Rafal Oleszek wrote: > I tried all options: > 1,2 > and in MINSUPPLIES: 1,2,3,4 > still didn't work. My mistake - I gave you the wrong advice before. For MINSUPPLIES, I'm used to either a 1:1 UPS-to-server ratio, or 2:1 where the server can run with either power supply unpowered. I just tr...
2014 Jan 23
0
Shutdown when both (all) UPS on battery / low battery
> On Jan 21, 2014, at 9:24 AM, Rafal Oleszek wrote: > >> I tried all options: >> 1,2 >> and in MINSUPPLIES: 1,2,3,4 >> still didn't work. > > My mistake - I gave you the wrong advice before. For MINSUPPLIES, I'm used > to either a 1:1 UPS-to-server ratio, or 2:1 where the server can run with > ei...
2014 Jan 21
2
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 8:05 AM, Rafa? Oleszek wrote: > MONITOR UPS_251 at localhost 2 monmaster password master > MONITOR UPS_252 at localhost 2 monmaster password master I think the "2"s here should be "1". "powervalue is an integer representing the number of power supplies that the UPS feeds *on this system*...
2014 Jan 21
2
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 8:05 AM, Rafa? Oleszek wrote: > It does not matter what value I'll put in MONITOR and MINSUPPLIES line. NUT not waiting for both UPS to start timer. Correct. You can think of upssched as operating on raw UPS status, rather than the calculated powervalue that upsmon uses to decide when to shut down. -- Charles...
2014 Jan 23
2
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 9:27 AM, Rafal Oleszek wrote: > So it's impossible to configure upssched to start timer only if all ups > are in status: OB or LB ? Not impossible, just not possible inside a single configuration file. You can always put that logic into an external script called by upssched. -- Charles Lepple clepple at gma...
2014 Jan 21
3
Shutdown when both (all) UPS on battery / low battery
On Jan 21, 2014, at 3:16 AM, Rafa? Oleszek wrote: > I would like to mention that MINSUPPLIES manipulation doesn't work. My nut version is : 2.2.2-4 (RHEL 5) What do your configuration files look like? Setting MINSUPPLIES to 2 should work. You can run upsmon with a debug level of 3 or greater, and it will print the current and min...
2014 Jan 21
0
Shutdown when both (all) UPS on battery / low battery
I tried all options: 1,2 and in MINSUPPLIES: 1,2,3,4 still didn't work. UPS_251 and UPS_252 feeds all environment and it's not feed directly one server, but many of them. > On Jan 21, 2014, at 8:05 AM, Rafa? Oleszek wrote: > >> MONITOR UPS_251 at localhost 2 monmaster password master >> MONITOR UPS_252 at localhost 2 monmaster password master > > I think the "2"s here should be "1". > > "powervalue is an integer representing the number of power supplies that...
2014 Jan 21
0
Shutdown when both (all) UPS on battery / low battery
So it's impossible to configure upssched to start timer only if all ups are in status: OB or LB ? > On Jan 21, 2014, at 8:05 AM, Rafa? Oleszek wrote: > >> It does not matter what value I'll put in MONITOR and MINSUPPLIES line. >> NUT not waiting for both UPS to start timer. > > Correct. You can think of upssched as operating on raw UPS status, rather > than the calculated powervalue that upsmon uses to decide w...
2014 Feb 03
0
Shutdown when both (all) UPS on battery / low battery
> On Jan 21, 2014, at 9:27 AM, Rafal Oleszek wrote: > >> So it's impossible to configure upssched to start timer only if all ups >> are in status: OB or LB ? > Not impossible, just not possible inside a single configuration file. You can always put that logic into an external script called by upssched. > Thank for yo...
2014 Jan 21
0
Shutdown when both (all) UPS on battery / low battery
> What do your configuration files look like? Setting MINSUPPLIES to 2 should work. You can run upsmon with a debug level of 3 or greater, and it will print the current and minimum "power value", which is what determines when to shut down. > > Also, if you don't want to wait for both UPSes to drain to the low battery state, you can set up a pair of dummy-ups drivers. I'm
2014 Jan 21
2
Shutdown when both (all) UPS on battery / low battery
Hi, I have data room with single master nut instance which calling scripts to shutdown environment. I have two Delta UPS reachable from network. Everything works fine but I need to configure nut to shutdown environment when both UPS on battery or low battery. Can you advise me how to do that (is it possible?). THX for any help. -------------- next part -------------- A non-text attachment was
2014 Jan 21
0
Shutdown when both (all) UPS on battery / low battery
I would like to mention that MINSUPPLIES manipulation doesn't work. My nut version is : 2.2.2-4 (RHEL 5) -------------- next part -------------- A non-text attachment was scrubbed... Name: smime.p7s Type: application/pkcs7-signature Size: 2274 bytes Desc: Kryptograficzna sygnatura S/MIME URL: