Has anyone gotten this model of tripp-lite to work? sudo /usr/local/bin/upsdrvctl -DDDDD -u root start Network UPS Tools - UPS driver controller 2.0.5 Starting UPS: tripplite exec: /usr/local/bin/tripplite_usb -a tripplite Network UPS Tools - Tripp Lite OMNIVS and SMARTPRO driver 0.7 (2.0.5) Warning: This is an experimental driver. Some features may not function correctly. Detected a UPS: TRIPP LITE/ TRIPP LITE SMART3000RM2U libusb_get_interrupt() returned -110 instead of 8 libusb_get_interrupt() returned 0 instead of 8 libusb_get_interrupt() returned -110 instead of 8 libusb_get_interrupt() returned -19 instead of 8 libusb_get_interrupt() returned -19 instead of 8 libusb_get_interrupt() returned -19 instead of 8 libusb_set_report() returned -19 instead of 8 Could not reset watchdog. Please send model information to nut-upsdev mailing list libusb_set_report() returned -19 instead of 8 Error reading protocol Driver failed to start (exit status=1) -- /usr/local/etc/ups.conf -- [tripplite] driver = tripplite_usb port = auto bus = 002 desc = "Tripp-lite SmartPro" -- 'lsusb -vv' output -- Bus 002 Device 003: ID 09ae:0001 Tripp Lite Device Descriptor: bLength 18 bDescriptorType 1 bcdUSB 1.10 bDeviceClass 0 (Defined at Interface level) bDeviceSubClass 0 bDeviceProtocol 0 bMaxPacketSize0 8 idVendor 0x09ae Tripp Lite idProduct 0x0001 bcdDevice 0.01 iManufacturer 1 TRIPP LITE iProduct 2 TRIPP LITE SMART3000RM2U iSerial 0 bNumConfigurations 1 Configuration Descriptor: bLength 9 bDescriptorType 2 wTotalLength 34 bNumInterfaces 1 bConfigurationValue 1 iConfiguration 0 bmAttributes 0x80 MaxPower 60mA Interface Descriptor: bLength 9 bDescriptorType 4 bInterfaceNumber 0 bAlternateSetting 0 bNumEndpoints 1 bInterfaceClass 3 Human Interface Devices bInterfaceSubClass 1 Boot Interface Subclass bInterfaceProtocol 0 None iInterface 0 HID Device Descriptor: bLength 9 bDescriptorType 33 bcdHID 1.00 bCountryCode 0 bNumDescriptors 1 bDescriptorType 34 Report wDescriptorLength 52 cannot get report descriptor Endpoint Descriptor: bLength 7 bDescriptorType 5 bEndpointAddress 0x81 EP 1 IN bmAttributes 3 Transfer Type Interrupt Synch Type none Usage Type Data wMaxPacketSize 0x0008 bytes 8 once bInterval 200 Language IDs: (length=4) 0409 English(US)
On 6/29/07, Michael Belanger <mrb at ciclops.org> wrote:> Has anyone gotten this model of tripp-lite to work? > > sudo /usr/local/bin/upsdrvctl -DDDDD -u root startupsdrvctl doesn't pass the "-DDDDD" portion to the driver -- see below the "exec" line below.> Network UPS Tools - UPS driver controller 2.0.5 > Starting UPS: tripplite > exec: /usr/local/bin/tripplite_usb -a trippliteJust run "/usr/local/bin/tripplite_usb -DDDDD -a tripplite" for testing. There have been a number of changes since 2.0.5, but the only one I see is an increase in the number of retries, and I am not sure yet if that will help. The "-DDDDD" output might shed some light on this, though. -- - Charles Lepple