Displaying 20 results from an estimated 4000 matches similar to: "Powercom BNT USB fix needs testing"
2017 Apr 28
3
Powercom BNT-2000AP(USB)
Hello all!
Some days ago we received new UPS?Powercom BNT-2000AP with USB interface to replace an old staff and I've spent four last days trying to connect it with NUT. I have a FreeBSD 8.4 box with NUT 2.7.2.
# dmesg|grep -i powercom
ugen0.3: <POWERCOM Co.,LTD> at usbus0
uhid0: <POWERCOM Co.,LTD HID UPS Battery, class 0/0, rev 1.10/0.01, addr 3> on usbus0
uhid0: <POWERCOM
2006 Apr 21
1
Powercom BNT-1200AP
Hello
I have UPS Powercom Black Knight Pro 1200 (BNT-1200AP)
I try to use nut, but powercom driver not understand my model
Ok, i try to use type KIN1500AP and it's work
But powercom driver can't set UPS's shutdown delay time
Also i have powercom's original program (upsmon), and this program can do it
What can i do for help to add this function to nut's powercom driver?
For
2013 May 01
1
Powercom BNT-1500AP serial config
Hey all,
Finally got around to hooking up my Powercom BNT-1500AP to nut. It's the
old serial interface.
Connects okay and gets most information, but a couple of data are way off.
Any config recommendations or upgrade recommended? I've played with
config a little, but no hits yet.
Details:
NUT version 2.4.3
ups.conf:
[ups]
driver = powercom
port = /dev/ttyS0
2007 Dec 24
3
Driver for Powercom BNT/KIN/IMP/IMD series
Hello all.
Try this driver (for nut 2.2.0). See attach.
- Trust, KP625AP, Egys models stay as it was
- add Powercom's Black Knight Pro model support ( BNT-400/500/600/800/801/1000/1200/1500/2000AP
220-240V )
- add Powercom's King Pro model support (
KIN-425/525/625/800/1000/1200/1500/1600/2200/3000/5000AP[-RM] 100-120,200-240 V)
- add Powercom's Imperial model support ( IMP-xxxAP,
2011 Oct 04
2
PowerCOM BNT-800AP (0d9f:0004)
Hello.
I've been trying to got it work but haven't luck.
I'm using NUT 2.6.0-1 under Windows XP with libusb driver installed
(USB\VID_0D9F&PID_0004&REV_0001).
I had tryed all options with such config:
*PWCOM]
driver = usbhid-ups
port = auto
vendorid = 0d9f
desc = "Powercom BNT-800AP"
type=BNT*
*
*Here is output from CMD:*
2009 Jul 27
1
Powercom BNT-1000CS
Hello. I have recently purchased a Powercom BNT-1000CS(Black Knight CS).
I am new to NUT(and am not a programmer), but I have noticed that this
model does not work with NUT. I am willing to provide details about this
UPS for anyone who would like to add support for it(i dont know how to
get much info though, so you'll have to tell me how). For starters, this
is what happens when I do
2006 Dec 22
1
Powercom BNT-1200AP driver
Hello.
What about driver for my UPS?
I have changed the powercom driver for myself, but I have made it not absolutely correctly. However, somehow this driver works.
Now i have protocol spec for powercom BNT series and attach it to this email.
It can be interesting to authors?
--
? ?????????, ??????? ???????
mailto:alex@reutman.ru
JID: alex@reutman.ru
ICQ: 5052225
-------------- next part
2012 Nov 13
1
PowerCom BNT-600AP on ubuntu 12.04.1 AMD64
Hello people,
I use a BNT-600AP from PowerCom, and on driver loading (nut service
start) the UPS goes off so I cannot use nut as service as the computer
goes off with the UPS.
When the computer is not using the UPS, but still connected, I see that
the UPS goes off for a very short time, does battery check and goes on
again.
I don't know how to deal with this issue as I cannot use my UPS
2013 Jun 08
0
several problems with Powercom BNT-500AP
On Jun 5, 2013, at 11:49 AM, M?rti?? Pu??tis wrote:
> Driver debug output attached.
The debug output looks normal (many devices do not implement the interrupt pipe; hence, the timeouts). Unfortunately, we might need the log over a longer period of time, including your observations as to when various events occurred (such as transitions to battery).
--
Charles Lepple
clepple at gmail
2013 Jun 11
0
several problems with Powercom BNT-500AP
[I am CC'ing Alexey from Powercom in case he has seen any of these issues with the Raspberry Pi hardware.]
On Jun 10, 2013, at 1:05 PM, M?rti?? Pu??tis wrote:
> I took the log. Here's what happened.
> Broadcast Message from nut at rasp
> (somewhere) at 16:18 ...
> UPS BNT500AP at localhost battery needs to be replaced
>
> occurred when for the first time value
2011 Nov 13
1
Installing Powercom BNT-2000AP on CentOS 5.6
Hi Guys,
Am a Linux newbie and need some help setting up this UPS with NUT on Cent
OS 5.6. So basically I have the following packages installed with yum:
libusb-devel-0.1.12-5.1.x86_64
libusb-devel-0.1.12-5.1.i386
libusb-0.1.12-5.1.x86_64
libusb-0.1.12-5.1.i386
nut-2.2.2-1.el5.x86_64
When I run service ups start I get the following:
Starting UPS driver controller:
2013 Jun 05
2
several problems with Powercom BNT-500AP
OS name and version:
pi at raspberrypi ~ $ cat /etc/*release
PRETTY_NAME="Debian GNU/Linux 7.0 (wheezy)"
uname -a
Linux raspberrypi 3.6.11+ #393 PREEMPT Fri Mar 8 16:36:28 GMT 2013 armv6l
GNU/Linux
exact NUT version
pi at raspberrypi ~ $ dpkg -s nut
Package: nut
...
Version: 2.6.4-2.3
NUT installation method: package
exact device name and related information:
2013 Jun 08
0
several problems with Powercom BNT-500AP
On Jun 8, 2013, at 12:57 PM, M?rti?? Pu??tis wrote:
> I'll take a longer driver log. This page (http://www.networkupstools.org/support.html) says that to take a driver log NUT should be stopped, so I won't be able to tell when these events occurred within a driver log.
Hmm, I didn't realize it said that, but I think that's to prevent having two copies of the same driver
2013 Jun 10
2
several problems with Powercom BNT-500AP
I took the log. Here's what happened.
Broadcast Message from nut at rasp
(somewhere) at 16:18 ...
UPS BNT500AP at localhost battery needs to be replaced
occurred when for the first time value "1" was read as "UPS.PowerSummary.PresentStatus.NeedReplacement", on this line:
6409.240690 Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID: 0x0a,
2013 Jun 08
2
several problems with Powercom BNT-500AP
Thanks for the support.
Here's list of when transition to battery with return to utility power within a few seconds occurred in last few days:
Wednesday
1:41
11:48
11:54
12:59
13:42
14:42
18:13
18:14
Thursday
5:23
Friday
5:12
7:39
7:43
Saturday
7:34
Here's list of when messages that battery needs replacement occurred:
Wednesday
20:34
Thursday
9:07
23:09
Friday
18:25
Saturday
7:32
19:47
2006 Dec 11
2
howto setup BNT-1500AP on gentoo
Good afternoon. I try to put nut on gentoo. Has executed installation
by a standard command emerge nut. All has passed successfully. I use
UPS POWERCOM BNT-1500AP. It is connected to serial port 1, i.e. for my
system it/dev/tts/0. In/etc/nut/ups.conf
[powercom]
driver = powercom
port = /dev/tts/0
desc = "PowerCom BNT-1500AP on IP-PBX"
modelname = "BNT-1500AP"
linevoltage = 230
2011 Jan 13
0
[NUT]updated powercom driver for powercom BNT-500AP
Hi,
2010/12/27 ??? <pointbre at naver.com>
> First of all, thanks for your effort to NUT Project,
> I'm developing remote monitoring solution for many devices based on linux
> server.
> In field test, we reached the power shutdown problem which may cause the
> crack of linux file system.
> I search the solution and find NUT project and i'm very glad that NUT
>
2023 Sep 16
1
Nut-upsdev Digest, Vol 206, Issue 5
It seems the `libmodbus` library or headers were not found, or something
similar - so the driver against it was not built. Did you install
`libmodbus-dev` before the build? What does `config.log` in the build root
say (and.or the summary shown after you run the `configure` script)?
On Sat, Sep 16, 2023 at 7:46?PM FatGear <fatgear1 at free.fr> wrote:
> Hi,
>
> I don't know what
2006 Jul 08
0
Powercom BNT-600AP and NUT (powercom driver)
Hello,
I'm new there. I bought an UPS Powercom BNT-600AP. It's compatible
in NUT with driver powercom and protocol type KIN1500AP.
But I have a simple problem: the 'upsc' shows wrong values in
battery.charge (maybe in other rows also /ups.load, voltages?/) - if
battery is 100% charged it shows only 92.6% or 93.0%.
I thing I have wrong values in driver parameters: batteryPercentage,
2017 Apr 26
0
Powercom BNT-2000AP(USB)
Hello all!
Some days ago we received new UPS?Powercom BNT-2000AP with USB interface to replace an old staff and I've spent three last days trying to connect it with NUT. I have a FreeBSD 8.4 box with NUT 2.7.2.
# dmesg|grep -i powercom
ugen0.3: <POWERCOM Co.,LTD> at usbus0
uhid0: <POWERCOM Co.,LTD HID UPS Battery, class 0/0, rev 1.10/0.01, addr 3> on usbus0
uhid0: <POWERCOM