Displaying 20 results from an estimated 1000 matches similar to: "Server did not shut down"
2023 Jun 10
1
Fopen upsmon.pid - no such file or directory - Nut 2.8.0 built from source
I've built NUT 2.8.0 from source. When the nut-monitor runs: fopen upsmon.pid fails. I'm running as root, upsmon has root:root permissions as well as the other daemons and .conf files. I've tried configuring with and without --prefixpath --prefixaltpath.
Is there something I am missing?
Please see attached.
Dan
-------------- next part --------------
An HTML attachment was
2015 Oct 27
0
The system doesn't shutdown
On Tue, 27 Oct 2015, George Anchev wrote:
> Yes, that was the power off test. However the upssched-cmd script gave
> absolutely no signs of activity. Even it's logger lines don't show up in
> journalctl. No any permission error messages - nothing. Only the 2
> messages from upsmon - on battery and then on line power.
>
> Here is the nut-report:
>
2010 Jan 09
2
problem with mailing (nut 2.4.1 and a powermust650 -> megatec_usb)
Hello guys
Yesterday i started do configure my Mustek Powermust650 with nut using
the megatec_usb driver. Everything works fine except for the mailing
when something happens. My upsmon looks like this:
MONITOR powermust650 at localhost 1 local controller master
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
NOTIFYCMD /root/upsmailer
POLLFREQ 10
POLLFREQALERT 5
HOSTSYNC 15
2023 Jun 16
1
Dummy-ups cycles between online and onbatt every 5 minutes. (Nut 2.8.0)
Now that upsstats.cgi works, I've noticed that dummy-ups changes state every 5 minutes between OL and OB (probably when the 300 second timer expires). The UPS state stays online.
Also "online" and "onbatt" are broadcast to the console probably via WALL. (The state changes don't seem to be form the ups as upsshed-cmd doesn't run). Upssched-cmd does run when the UPS
2015 Jul 15
3
No messages
Charles,
This is how I have the upsmon.conf set up. ?The only time I get a message is if the?NUT Monitor gui is running. ?I open LXterminal, pull the wall plug, and I get no messagesin the terminal.
?MONITOR Asium_p700 at localhost 1 upsmon jsamcr master?MINSUPPLIES 1?SHUTDOWNCMD "/sbin/shutdown -h +0"?NOTIFYCMD /sbin/upssched?POLLFREQ 5?POLLFREQALERT 5?HOSTSYNC 15?DEADTIME
2012 Jan 28
2
No shutdown on empty battery
Hello,
I set up a FreeBSD 8.2 system with nut 2.6.1 and a Powerware 5115
connected by RS-232. I expected this setup to shut down before running
out of battery power, but I either missed some important configuration
or something else went wrong:
The syslog says:
Jan 9 05:03:42 b1 upsmon[67752]: UPS upsb1 at localhost on battery
Jan 9 05:04:42 b1 upsmon[67752]: UPS upsb1 at localhost on line
2024 Jul 27
1
Fedora 40 nut-server not starting at boot
Hi folks, I'm having an issue with getting nut-server to start at boot on a
freshly installed Fedora 40 desktop. Seems once the machine is up, I can
manually start with systemctl start nut-server and everythings fine.
dnf info nut
Last metadata expiration check: 2:08:11 ago on Sat 27 Jul 2024 03:48:13 PM
EDT.
Installed Packages
Name : nut
Version : 2.8.2
Release : 1.fc40
2020 Mar 10
2
Fwd: Windows upssched does not work
Hi,
I have problem with upssched on windows. Upssched is not executed. I
have 2 scripts, 1 for notification in upsmon and second for scheduling
in upssched. Monitoring is working fine, script write to log. I'm
using binary windows installer 2.6.5-6 from NUT.
Here are my configs:
--- nut.conf
MODE=netclient
--- upsmon.conf
MONITOR ups_1000 at 192.168.3.95 1 <user> <password> slave
2023 May 27
2
unable to connect to APC UPS Connection Refused
I've not been able to connect to my ups using NUT 2.7.4 or NUT 2.8.0.
2.7.4 was installed as a package, 2.8.O was compiled from source.
I've messed with permissons, everything is root:root and has the approprate read/execute permissons. I've tried two differnt UPS(es) APC & CyperPower. I'm running PI OS (Raspbian) on a Raspberry Pi3 model B. The port 3493 is open (UFW). I can
2017 Oct 18
2
debian 8 "jessie" nut 2.7.2 slaves not shutting down
MASTER SYSTEM
nut.conf
MODE=netserver
ups.conf
[TOPAPC]
driver = usbhid-ups
port = auto
pollonly
serial = "IS1309002707"
desc = "TOPAPC"
[MIDAPC]
driver = usbhid-ups
port = auto
pollonly
serial = "IS1309001233"
desc = "MIDAPC"
[BOTAPC]
driver = usbhid-ups
port = auto
2020 Apr 28
2
Tripp-Lite SMART1500LCD: powers off with /etc/killpower...then powers back on...
Hi Everyone,
I recently bought a Tripp-Lite SMART1500LCD for my Linux Mint 19.3 machine,
connected via a USB cable. I installed Nut 2.7.4 from the Mint package
repository via sudo apt update && sudo apt install nut. Everything works
great: NUT issues low battery warning when it reaches the set low
battery point and then issues shutdown commands...computer shuts
down..then the UPS shuts
2023 Jun 11
1
Upssched 100% CPU after updating Debian 12
Hi,
I have been running nut successfully for a long time with my Debian 11 server. I upgraded my server to Debian 12 today, which upgraded nut also from 2.7.4-13 to 2.8.0-7. I noticed that after upgrade there was a upssched process running and taking 100% cpu time.
I checked if there were any changes to configuration file formats with nut upgrade and only differences I noticed were a terminology
2017 Jan 09
2
NUT Client shuts down when performing runtime calibration on APC UPS
Here are the results from the output of upsc under different conditions from my Debian Test system with NUT 2.7.2 :
Normal: ups.status: OL
No wall power: ups.status: OB
Runtime calibration (started from AP9630 web interface): ups.status: OB CAL
So at this stage there is a difference!
I then connected to my QNAP and set the UPS settings on the web interface to "Shutdown server if power
2024 Oct 30
1
NUT 2.8.1-3 " Can't claim USB device [051d:0002]@0/0: Entity not found" using usbhid-ups
Hi all,
Yesterday, I bought a UPS for the first time in my life, and was eager to
dive into NUT. But not all is working as expected... I saw a similar thread
started on 18 October, but it didn't help me. (I also spent a handful of
hours searching the web for solutions, and of course read the manual and
FAQ - "queequeg".)
I tried shutting my UPS (APC "Back-UPS BX750MI
2023 Jun 13
1
Upssched 100% CPU after updating Debian 12
Hi,
I ran the strace command while upssched was 100% CPU hungry. This is what I got:
1686633611.702798 read(7, "", 1) = 0 <0.000004>
1686633611.702816 read(7, "", 1) = 0 <0.000004>
1686633611.702834 pselect6(11, [7 10], NULL, NULL, {tv_sec=1, tv_nsec=0}, NULL) = 1 (in [7], left {tv_sec=0, tv_nsec=999998800}) <0.000006>
1686633611.702862 read(7,
2023 Jun 13
1
Upssched 100% CPU after updating Debian 12
Hi,
I ran the strace command while upssched was 100% CPU hungry. This is what I got:
1686633611.702798 read(7, "", 1) = 0 <0.000004>
1686633611.702816 read(7, "", 1) = 0 <0.000004>
1686633611.702834 pselect6(11, [7 10], NULL, NULL, {tv_sec=1, tv_nsec=0}, NULL) = 1 (in [7], left {tv_sec=0, tv_nsec=999998800}) <0.000006>
1686633611.702862 read(7,
2016 May 09
2
cyberpower ups need to manully turn on the switch
HI
in centos: C="/usr/bin/upssched-cmd"
here is the output of that file:
# more /tmp/NUT.report
NUT configuration 2016-05-10 03:02:20 UTC
########### /etc/ups/nut.conf ###########
MODE=netserver
########### /etc/ups/ups.conf ###########
[cyberpower]
#driver = powerpanel
#port = auto
driver = usbhid-ups
port = auto
vendorid = 0764
desc = " My main
2017 Oct 31
0
Email Alerts for Multiple UPSs with upssched
There's supposedly another way with a custom upsmon.conf:
NOTIFYMSG type message
upsmon comes with a set of stock messages for various events. You can change them if you like.
NOTIFYMSG ONLINE "UPS %s is getting line power"
NOTIFYMSG ONBATT "Someone pulled the plug on %s"
Note that %s is replaced with the identifier of the UPS in question.
The message must be one
2018 Sep 20
3
Upssched not getting called from UPSMON
Hi, I cant seem to get my upssched to get called by upsmon. Upsmon -c fsd just shuts down without the message I set or the one in upssched-cmd
/etc/ups/upsmon.conf:
MONITOR ups6 at localhost 1 <user> <pass> master
MONITOR ups8 at localhost 1 <user> <pass> master
SHUTDOWNCMD "/sbin/shutdown -h +0"
NOTIFYCMD /usr/sbin/upssched
NOTIFYMSG
2017 Jun 26
0
Help with Elite 800VA usb UPS
Good morning again,
I have finished some tests and the driver works perfectly for shutting down
the server and a client, both Ubuntu 16.04.
I have to change the battery, I am unable to test with 100% load and now I
have 5 minutes of battery power with a load of 18%.
I am still unable to send email notifications, I have enabled all the
warnings in upsmon.conf:
NOTIFYFLAG ONLINE