Displaying 20 results from an estimated 5000 matches similar to: "UPS shuts down on NUT boot with low battery [APS Back-UPS RS 550G]"
2019 Jun 11
0
UPS shuts down on NUT boot with low battery [APS Back-UPS RS 550G]
Thanks for the reply. However these two FAQ are unfortunately not describing the situation.
- The first issue is that NUT switches off the UPS upon reboot on low battery (not that it dies because of low battery)
- The second issue is that the UPS does not recognise being online again (not that the PC does not restart)
Sent from my iPhone
> On 11 Jun 2019, at 02:03, Charles Lepple <clepple
2017 Dec 18
2
Tripp-Lite BCPERS450 shutdown/restart problems
I have a Tripp-Lite BCPERS450, connected to a system running Ubuntu
16.04.3 LTS and NUT 2.7.2-4ubuntu1.2. I had to make my own
/lib/systemd/system-shutdown/nutshutdown, but now everything is working
except for powering on and off the UPS. Regardless of the settings of
offdelay and ondelay in upsconf, and regardless of whether the AC power
is on, when I say "upsdrvctl shutdown" the UPS
2020 Sep 03
2
UPS reboots with APC UPS
Hello,
I have been using NUT for a short period of time and have some questions
regarding the UPS reboot signal that I can't figure out. Have tried some
googling and reading the DOCs but I am struggling to understand how some
variables / things are supposed to work, so would appreciate any help
with any of the following questions.
I am running NUT on standalone mode on a linux machine
2015 Jan 09
2
persistent "low battery" condition
Hello Nutters,
I'm running nut 2.7.2 on FreeBSD 10-stable (via the FreeBSD port) with
an APC Back-UPS CS 350 connected via USB. I get persistent (every few
minutes) messages logged "battery is low" but I don't understand why. I
don't think it's for the reason described in the FAQ (but I'm not 100%
sure).
In the trace output I can see that
2020 Jun 28
2
AVR750U Low Power not Triggering Shutdown
Hello,
I am having difficulty using NUT to shut down my Netgate SG-1100
(a pfSense router) when the power level of the UPS gets critically
low.
Here is some relevant information:
- OS: pfSense 2.4.5-RELEASE-p1 (FreeBSD 11.3-STABLE)
- NUT version: 2.7.4
- Installed from: pfSense package 2.7.4_7
- UPS: AVR750U (Device release number 2)
- I have included my config files, output from `upsc`, and
2009 Mar 13
7
Weird Load and Battery Temp Readings
I've acquired and installed NUT 2.4.1 on a D-Link DNS323 NAS. With
exception of Load and Battery Temp readings all works well. A upsc
ups at localhost command returns;
battery.charge: 100
battery.charge.low: 10
battery.charge.warning: 50
battery.date: 2001/09/25
battery.mfr.date: 2008/06/05
battery.runtime: 2122
battery.runtime.low: 120
battery.temperature: 3022999999999998800
battery.type:
2016 May 04
2
New UPS Support: Eaton 5S 1000
Charles,
It starts out good, then goes into a Connection timed out loop. If I can
provide any information to fix a driver I'll do my best. Here's the output:
# /usr/local/ups/bin/usbhid-ups -DD -a eaton
Network UPS Tools - Generic HID driver 0.41 (2.7.4)
USB communication driver 0.33
0.000000 debug level is '2'
0.002550 upsdrv_initups...
0.288229 Checking device
2007 Feb 26
1
Tripp Lite USB UPS
Hello all,
About a month ago Peter and Charles were kind enough to try to help me with
getting a Tripp Lite USB UPS to work with NUT. I reported quite a bit of
initial success, and then other things here fell apart. Between work, fence
building and a week-long out of town business trip, I have had to drop this
from my list of things to do lately. I am back at it, and I believe I will
have
2007 Jan 26
1
newhidups output for Geek Squad GS1285U
This took a long time because I had problems with my system. After I
reloaded my operating system several times I found I had a bad memory
module.
Here is the output from newhidups for my Geek Squad GS1285U. It just
kept repeating until I hit ctl-z. I think that this means nut will work
for this ups. My computer is not powered by the ups yet. I did not want
it to be powered down by accident.
2008 Oct 16
2
usbhid-ups works, upsc doesn't - help?
Hi, Folks,
I'm new to this admin game, and one of the hardest parts for me is
figuring out where files/programs/data are stored in the file system.
I think this is one of these situations.
I've installed NUT on my Mac OS X 10.5 server, using the macports
build. The machine is a dual processor G4 tower, connected to an APC
UPS via USB.
usbhid-ups seems to be working, see output
2016 May 28
2
Powercom INF-800 support
Hello.
Not listed as supported, so here is some info,
[root at vhost ~]# /usr/sbin/usbhid-ups -DD -a powercom
Network UPS Tools - Generic HID driver 0.38 (2.7.2)
USB communication driver 0.32
0.000000 debug level is '2'
0.001318 upsdrv_initups...
0.074753 Checking device (0529/0001) (003/002)
0.074835 Failed to open device, skipping. (Permission denied)
2006 Oct 18
2
newhidups with APC Smart-UPS 1500
I tested your fix (newhidups -DDD /dev/null) using both and APC Back-UPS
350 an APC Smart-UPS RT 2000 XL.
No more segmentation fault due to the fixed-size array.
~Jacob
-----Original Message-----
From: nut-upsdev-bounces@lists.alioth.debian.org
[mailto:nut-upsdev-bounces@lists.alioth.debian.org] On Behalf Of Peter
Selinger
Sent: Monday, October 16, 2006 12:12 PM
To: Schmier, Jacob
Cc: NUT
2015 Jan 09
0
persistent "low battery" condition
On Jan 8, 2015, at 11:43 PM, Graham Menhennitt <graham at menhennitt.com.au> wrote:
> Hello Nutters,
>
> I'm running nut 2.7.2 on FreeBSD 10-stable (via the FreeBSD port) with an APC Back-UPS CS 350 connected via USB. I get persistent (every few minutes) messages logged "battery is low" but I don't understand why. I don't think it's for the reason
2014 Apr 05
2
I can't make changes to ups.delay.shutdown to stick
Thanks Charles,
On Saturday 05 Apr 2014 12:53:06 Charles Lepple wrote:
> On Apr 5, 2014, at 7:18 AM, Mick wrote:
> > $ upsrw -s "ups.delay.shutdown"="30" iDowell at localhost
> > Username (suzy): admin
> > Password:
> > OK
>
> This command is sending the value to the UPS (via the usbhid-ups driver).
>
> > $ upsc iDowell at localhost
2009 Sep 02
6
Selftest intervall, APC Smart-UPS 750 RM
Hello
I recently switched from apcupsd to NUT2.2.2 without
any troubles.
I tried to figure out how I can configure the self-test
intervall. The command upsrw lists only the variables
battery.charge.low
battery.runtime.low
ups.delay.shutdown
ups.delay.start
The command usbhid-ups -D and the listing under
http://obsvermes.org/cgi-bin/nut/upsstats.cgi?host=apcsmart at localhost&treemode
2007 Dec 05
2
Crash when I start driver
It's been a while since I tried to use NUT, so I thought I would give it
another try. Big trouble.
The UPS is a Tripp-Lite AVR 550U. It has only a USB connector.
The computer is running Red Hat Enterprise Linux 4.
I just installed NUT version 2.2.0. I'm going through the steps in
the INSTALL document.
# cat ups.conf
[igor]
driver = usbhid-ups
port = auto
2010 Sep 17
1
Liebert PSP
Hi,
I posted about this to the list earlier this week, but it seems to
have got combined with a previous thread and lost, at least that's
what it looks like in the archive (and I didn't receive a copy as I
would have expected).
So forgive me if you've already seen this, but:
I've got a couple of LiebertPSP's connected to my equipment and I'd
like to use NUT to keep an
2010 Sep 17
1
Liebert PSP
Hi,
I posted about this to the list earlier this week, but it seems to
have got combined with a previous thread and lost, at least that's
what it looks like in the archive (and I didn't receive a copy as I
would have expected).
So forgive me if you've already seen this, but:
I've got a couple of LiebertPSP's connected to my equipment and I'd
like to use NUT to keep an
2015 Jan 12
2
persistent "low battery" condition
On 10/01/2015 00:45, Charles Lepple wrote:
> On Jan 8, 2015, at 11:43 PM, Graham Menhennitt
> <graham at menhennitt.com.au <mailto:graham at menhennitt.com.au>> wrote:
>
>> Hello Nutters,
>>
>> I'm running nut 2.7.2 on FreeBSD 10-stable (via the FreeBSD port)
>> with an APC Back-UPS CS 350 connected via USB. I get persistent
>> (every few
2013 Jun 10
2
several problems with Powercom BNT-500AP
I took the log. Here's what happened.
Broadcast Message from nut at rasp
(somewhere) at 16:18 ...
UPS BNT500AP at localhost battery needs to be replaced
occurred when for the first time value "1" was read as "UPS.PowerSummary.PresentStatus.NeedReplacement", on this line:
6409.240690 Path: UPS.PowerSummary.PresentStatus.NeedReplacement, Type: Input, ReportID: 0x0a,