Displaying 20 results from an estimated 500 matches similar to: "nutdrv_qx - Device not supported"
2016 Feb 15
1
nutdrv_qx - Device not supported
Hi
Thank you very much for the feedback. I will download and try to get it
working on the Raspberry Pi.
Regards
Tom
On Sun, Feb 14, 2016 at 1:49 AM, hyouko at gmail.com <hyouko at gmail.com> wrote:
> > I have the RCT 3KVA Axpert solar hybrid inverter. It is also known as
> the
> > MPP Solar PIP-MS series, the IPS-4000WM and the Voltronic Axpert MKS. I
> am
>
>
2016 Oct 09
0
connection pb with blazer_usb with infusec UPS
Please keep the list CC'd, thanks.
2016-10-07 8:54 GMT+02:00 MATHIEU Clement <clement.mathieu at gmail.com>:
> Hello
> thanks for your answer
> i?ve tried with nutdrv_qx driver
> and i got this result
>
> lsusb :
>
> Bus 001 Device 058: ID 0665:5161 Cypress Semiconductor USB to Serial
> Bus 001 Device 005: ID 13ee:0001 MosArt
> Bus 001 Device 004: ID
2017 Jun 09
2
Help with Elite 800VA usb UPS
Use the name from ups.conf in front of "@localhost".
?The re?sult is quite different ;)
root at artu:~# upsc Elit at artu
Init SSL without certificate database
Error: Driver not connected
> What if you try nutdrv_qx without specifying megatec? (It should
> autodetect.)
>
?Here is the result:
?
root at artu:~# upsdrvctl start
Network UPS Tools - UPS driver controller
2016 Feb 13
0
nutdrv_qx - Device not supported
> I have the RCT 3KVA Axpert solar hybrid inverter. It is also known as the
> MPP Solar PIP-MS series, the IPS-4000WM and the Voltronic Axpert MKS. I am
This device could be supported by nutdrv_qx (subdriver
'voltronic-sunny') built starting from this branch:
https://github.com/zykh/nut/tree/nutdrv_qx_voltronic-sunny_rebased+command
Please note that this subdriver is not ready
2013 Nov 22
1
nutdrv_qx does not support UPS, blazer_ups does
Hello All,
I tested our new UPS yesterday. I noticed that while the blazer_ups
drivers support this device, the newer nutdrv_qx does not. I suppose
that this should not be the case, as nutdrv_qx will replace blazer_ups(?).
Versions:
I installed Nut on Ubuntu 13.10 (64 bit) from the standard package
(2.6.4-2.3ubuntu2), and I also installed from the source tarball
(2.7.1), into a different
2015 Mar 06
0
nutdrv_atcl_usb
It seems like it works (partially?) with NUT/driver you mentioned.
I will test it more when I return home.
root at Failure:/lib/nut# ./nutdrv_qx -a test -x subdriver=fuji -u root -x
productid=0000 -x vendorid=0001 -DDDDDD
Network UPS Tools - Generic Q* USB/Serial driver 0.13 (2.7.2.5)
USB communication driver 0.32
0.000000 debug level is '6'
0.001247 upsdrv_initups...
2015 Jan 05
0
Fwd: Data stale error after short while
> Hope this helps.
It did - thanks! I managed to hack around a bit earlier and did produce the
driver binary but thought I would try from fresh with your steps and got
the binary.
Unfortunately the problem is still there... after a while connection is
lost, updates stop, and upsc reports stale data. Log attached.
What I'm thinking now is that I should run a cron job that regularly
2016 Oct 01
2
connection pb with blazer_usb with infusec UPS
Hello
i need your help regarding the following issue :
i have a hero touch ups from infosec. it is connected via USB to a raspberry pi 3.
i?ve configure ups.conf file as below
[HERO]
driver = blazer_usb
vendorid = 0665
productid = 5161
either with
port = auto
or
port = /dev/hidraw0
or
port = /dev/ttySo
the connection never works
i get the
2015 Nov 20
2
Contact-closure UPS
No progress has been made:
cable is UPS - PC
6 - 3
7 - 5
9 - 2
for ./blazer_ser -DDDDD -a infosec
0.000000 send_to_all: SETINFO driver.parameter.port "/dev/ttyS1"
0.000323 debug level is '5'
0.103068 send_to_all: SETINFO device.type "ups"
0.103104 send_to_all: SETINFO driver.version "2.7.3"
0.103118 send_to_all: SETINFO
2013 Apr 05
3
New driver for UPSes manufactured by Voltronic Power
Hi there,
I made a new driver, based on blazer, that should work with most of the
UPSes manufactured by Voltronic Power -
http://www.voltronicpower.com/oCart2/index.php?route=product/category&path=37-
and rebranded as Atlantis Land, Cablematic, EPC, FSP, Mustek, SHT,
Tuncmatik and many others (they come with a software called Viewpower -
http://www.power-software-download.com/viewpower.html )
2013 Dec 09
1
AtlantisLand don't want to wake up after the whiteout
2013/12/9 Fabio Cecamore <ceca_89 at hotmail.com>:
> and the UPS don't wake up after the whiteout..
2013/12/6 Fabio Cecamore <ceca_89 at hotmail.com>:
> desc = "AtlantisLand Host Power 851+"
Is your UPS an 'Atlantis Land Host Power 851' or an 'Atlantis Land One
Power 841+'?
The first one should be using a slighty modified version of the
2023 Jan 17
1
PR to test for users of Qx devices (blazer and nutdrv_qx)
Jim Klimov via Nut-upsuser <nut-upsuser at alioth-lists.debian.net>
>
> Cheers,
>
> One PR waiting to get into 2.8.1 release timeframe is https://github.com/networkupstools/nut/pull/1652 stemming from issue https://github.com/networkupstools/nut/issues/1279
>
> The gist of it is that "battery.voltage" and "battery.charge" were not always reported
2023 Jan 17
1
PR to test for users of Qx devices (blazer and nutdrv_qx)
Jim Klimov via Nut-upsuser <nut-upsuser at alioth-lists.debian.net>
>
> Cheers,
>
> One PR waiting to get into 2.8.1 release timeframe is https://github.com/networkupstools/nut/pull/1652 stemming from issue https://github.com/networkupstools/nut/issues/1279
>
> The gist of it is that "battery.voltage" and "battery.charge" were not always reported
2014 Jan 04
0
Problems with blazer_usb. Driver will not shut down my UPS
(Keep the list CCed)
2014/1/4 Eirik Skorstad <eskorsta at hotmail.com>:
> -----BEGIN PGP SIGNED MESSAGE-----
> Hash: SHA1
>
>
>> Assuming shutdown.return works when issued via upscmd (does it
>> work?), the problem seems to be that your UPS doesn't accept a
>> shutdown.stop when there's no shutdown pending (or, maybe, the UPS
>> doesn't
2014 Nov 02
2
nutdrv_qx and Best Power equipment
On Nov 1, 2014, at 9:28 PM, hyouko at gmail.com wrote:
> Provided that the subdriver works, I'd like to see, if possible, the logs of:
> - driver startup
> - a command that succeeds
> - a command that fails
> - q1 when online and all's ok
> - q1 on battery
> - setting pins_shutdown_mode
Attached is a log of most of these conditions.
Looks like reading the status for
2023 Jan 15
1
PR to test for users of Qx devices (blazer and nutdrv_qx)
Cheers,
One PR waiting to get into 2.8.1 release timeframe is
https://github.com/networkupstools/nut/pull/1652 stemming from issue
https://github.com/networkupstools/nut/issues/1279
The gist of it is that "battery.voltage" and "battery.charge" were not
always reported correctly with nutdrv-qx driver (might be handled better by
blazer drivers though), and the overrides
2017 Jun 08
2
Help with Elite 800VA usb UPS
Thank you for your reply Charles,
this is the "upsc" result:
root at artu:~# upsc ups at localhost
Init SSL without certificate database
Error: Unknown UPS
Trying with nutdrv_qx, protocol megatec the driver does not start...
2017-06-08 14:47 GMT+02:00 Charles Lepple <clepple at gmail.com>:
> On Jun 7, 2017, at 12:54 AM, Andrea de Lutti <adelutti at gmail.com> wrote:
2013 Jun 23
0
New driver for UPSes manufactured by Voltronic Power
Hello,
I?m looking for the protocol for Voltronic power inverter (Axpert MKS 24V).
Now I?m finding your e-mail communication:
http://lists.alioth.debian.org/pipermail/nut-upsdev/2013-April/006431.html
where is a link to Voltronic_Power_UPS_Protocol.pdf
Is there any *.pdf document for the Voltronic power photovoltaic inverters ?
2014 Jan 03
3
Problems with blazer_usb. Driver will not shut down my UPS
-----BEGIN PGP SIGNED MESSAGE-----
Hash: SHA1
Hi there!
I don't know if you are able to help me. Have tried almost everything
at this point..
I recently switched from a BlueWalker(Powerwalker?) PW UPS VI2000 LCD
2000VA offline UPS to a BlueWalker(Powerwalker?) PW UPS VFI 1500 LCD
1500VA Online UPS.
Seems like the driver is accepting both, however, the shutdown command
wont work. And this
2013 Dec 09
0
AtlantisLand don't want to wake up after the whiteout
Thanks for your reply Hyouko,
these are the actual not working parameters:
driver.parameter.offdelay: 60
driver.parameter.ondelay: 5
ups.delay.shutdown: 60
ups.delay.start: 300
and the UPS don't wake up after the whiteout..
My UPS is not so old :(
Il 09/12/2013 16.04, hyouko at gmail.com ha scritto:
> 2013/12/6 Fabio Cecamore <ceca_89 at hotmail.com>:
>> Hi all,