Displaying 20 results from an estimated 3000 matches similar to: "Loses connection after a month or so"
2010 Jan 09
2
problem with mailing (nut 2.4.1 and a powermust650 -> megatec_usb)
Hello guys
Yesterday i started do configure my Mustek Powermust650 with nut using
the megatec_usb driver. Everything works fine except for the mailing
when something happens. My upsmon looks like this:
MONITOR powermust650 at localhost 1 local controller master
MINSUPPLIES 1
SHUTDOWNCMD "/sbin/shutdown -h +0"
NOTIFYCMD /root/upsmailer
POLLFREQ 10
POLLFREQALERT 5
HOSTSYNC 15
2015 Aug 31
0
Loses connection after a month or so
On Aug 29, 2015, at 3:11 AM, paul at smithp.co.uk wrote:
>
> Is there a way (has anyone done it) to reboot (not shutdown!!) the host if communications to the UPS fails ? I want to automatically reboot my Pi after a couple of minutes of no communications.
>
> Has anyone done this? Is there a setting that I can add to monitor nut or the usb subsystem and find out that comms has
2017 Jun 09
2
Apple Mac slave
On Thu, 8 Jun 2017, Robbie van der Walle wrote:
> After the first test and the NAS is restarted I had to change the
> setting battery.charge.low again to 80?
Does the NAS DSM reset battery.charge.low to 10 or is it internal to the
UPS? You will have to experiment by disconnecting the UPS control lead
from the NAS and connecting it (if possible) to the Mac. After setting to
80 and a
2006 Feb 14
3
Master privileges unavailable on UPS
Hello all,
I'm having problems with what I'm told should be a straightforward
issue.
The message in /var/log/daemon is:
<quote>
Feb 13 10:37:57 lupin upsmon[31324]: Master privileges unavailable on
UPS [lupin1500AVR@localhost]
2006 Jul 11
2
notifycmd problem
hello,
i've got a problem with the notifycmd
here is a part of my upsmon.conf :
NOTIFYCMD /usr/local/ups/bin/nut_notify
NOTIFYMSG ONLINE "UPS %s is getting line power"
NOTIFYMSG ONBATT "UPS %s is on battery"
NOTIFYMSG REPLBATT "The UPS %s battery is bad and needs to be replaced"
NOTIFYMSG LOWBATT "UPS %s is being shutdown by the master"
NOTIFYMSG FSD
2023 May 27
2
unable to connect to APC UPS Connection Refused
I've not been able to connect to my ups using NUT 2.7.4 or NUT 2.8.0.
2.7.4 was installed as a package, 2.8.O was compiled from source.
I've messed with permissons, everything is root:root and has the approprate read/execute permissons. I've tried two differnt UPS(es) APC & CyperPower. I'm running PI OS (Raspbian) on a Raspberry Pi3 model B. The port 3493 is open (UFW). I can
2017 Oct 18
2
debian 8 "jessie" nut 2.7.2 slaves not shutting down
OS name and version,
MASTER SYSTEM has three APC smart UPS 3000 UPS connected via USB
debian 8 "jessie" Linux pdxvhtst01 3.16.0-4-amd64 #1 SMP Debian 3.16.43-2+deb8u5 (2017-09-19) x86_64 GNU/Linux
SLAVE SYSTEMS monitoring MASTER via IP
debian 8 "jessie" Linux geaaetst01
2006 Aug 25
2
suse linux and nut
hi
i bought a ultra ULT31502 ups
someone seem able to run this ups with nut
just see Dean thread on:
http://www.tigerdirect.com/applications/searchtools/item-details.asp?EdpNo=770423&Tab=11&NoMapp=0
i use suse 10.1, i installed nut
the ups is connected directely to my computer with an usb cable
lsusb return
Bus 001 Device 004: ID 0d9f:0001 Powercom Co., Ltd
with lsmod, i can see
2011 Sep 02
2
NUT 2.6.1+ Windows 2008 R2 - NOTIFYCMD not being called
Hi All,
I'm using a recent post 2.6.1 build provided by Fred (executables have modified date of 9th August)
I have configured upsmon.conf with :-
NOTIFYCMD C:\NUT\etc\NotifyCmd.bat
and :-
NOTIFYFLAG ONLINE SYSLOG+EXEC
NOTIFYFLAG ONBATT SYSLOG+EXEC
NOTIFYFLAG LOWBATT SYSLOG+EXEC
NOTIFYFLAG FSD SYSLOG+EXEC
NOTIFYFLAG COMMOK SYSLOG+EXEC
NOTIFYFLAG COMMBAD SYSLOG+EXEC
2015 Oct 27
2
The system doesn't shutdown
Yes, that was the power off test. However the upssched-cmd script gave
absolutely no signs of activity. Even it's logger lines don't show up in
journalctl. No any permission error messages - nothing. Only the 2 messages
from upsmon - on battery and then on line power.
Here is the nut-report:
http://www.filehosting.org/file/details/518300/NUT.report
---
George Anchev
On Tue, Oct 27,
2006 Jan 09
2
Master privileges unavailable
Hi,
I'm using debian sarge on my server and connected a MGE-ups ellipse via
the serial port.
I searched the internet for the answer, but can't find it.
My config files:
<upsd.users>
[admin]
password = pwd
allowfrom = 127.0.0.1/32
actions = set
instcmds = all
[upsmon]
password = pwd
allowfrom = 127.0.0.1/32 10.0.0.224/32
upsmon master
[upsslave]
password
2012 Jan 06
1
upsmon+snmp-ups does not shut down system
I've googled and RTFM'ed, but still can't solve this one. I hope you folks can.
This affects my entire computer cluster, but let's start simple: I've got a
computer running NUT; OS is Scientific Linux 5.5; kernel 2.6.18-274.12.1.el5xen.
It connects to an APC SMART-UPS via an APC SmartCard using the snmp-ups driver.
It generally works: upsmon will detect if the battery is low
2017 Oct 31
2
Email Alerts for Multiple UPSs with upssched
Ah! So I can detect the source UPS in the upssched.conf and pass it as a distinct event to the shell script. That sounds like an excellent approach.
Thanks!
GMH
From: O'Shaughnessy, Mike [mailto:Mike.OShaughnessy at gd-ms.com]
Sent: Tuesday, October 31, 2017 12:46 PM
To: Garrett Michael Hayes <Garrett at VerbalImaging.com>; nut-upsuser at lists.alioth.debian.org
Subject: RE: Email
2015 Feb 09
2
About your driver NUTDRV_ATCL_USB(8) for install
On Feb 9, 2015, at 6:48 AM, PERE (yahoo.es) <pererivers at yahoo.es> wrote:
> 0.028188 Can't set USB configuration: could not set config 1: Device or resource busy
> 0.029246 detached kernel driver from USB device...
> 0.030559 USB device [0001:0000] opened
> 0.866216 read: (8 bytes) => 03 00 00 00 00 00 00 00
> 0.866413 reply[0] = 0x03
2014 Sep 03
2
howto force shutdown if nut-snmp Communications lost
Hallo,
I have one ups with snmp and any ups without snmp.
Shutdown works while network online.
But some batteries are empty, so that the communication break early.
Howto force shutdown if nut-snmp Communications lost?
My 1. suggestion was option DEADTIME, but seem to be information only. (s. below)
Any suggestions?
The last way would be a ugly cronjob (like: ping || shutdown).
regards Heiko
2017 Aug 12
2
Keep on losing communication: Raspberry Pi, CyberPower PR1500LCD
Everything runs fine for several hours, then communication is lost and nut
doesn't reestablish communication on its own.
Running sudo upsdrvctl stop then sudo upsdrvctl start reestablishes
communication.
OS Version: Linux piaware 4.9.35-v7+ #1014 SMP Fri Jun 30 14:47:43 BST 2017
armv7l GNU/Linux
Nut Version: 2.7.2-4
Nut Installation Method: apt
Device: CyberPower PR1500LCD
Uses
? ?
Generic
2023 Jun 11
1
Upssched 100% CPU after updating Debian 12
Hi,
I have been running nut successfully for a long time with my Debian 11 server. I upgraded my server to Debian 12 today, which upgraded nut also from 2.7.4-13 to 2.8.0-7. I noticed that after upgrade there was a upssched process running and taking 100% cpu time.
I checked if there were any changes to configuration file formats with nut upgrade and only differences I noticed were a terminology
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
2017 Apr 03
3
battery not installed, but battery still 100% and NUT 2.7.2-4 does not catch this and report a error
On Mon, 3 Apr 2017, Gene Heskett wrote:
>>
> Nut, IIRC, can do a periodic battery test by putting it offline, using
> the battery, for a predetermined length of time, weekly, monthly etc,
We definitely don't want that in this instance either! (Unless it is a
dual PS server.) We want the ALARM that the nut driver is generating,
and upsd is passing on - to be acted on in some
2015 Feb 09
0
About your driver NUTDRV_ATCL_USB(8) for install
Dear Chales,
Thanks for your quick reply.
I have Raspberry with last Kernel [Linux pi1 3.18.6+ #753 PREEMPT Sun Feb 8
14:47:22 GMT 2015 armv6l GNU/Linux]
If <upsdrvctl>, <upsd> and <upsmon> are stopped <nutdrv_atcl_usb> Works well
without any error as "Device or resource busy".
If I run <upsc> command never receive any value from my ups <upsc
ups at
2012 Jan 28
2
No shutdown on empty battery
Hello,
I set up a FreeBSD 8.2 system with nut 2.6.1 and a Powerware 5115
connected by RS-232. I expected this setup to shut down before running
out of battery power, but I either missed some important configuration
or something else went wrong:
The syslog says:
Jan 9 05:03:42 b1 upsmon[67752]: UPS upsb1 at localhost on battery
Jan 9 05:04:42 b1 upsmon[67752]: UPS upsb1 at localhost on line