similar to: NUT on Windows, Wall->message.exe

Displaying 20 results from an estimated 2000 matches similar to: "NUT on Windows, Wall->message.exe"

2014 Feb 28
0
NUT on Windows, Wall->message.exe
On Feb 25, 2014, at 1:13 AM, Kris Jordan wrote: > If there is a next Windows release, perhaps the default NOTIFYFLAG's should be adjusted? > > NOTIFYFLAG ONLINE SYSLOG > NOTIFYFLAG ONBATT SYSLOG > NOTIFYFLAG LOWBATT SYSLOG > NOTIFYFLAG FSD SYSLOG > NOTIFYFLAG COMMOK SYSLOG > NOTIFYFLAG COMMBAD SYSLOG > NOTIFYFLAG SHUTDOWN SYSLOG > NOTIFYFLAG
2010 Jan 09
2
problem with mailing (nut 2.4.1 and a powermust650 -> megatec_usb)
Hello guys Yesterday i started do configure my Mustek Powermust650 with nut using the megatec_usb driver. Everything works fine except for the mailing when something happens. My upsmon looks like this: MONITOR powermust650 at localhost 1 local controller master MINSUPPLIES 1 SHUTDOWNCMD "/sbin/shutdown -h +0" NOTIFYCMD /root/upsmailer POLLFREQ 10 POLLFREQALERT 5 HOSTSYNC 15
2017 Jun 09
2
Apple Mac slave
On Thu, 8 Jun 2017, Robbie van der Walle wrote: > After the first test and the NAS is restarted I had to change the > setting battery.charge.low again to 80? Does the NAS DSM reset battery.charge.low to 10 or is it internal to the UPS? You will have to experiment by disconnecting the UPS control lead from the NAS and connecting it (if possible) to the Mac. After setting to 80 and a
2023 May 27
2
unable to connect to APC UPS Connection Refused
I've not been able to connect to my ups using NUT 2.7.4 or NUT 2.8.0. 2.7.4 was installed as a package, 2.8.O was compiled from source. I've messed with permissons, everything is root:root and has the approprate read/execute permissons. I've tried two differnt UPS(es) APC & CyperPower. I'm running PI OS (Raspbian) on a Raspberry Pi3 model B. The port 3493 is open (UFW). I can
2012 Jan 28
2
No shutdown on empty battery
Hello, I set up a FreeBSD 8.2 system with nut 2.6.1 and a Powerware 5115 connected by RS-232. I expected this setup to shut down before running out of battery power, but I either missed some important configuration or something else went wrong: The syslog says: Jan 9 05:03:42 b1 upsmon[67752]: UPS upsb1 at localhost on battery Jan 9 05:04:42 b1 upsmon[67752]: UPS upsb1 at localhost on line
2011 Sep 02
2
NUT 2.6.1+ Windows 2008 R2 - NOTIFYCMD not being called
Hi All, I'm using a recent post 2.6.1 build provided by Fred (executables have modified date of 9th August) I have configured upsmon.conf with :- NOTIFYCMD C:\NUT\etc\NotifyCmd.bat and :- NOTIFYFLAG ONLINE SYSLOG+EXEC NOTIFYFLAG ONBATT SYSLOG+EXEC NOTIFYFLAG LOWBATT SYSLOG+EXEC NOTIFYFLAG FSD SYSLOG+EXEC NOTIFYFLAG COMMOK SYSLOG+EXEC NOTIFYFLAG COMMBAD SYSLOG+EXEC
2017 Oct 31
2
Email Alerts for Multiple UPSs with upssched
Ah! So I can detect the source UPS in the upssched.conf and pass it as a distinct event to the shell script. That sounds like an excellent approach. Thanks! GMH From: O'Shaughnessy, Mike [mailto:Mike.OShaughnessy at gd-ms.com] Sent: Tuesday, October 31, 2017 12:46 PM To: Garrett Michael Hayes <Garrett at VerbalImaging.com>; nut-upsuser at lists.alioth.debian.org Subject: RE: Email
2020 Apr 28
2
Tripp-Lite SMART1500LCD: powers off with /etc/killpower...then powers back on...
Hi Everyone, I recently bought a Tripp-Lite SMART1500LCD for my Linux Mint 19.3 machine, connected via a USB cable. I installed Nut 2.7.4 from the Mint package repository via sudo apt update && sudo apt install nut. Everything works great: NUT issues low battery warning when it reaches the set low battery point and then issues shutdown commands...computer shuts down..then the UPS shuts
2023 Jun 11
1
Upssched 100% CPU after updating Debian 12
Hi, I have been running nut successfully for a long time with my Debian 11 server. I upgraded my server to Debian 12 today, which upgraded nut also from 2.7.4-13 to 2.8.0-7. I noticed that after upgrade there was a upssched process running and taking 100% cpu time. I checked if there were any changes to configuration file formats with nut upgrade and only differences I noticed were a terminology
2006 Jul 11
2
notifycmd problem
hello, i've got a problem with the notifycmd here is a part of my upsmon.conf : NOTIFYCMD /usr/local/ups/bin/nut_notify NOTIFYMSG ONLINE "UPS %s is getting line power" NOTIFYMSG ONBATT "UPS %s is on battery" NOTIFYMSG REPLBATT "The UPS %s battery is bad and needs to be replaced" NOTIFYMSG LOWBATT "UPS %s is being shutdown by the master" NOTIFYMSG FSD
2012 Nov 09
1
181 message.exe processes
Windows Server 2000 R2 Standard edition x64 I found a bunch of message.exe processes running on this system (181 of them in total). The UPS was going on-battery a lot! There is no attached screen and I don't see any message boxes when I RDP. Do I just set NOTIFYCMD to something nonsensical to stop it from running message.exe? It would be nice if the Windows defaults were shown in the
2015 Oct 29
2
The system doesn't shutdown
P.S.2 Today I experienced something weird. As I was working, the system started a shutdown and did shut down, then the UPS got powered off and then back on - an expected behavior for a power fail situation. However there was no power failure! I ran nut-journal to check what happened: Previous complete boot through shutdown Oct 29 10:09:33 i7 upsdrvctl[1966]: Using subdriver: MGE HID
2012 Jan 06
1
upsmon+snmp-ups does not shut down system
I've googled and RTFM'ed, but still can't solve this one. I hope you folks can. This affects my entire computer cluster, but let's start simple: I've got a computer running NUT; OS is Scientific Linux 5.5; kernel 2.6.18-274.12.1.el5xen. It connects to an APC SMART-UPS via an APC SmartCard using the snmp-ups driver. It generally works: upsmon will detect if the battery is low
2017 Jan 11
3
NUT Client shuts down when performing runtime calibration on APC UPS
I've setup nas4free (latest version 11.0.0.4, which has NUT 2.7.4) in a VM and configured it via webinterface to my APC UPS and set "shutdown mode" to "UPS goes on battery" with a timer of 30s. Then I started runtime calibration on the UPS and after 30s nas4free has shut down! I think this is not the correct behavior, since the status was "OB CAL". The system
2017 Oct 18
2
debian 8 "jessie" nut 2.7.2 slaves not shutting down
OS name and version, MASTER SYSTEM has three APC smart UPS 3000 UPS connected via USB debian 8 "jessie" Linux pdxvhtst01 3.16.0-4-amd64 #1 SMP Debian 3.16.43-2+deb8u5 (2017-09-19) x86_64 GNU/Linux SLAVE SYSTEMS monitoring MASTER via IP debian 8 "jessie" Linux geaaetst01
2015 Oct 27
2
The system doesn't shutdown
Yes, that was the power off test. However the upssched-cmd script gave absolutely no signs of activity. Even it's logger lines don't show up in journalctl. No any permission error messages - nothing. Only the 2 messages from upsmon - on battery and then on line power. Here is the nut-report: http://www.filehosting.org/file/details/518300/NUT.report --- George Anchev On Tue, Oct 27,
2006 Feb 14
3
Master privileges unavailable on UPS
Hello all, I'm having problems with what I'm told should be a straightforward issue. The message in /var/log/daemon is: <quote> Feb 13 10:37:57 lupin upsmon[31324]: Master privileges unavailable on UPS [lupin1500AVR@localhost]
2015 Feb 09
0
About your driver NUTDRV_ATCL_USB(8) for install
Dear Chales, Thanks for your quick reply. I have Raspberry with last Kernel [Linux pi1 3.18.6+ #753 PREEMPT Sun Feb 8 14:47:22 GMT 2015 armv6l GNU/Linux] If <upsdrvctl>, <upsd> and <upsmon> are stopped <nutdrv_atcl_usb> Works well without any error as "Device or resource busy". If I run <upsc> command never receive any value from my ups <upsc ups at
2007 Nov 09
2
UPSSched UPSNAME env variable
Hi everybody, i'm trying to use the UPSNAME environment variable within the script launched by upssched, and although it is correctly written and thus read by my script, it doesn't get updated when multiple UPSes are configured. To be more precise i'm monitoring 2 UPSes and using AT *EVENT* * *OPERATION* *handle *to manage events in upssched.conf. Am i wrong somewhere? I'm
2017 Jun 16
3
Help with Elite 800VA usb UPS
Thanks mates, as suggested I have added runtimecal = 240,100,720,50 default.battery.voltage.low = 10.4 default.battery.voltage.high = 13.8 (the actual charging voltage) In ups.conf I have also added the startup procedure in rc.local file, everything is fine... I have only to make a deep test. Is there a way to add a NOTIFYMSG value for the battery test? Thank you lots Andrea