Displaying 14 results from an estimated 14 matches for "ups0".
Did you mean:
ups
2009 Dec 02
5
Timers fireing too early
...Could I be missing some dependency, external application, which upsmon uses as a timer?
(A side issue is that it's not using the correct variable when passing to upssched-cmd, but uses the notify text itself, "ONBATT", this can be seen in the last line from, messages, $1 is "UPS ups0 at localhost on line power", but this is not important for me, but may be used to explain why the timer is not working)
ONBATT
Dec 2 18:48:56 storage01 upsmon[3603]: ONBATT
Dec 2 18:48:56 storage01 wall[4371]: wall: user root broadcasted 1 lines (8 chars)
Dec 2 18:48:56 storage01 upssched...
2013 Sep 21
2
Smart-UPS staying in OB after power return
...al, googled much, read most NUT manuals, read up to
'queequeg', asked on APC forums, etc.
The most distressing problem is the UPS stays OB after removing and
reapplying utility power. When power is removed, the UPS goes OB and
upsmon detects the power failure no problem, reporting
's0-ups0 at localhost is on battery'. But when power is restored, there is
no clicking of contactors, no switch back to OL, and no detection by
upsmon that power is restored. The UPS can be manually put back OL with
'upscmd load.on'. I would expect the UPS go back OL automatically,
though; am...
2013 Sep 21
0
Smart-UPS staying in OB after power return
...UT manuals, read up to
> 'queequeg', asked on APC forums, etc.
>
> The most distressing problem is the UPS stays OB after removing and
> reapplying utility power. When power is removed, the UPS goes OB and
> upsmon detects the power failure no problem, reporting
> 's0-ups0 at localhost is on battery'. But when power is restored, there is
> no clicking of contactors, no switch back to OL, and no detection by
> upsmon that power is restored. The UPS can be manually put back OL with
> 'upscmd load.on'. I would expect the UPS go back OL automatica...
2013 Apr 18
4
Not receiving real data from a Eaton E series DX 1000H UPS
...ne is 2.6.3-1ubuntu2. Both of them are installed from the repositories.
I tried adding "pollinterval=20" to ups.conf, "MAXAGE25" to upsd.conf
and "DEADTIME25" to upsmon.conf but I still get stale errors in syslog
and null information about all the stats.
#ups.conf
[ups0]
driver = mge-utalk
port = /dev/ttyS0
pollinterval = 20
The logs are in the attached file.
-------------- next part --------------
An HTML attachment was scrubbed...
URL: <http://lists.alioth.debian.org/pipermail/nut-upsuser/attachments/20130418/59ae715a/attachment.html>
-------------- next...
2013 Sep 22
1
Smart-UPS staying in OB after power return
...s Jordan wrote:
> John Morris wrote, On 9/21/2013 11:28 AM:
>> The most distressing problem is the UPS stays OB after removing and
>> reapplying utility power. When power is removed, the UPS goes OB and
>> upsmon detects the power failure no problem, reporting
>> 's0-ups0 at localhost is on battery'. But when power is restored, there is
>> no clicking of contactors, no switch back to OL, and no detection by
>> upsmon that power is restored. The UPS can be manually put back OL with
>> 'upscmd load.on'. I would expect the UPS go back O...
2010 Feb 04
0
Powercom BNT-800AP
...ars correct, as the input stays steady,
and the output shows ~5V.
For the above, the Powercom upsmon software appears to special-case
those ~5/15V results, and on the next update, report it as 0V. I have
no idea how to even special-case the screwy input/output-swapping
behavior...
./powercom -a ups0 -DDD
Network UPS Tools - PowerCom protocol UPS driver 0.12 (2.4.1-2308)
0.000000 debug level is '3'
0.001406 Flow control disable
0.150003 Detected: BNT-other-500AP , 120V
0.153986 Values of arguments:
0.154001 manufacturer : 'PowerCom'...
2006 Nov 21
1
MGE Nova 1100 AVR + upssched
...f it is disconnected just for a second, or even
worse, when I got low tension.
So, mail notifications are well configured, I guess...
I think the problem is in upssched.
I'm new to this, so it could be a stupid thing that I'm missing...
My configurations files are like this:
*ups.conf:*
[ups0]
driver = mge-shut
port = /dev/ttyS0 #It's serial, not USB
*upsmon.conf:*
# NOTIFYCMD <command>
NOTIFYCMD /usr/local/ups/bin/notifyme
# POWERDOWNFLAG - Flag file for forcing UPS shutdown on the master system
POWERDOWNFLAG /etc/killpower
# Th...
2013 May 07
2
Problems with USB-serial converters -- please advise on code fix
Hello!
I've ran into this annoying issue when setting up a new server. I have an APC
SmartUPS hooked up on a USB-serial converter on /dev/ttyUSB0.
This works nicely, until:
hub 3-0:1.0: port 1 disabled by hub (EMI?), re-enabling...
pl2303 ttyUSB0: pl2303 converter now disconnected from ttyUSB0
usb 3-1: pl2303 converter now attached to ttyUSB1
apcsmart gets into an infinite loop of this:
2020 Apr 10
1
Tripp Lite AVR900U
...ce 003: ID 09ae:3024 Tripp Lite AVR900U
Contents of /etc/ups/ups.conf:
> [tripplite]
> driver = usbhid-ups
> port = auto
Contents of /etc/udev/rules.d/50-ups.rules:
> SUBSYSTEM=="usb", ATTR{idVendor}=="09ae", ATTR{idProduct}=="3024", SYMLINK+="ups0", GROUP="nut"
Post-configuration, I rebooted then ran upsdrvctl and received the
following output:
> $ upsdrvctl start
> Network UPS Tools - UPS driver controller 2.7.4
> Network UPS Tools - Generic HID driver 0.41 (2.7.4)
> USB communication driv...
2013 Apr 22
0
Fwd: Not receiving real data from a Eaton E series DX 1000H UPS
...t; repositories.
>
> I tried adding "pollinterval=20" to ups.conf, "MAXAGE25" to
> upsd.conf and "DEADTIME25" to upsmon.conf but I still get stale
> errors in syslog and null information about all the stats.
>
> #ups.conf
> [ups0]
> driver = mge-utalk
> port = /dev/ttyS0
> pollinterval = 20
>
> The logs are in the attached file.
>
>
> mge-utalk was fixed in the development branch, but was not yet released.
> You can download from github either the tree or just the patch:
> https...
2019 May 13
1
Update to user-manual.html#Configuration_notes
...1)
It's most likely a problem with permissions for accessing the device. You can
fix that by specifying an udev rule that sets the correct group:
/etc/udev/rules.d/50-ups.rules
SUBSYSTEM=="usb", ATTR{idVendor}=="XXXX", ATTR{idProduct}=="YYYY",
SYMLINK+="ups0", GROUP="nut"
Where idVendor and idProduct are the device manufacturer and product ID. You
can see these either in the error output [XXXX:YYYY] or by using lsusb.
After this is done, reload and retrigger udev rules by issuing this command:
# udevadm control --reload-rules &&...
2005 Dec 08
2
Fw: NUT hidups dont working on new linux kernels
I am forwarding the below message. Does anybody on this list know
anything about this problem?
Petr - perhaps you should switch from the "hidups" to the "newhidups"
driver. I believe it supported the APC Back UPS even in NUT 2.0.2, and
it certainly does so in the Development version that you can get from
CVS (see the NUT download page).
Also, could you post the output of
2006 May 11
1
Tripp Lite OMNI1000LCD
.... I downloaded NUT 2.0.3 and
built it from source using
./configure --prefix /usr/local --with-statepath=/var/run/nut/ \
--with-pidpath=/var/run/nut/ --sysconfdir=/etc/nut --with-user=nut
With NUT installed and the UPS plugged in to a USB port on the machine:
kaylee# cat /etc/nut/ups.conf
[ups0]
driver = tripplite_usb
port = auto
product = "TRIPP LITE UPS"
productid = 2005
serial = "692195 A"
kaylee# tripplite_usb -a ups0 -DDDDD -u root
Network UPS Tools - Tripp Lite OMNIVS and SMARTPRO driver 0.6 (2.0.3)
Warning: This is an experimental driver.
Some feature...
2011 Oct 06
1
Differences between USB and serial on an MGE Pulsar Evolution 3000
...rial (using mge-shut)
-----------------------
battery.charge: 100
battery.charge.low: 20
battery.runtime: 5400
device.mfr: MGE UPS SYSTEMS
device.model: Pulsar Evolution 3000
device.serial: AF3E39202
device.type: ups
driver.name: mge-shut
driver.parameter.pollinterval: 2
driver.parameter.port: /dev/ups0
driver.version: 2.6.2
driver.version.internal: 0.69
input.frequency: 50
input.voltage: 240
outlet.1.autoswitch.charge.low: 0
outlet.1.delay.shutdown: -1
outlet.1.delay.start: -1
outlet.1.desc: PowerShare Outlet 1
outlet.1.id: 1
outlet.1.switch: 1
outlet.1.switchable: 1
outlet.2.autoswitch.charge.lo...