2024 Dec 22
1
clearing the 'Replace Battery' on Eaton 5PX
...766015/4
I repeated the "drain the capacitors" procedure at the top of my first email.
Interesting: the network setting persisted - I could get the UPS via the web UI - it still used the same IP address.
However, connecting to the serial console, I get:
Local database initialisation
- state_bind_error -
* END state_bind_error *
Local database initialisation
- state_bind_error -
* END state_bind_error *
Local database initialisation
... repeat
>From the host connected to the UPS via the USB cable:
$ upsc ups02
Error: Driver not connected
I suppose they might all be related. It's dinner...
2024 Dec 22
1
clearing the 'Replace Battery' on Eaton 5PX
I thought I could clear the Eaton 5PX battery message. I've failed.
The following is based on https://haefelfinger.ch/posts/2020/2020-09-23-reset-battery-alert-eaton-5p-ups/
I shutdown the UPS. I disconnected it from power. I disconnected both the main battery and the external battery pack. I pressed the power on button several times, until the clicking stopped....
I waited 10 minutes.